Industrial Frigo BRG/A and BRW/A Technical Table

Original title Industrial Frigo BRG/A ve BRW/A teknik tablosu

Industrial Frigo / HASTEK

Industrial Frigo (HASTEK) catalogue for BRW/A and BRG/A adiabatic dry coolers: 8 models from 77,400 to 860,000 kcal/h at ΔT 5 °C, with up to 85% energy saving against mechanical cooling.

On this page

Overview

The catalogue describes Industrial Frigo's adiabatic dry-cooler series. The BRW/A series cools naturally with ambient air at very low energy use; it is a fully closed system with built-in tank and pump, used for hydraulic oil cooling, gearboxes, metalworking, foundries, rubber and power plants. The BRG/A series needs no antifreeze thanks to a special coil design; it uses 100% water and has automatic drain-down.

Highlights stated by the maker include increased coil heat-transfer area, EBMPAPST brushless-motor fans with 57% less electricity use and 55% lower sound pressure, DANFOSS controls, Calpeda or Lowara pumps, aluminium air filters, automatic air vents and an expansion tank. The adiabatic kit and ENTHALPY kit give efficient cooling even in humid, hot air, and condensate-tray water can be recovered. Options include a high-pressure pump, a standby pump that starts on failure, automatic by-pass and an inverter-controlled pump.

The technical table gives ΔT 5 and ΔT 10 capacities for BRG/A 160, 210, 310, 450, 620, 900, 1300 and 1800: 80-900 kW at ΔT 5 and 160-1800 kW at ΔT 10. For example BRG/A 160 has 2 fans (36,000 m3/h total), a 1.5 kW pump, 810 kg net weight and 63 dB(A) at 10 m, and BRG/A 1800 has 20 fans (432,000 m3/h), an 18.5 kW pump, 6000 kg and 74 dB(A). BRW/A 180-1000 are given 49-56 dB(A) at 10 m. Capacities are calculated at 25 °C ambient and 15 °C set temperature with 30% antifreeze; all models are galvanised.

Key points

  1. BRW/A: fully closed system with built-in tank and pump; BRG/A: antifreeze-free with automatic drain.
  2. 8 models from 77,400 to 860,000 kcal/h at ΔT 5 °C.
  3. Capacity condition: ambient 25 °C, set temperature 15 °C, 30% antifreeze.
  4. Up to 85% energy saving against mechanical cooling is claimed.
  5. EBMPAPST fans: 57% less electricity use and 55% lower sound pressure.
  6. BRG/A 160: 80 kW at ΔT 5, 160 kW at ΔT 10, 63 dB(A) at 10 m, 810 kg; BRG/A 1800: 1800 kW at ΔT 10, 74 dB(A), 6000 kg.
  7. BRW/A 180-1000: 49-56 dB(A) at 10 m; options include standby pump, by-pass, inverter pump.

Using it in design

  • Compare ΔT 5 and ΔT 10 capacities with the project water regime and summer dry-bulb temperature; the table is only for 25 °C ambient and 15 °C set.
  • Calculate adiabatic and ENTHALPY kit water consumption and water quality separately for the summer peak.
  • Compare sound level at 10 m with the environmental limit; the BRW/A series is quieter.
  • Carry fan, pump and installed power into panel and generator sizing.
  • Write the standby pump and automatic by-pass options into the specification together with the redundancy target.

Who should read it

Mechanical designers selecting adiabatic dry coolers and engineers planning free-cooling loops.

Document contents

  1. BRW/A series adiabatic dry cooler
  2. BRG/A series antifreeze-free adiabatic dry cooler
  3. Technical table (BRG/A and BRW/A)

Publication details

Authors
Industrial Frigo / HASTEK
Publisher
Industrial Frigo / HASTEK
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Industrial Frigo / HASTEK Industrial Frigo BRG/A ve BRW/A teknik tablosu. Industrial Frigo / HASTEK. https://www.hastek.com.tr/assets/pdf/products/21/adyabatik-kuru-sogutucu-brw-a-serisi-catalog-1660723557.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.