Climate Accord Maturity Model: A Guide to Emissions Reduction in Digital Infrastructure, Version 1.1

iMasons Climate Accord (Infrastructure Masons) · iMasons Climate Accord

A voluntary maturity framework (levels 0-4) for decarbonizing data center portfolios in three areas: power, materials, and MEP and IT equipment.

On this page

Overview

Version 1.1 (February 2025) of the iMasons Climate Accord model offers a voluntary maturity framework for decarbonizing data center portfolios. It covers three areas: carbon intensity of power, embodied carbon of materials, and embodied carbon of MEP and IT equipment. The introduction notes that data centers used about 460 TWh in 2022, nearly 2% of global electricity.

For power, levels 1-4 are 40-59%, 60-79%, 80-99% and 100% annual renewable supply, with hourly match of 20-39%, 40-59%, 60-79% and 80% or more. Carbon-free power locality steps through same region, same interconnected grid, within 100 miles and collocated. Grid benefit (export, reused waste heat or demand-response curtailment as a share of energy) is 1-2%, 3-5%, 6-9% and 10% or more.

For embodied carbon, measurement levels start with spend-based and then move to 20%, 80% and 100% of the portfolio measured by activity-based methods. Reduction targets against baseline are 1-15%, 16-30%, 30-45% and 45% or more for materials, and 1-10%, 11-20%, 21-30% and 30% or more for MEP and IT equipment. Data quality is tiered by the share of total GWP from supplier-specific LCA/EPD data: high quality means 50-100%, and CIBSE TM65 bill-of-materials proxies are allowed for MEP/IT only at low data quality. The document is a voluntary framework, not a legal requirement or standard. Related documents are CLC/TS 50600-5-1, ISO/IEC 30134-7, ISO/IEC 21836, CIBSE TM65 and ISO 14025.

Key points

  1. Power levels 1-4: 40-59%, 60-79%, 80-99%, 100% annual renewable supply; hourly match 20-39%, 40-59%, 60-79%, 80% or more.
  2. Carbon-free power locality levels: same region, same interconnected grid, within 100 miles, collocated.
  3. Grid benefit (export, reused waste heat or demand-response curtailment as a share of energy): 1-2%, 3-5%, 6-9%, 10% or more.
  4. Embodied carbon measurement levels: spend-based, then 20%, 80%, 100% of portfolio measured by activity-based methods.
  5. Reduction targets: materials 1-15%, 16-30%, 30-45%, 45% or more; MEP and IT equipment 1-10%, 11-20%, 21-30%, 30% or more.
  6. High data quality is 50-100% of total GWP from supplier-specific LCAs/EPDs; CIBSE TM65 BOM proxies are allowed for MEP/IT only at low data quality.
  7. Data centers used about 460 TWh in 2022, nearly 2% of global electricity.

Using it in design

  • Record equipment embodied carbon in kgCO₂e and identify whether it comes from an EPD, TM65 or spend-based estimate. Sum the design total and report the share covered by supplier-specific EPDs.
  • In a sustainability panel, score designs against the iCA power and materials levels (for example hourly CFE match, percentage of embodied carbon measured).
  • State the data-quality tier (share of supplier-specific LCA/EPD data) explicitly in every report.

Who should read it

Sustainability managers and design teams preparing a carbon reduction roadmap for a data center portfolio.

Related standards

  • CLC/TS 50600-5-1
  • ISO/IEC 30134-7
  • ISO/IEC 21836
  • CIBSE TM65
  • ISO 14025

Publication details

Authors
iMasons Climate Accord
Publisher
iMasons Climate Accord (Infrastructure Masons)
Year
2025
Document number
v1.1 (February 2025)
Document language
English
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

iMasons Climate Accord (2025). Climate Accord Maturity Model: A Guide to Emissions Reduction in Digital Infrastructure, Version 1.1. iMasons Climate Accord (Infrastructure Masons). v1.1 (February 2025). https://static.swapcard.com/public/files/b38001c14e024951b4709c5cc8c93202.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cost studies in SoSo CAD

Calculate equipment cost, energy cost and total cost of ownership (TCO) from the design’s quantities and your own price assumptions.

CAPEX and TCO estimates in the SoSo CAD cost workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.