Immersion cooling fluid comparison using a single-phase immersion/liquid technique for data centers

Applied Thermal Engineering (Elsevier BV) · Ayoub Ruichek, Mohamad Hnayno et al.

The authors test four single-phase dielectric immersion fluids (Shell SL 3568, Fuchs FES 822-6542, Motul EGEN 100R8 and TotalEnergies BioLife 4) in a hybrid server: CPUs cooled by direct-to-chip water blocks, the rest of the board (RAM, NVMe, SSD) passively immersed in the fluid.

CC BY 4.0: share with attribution

On this page

Overview

The study asks how different immersion fluids perform in a hybrid server. Fluids were ranked with the OCP Immersion Cooling Sub-Project Figure of Merit for natural convection (FOM1), component temperatures were measured, and a CFD model was validated for wider fluid screening; the CFD model matched experiments with a maximum temperature deviation of 10.7% (NVMe average temperature). SL 3568 properties: density 838/812/773 kg/m³ and kinematic viscosity 406/43/7.6 cSt at 0/40/100 °C, with thermal conductivity 0.142-0.134 W/m·K.

Roughly doubling FOM1 (BioLife 4 versus SL 3568) reduces the Prandtl number by about a factor of ten. A near doubling of FOM1 lowered average fluid temperature by approximately 7.7 °C. With roughly doubled FOM1, immersed RAMs, NVMes and SSDs ran about 6.7, 6.4 and 5.9 °C cooler respectively. Higher-FOM1 fluids cool immersed components better.

Unexpectedly, they make cold-plated CPUs hotter: CPU temperatures were highest with high-FOM1 fluids, attributed to dielectric fluid infiltrating the TIM between CPU and water block and reducing TIM viscosity by at least 94.4%. This is a compatibility risk for hybrid immersion/direct liquid cooling designs.

Limits: a single hybrid server and four commercial fluids; results are for this TIM (KP98) and server and must be re-verified for other TIM and fluid pairings. It shows a trade-off between cooling performance and TIM compatibility.

Key points

  1. Roughly doubling FOM1 (BioLife 4 vs SL 3568) reduces the Prandtl number by about a factor of ten.
  2. A near doubling of FOM1 lowered average fluid temperature by approximately 7.7 °C.
  3. With roughly doubled FOM1, immersed RAMs, NVMes and SSDs ran about 6.7, 6.4 and 5.9 °C cooler respectively.
  4. CPU temperatures were highest with high-FOM1 fluids, attributed to dielectric fluid infiltrating the TIM between CPU and water block and reducing TIM viscosity by at least 94.4%.
  5. The CFD model matched experiments with a maximum temperature deviation of 10.7% (NVMe average temperature).
  6. SL 3568 properties: density 838/812/773 kg/m³ and kinematic viscosity 406/43/7.6 cSt at 0/40/100 °C, thermal conductivity 0.142-0.134 W/m·K.

Using it in design

  • In hybrid immersion/direct liquid cooling design, rank dielectric fluids by FOM1, but remember a high-FOM1 fluid can infiltrate the TIM of cold-plated CPUs and raise their temperature.
  • Add fluid and TIM compatibility (viscosity drop of 94.4%) to design verification; in hybrid systems select the fluid together with a CPU cooling test.
  • For immersed components (RAM, NVMe, SSD), a higher-FOM1 fluid gave 6-7 °C cooler operation; compare component-level temperature targets with that gain.

Who should read it

Cooling engineers selecting dielectric fluids for single-phase immersion and hybrid direct liquid cooling.

Document contents

  1. 1. Introduction
  2. 3. Fluids comparison experimental test (3.1 Experimental setup and procedure, 3.2 Results and discussion: FOM1 criteria evaluation)
  3. 4. Numerical methodology (4.1 Model description, 4.2 Grid independence analysis, 4.3 Results and discussion: water and fluid behavior, IT components behavior)
  4. 5. Conclusion

Related standards

  • OCP Immersion Cooling Sub-Project (FOM1)

Read the document

immersion-fluid-comparison-single-phase-2025.pdf

PDF · 8.7 MB · English

CC BY 4.0: share with attribution

The document is provided unaltered because its licence permits redistribution.

Publication details

Authors
Ayoub Ruichek; Mohamad Hnayno; Ali Chehade; Farouk Fardoun; Tala Moussa; Guillaume Polidori; Chadi Maalouf
Publisher
Applied Thermal Engineering (Elsevier BV)
Year
2025
Volume
280
Pages
128355
Document language
English
Source type
Scientific
Access
Open licence (downloadable)
Licence
CC BY 4.0: share with attribution
Licence evidence
hal.science
Original licence note

HAL deposit of the published version; HAL cover page states 'Distributed under a Creative Commons CC BY 4.0 - Attribution - International License' and the article p.1 says open access under CC BY. PDF page numbers include the 1-page HAL cover.

Citation

Ayoub Ruichek; Mohamad Hnayno; Ali Chehade; Farouk Fardoun; Tala Moussa; Guillaume Polidori; Chadi Maalouf (2025). Immersion cooling fluid comparison using a single-phase immersion/liquid technique for data centers. Applied Thermal Engineering (Elsevier BV). 280, 128355. https://doi.org/10.1016/j.applthermaleng.2025.128355

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.