Immersion cooling fluid comparison using a single-phase immersion/liquid technique for data centers
Applied Thermal Engineering (Elsevier BV) · Ayoub Ruichek, Mohamad Hnayno et al.
The authors test four single-phase dielectric immersion fluids (Shell SL 3568, Fuchs FES 822-6542, Motul EGEN 100R8 and TotalEnergies BioLife 4) in a hybrid server: CPUs cooled by direct-to-chip water blocks, the rest of the board (RAM, NVMe, SSD) passively immersed in the fluid.
CC BY 4.0: share with attribution
On this page
Overview
The study asks how different immersion fluids perform in a hybrid server. Fluids were ranked with the OCP Immersion Cooling Sub-Project Figure of Merit for natural convection (FOM1), component temperatures were measured, and a CFD model was validated for wider fluid screening; the CFD model matched experiments with a maximum temperature deviation of 10.7% (NVMe average temperature). SL 3568 properties: density 838/812/773 kg/m³ and kinematic viscosity 406/43/7.6 cSt at 0/40/100 °C, with thermal conductivity 0.142-0.134 W/m·K.
Roughly doubling FOM1 (BioLife 4 versus SL 3568) reduces the Prandtl number by about a factor of ten. A near doubling of FOM1 lowered average fluid temperature by approximately 7.7 °C. With roughly doubled FOM1, immersed RAMs, NVMes and SSDs ran about 6.7, 6.4 and 5.9 °C cooler respectively. Higher-FOM1 fluids cool immersed components better.
Unexpectedly, they make cold-plated CPUs hotter: CPU temperatures were highest with high-FOM1 fluids, attributed to dielectric fluid infiltrating the TIM between CPU and water block and reducing TIM viscosity by at least 94.4%. This is a compatibility risk for hybrid immersion/direct liquid cooling designs.
Limits: a single hybrid server and four commercial fluids; results are for this TIM (KP98) and server and must be re-verified for other TIM and fluid pairings. It shows a trade-off between cooling performance and TIM compatibility.
Key points
- Roughly doubling FOM1 (BioLife 4 vs SL 3568) reduces the Prandtl number by about a factor of ten.
- A near doubling of FOM1 lowered average fluid temperature by approximately 7.7 °C.
- With roughly doubled FOM1, immersed RAMs, NVMes and SSDs ran about 6.7, 6.4 and 5.9 °C cooler respectively.
- CPU temperatures were highest with high-FOM1 fluids, attributed to dielectric fluid infiltrating the TIM between CPU and water block and reducing TIM viscosity by at least 94.4%.
- The CFD model matched experiments with a maximum temperature deviation of 10.7% (NVMe average temperature).
- SL 3568 properties: density 838/812/773 kg/m³ and kinematic viscosity 406/43/7.6 cSt at 0/40/100 °C, thermal conductivity 0.142-0.134 W/m·K.
Using it in design
- In hybrid immersion/direct liquid cooling design, rank dielectric fluids by FOM1, but remember a high-FOM1 fluid can infiltrate the TIM of cold-plated CPUs and raise their temperature.
- Add fluid and TIM compatibility (viscosity drop of 94.4%) to design verification; in hybrid systems select the fluid together with a CPU cooling test.
- For immersed components (RAM, NVMe, SSD), a higher-FOM1 fluid gave 6-7 °C cooler operation; compare component-level temperature targets with that gain.
Who should read it
Cooling engineers selecting dielectric fluids for single-phase immersion and hybrid direct liquid cooling.
Document contents
- 1. Introduction
- 3. Fluids comparison experimental test (3.1 Experimental setup and procedure, 3.2 Results and discussion: FOM1 criteria evaluation)
- 4. Numerical methodology (4.1 Model description, 4.2 Grid independence analysis, 4.3 Results and discussion: water and fluid behavior, IT components behavior)
- 5. Conclusion
Related standards
- OCP Immersion Cooling Sub-Project (FOM1)
Read the document
immersion-fluid-comparison-single-phase-2025.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Ayoub Ruichek; Mohamad Hnayno; Ali Chehade; Farouk Fardoun; Tala Moussa; Guillaume Polidori; Chadi Maalouf
- Publisher
- Applied Thermal Engineering (Elsevier BV)
- Year
- 2025
- Volume
- 280
- Pages
- 128355
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- hal.science
Original licence note
HAL deposit of the published version; HAL cover page states 'Distributed under a Creative Commons CC BY 4.0 - Attribution - International License' and the article p.1 says open access under CC BY. PDF page numbers include the 1-page HAL cover.
Citation
Ayoub Ruichek; Mohamad Hnayno; Ali Chehade; Farouk Fardoun; Tala Moussa; Guillaume Polidori; Chadi Maalouf (2025). Immersion cooling fluid comparison using a single-phase immersion/liquid technique for data centers. Applied Thermal Engineering (Elsevier BV). 280, 128355. https://doi.org/10.1016/j.applthermaleng.2025.128355
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.