INVT In-row Precision Cooling System (12.5-60kW), Specifications table

INVT

INVT's VCR in-row DX precision air conditioner offers six models from 12.5 to 62.7 kW with variable-speed scroll compressors and EC fans; a full cabinet reaches 60 kW and a half cabinet 35 kW.

On this page

Overview

INVT's product page presents the VCR series as an in-row precision cooling system for modular and container data centres, installed side by side with the server cabinets. It combines a variable-frequency compressor, an EC backward-inclined centrifugal fan and a full frequency-conversion design. The compressor modulates capacity dynamically between 20% and 100%, and an electronic expansion valve gives fast response and fine flow control.

Under reliability the page lists a variable-speed scroll compressor resistant to liquid slugging, a starting current below rated current, a two-stage evaporator with an intermediate water tray, and detection of supply voltage, frequency and three-phase imbalance. Configuration options include a standard electrode humidifier (wet-film optional), a delivery grille for left or right air supply, a fluorine-pump natural cooling module and a dual power input.

For management there is a 7-inch colour touch screen, CAN networking of up to 64 units, 10 temperature sensor inputs, RS485 (SNMP optional) and three-level password authorisation. The published table gives six indoor units from VCR012 to VCR060 with matched outdoor units from VCP018 to VCP088.

The table includes capacity, airflow, heating and humidifying capacity, EER, dimensions and weight. Depth and weight each carry two options (1100 or 1200 mm), and the row does not say which value belongs to which variant. The thermal rating temperatures are not stated in the table, so values should be confirmed with the manufacturer before being moved to a design condition.

Key points

  1. Total and sensible capacity: VCR012 12.5; VCR025 25.5; VCR030 30.8; VCR040 42.8; VCR050 51.5; VCR060 62.7 kW.
  2. EER ranges from 3.00 to 3.38 (VCR012 3.38; VCR060 3.00).
  3. Airflow is 2800 to 11500 m³/h; cabinet width 300 mm (012, 025, 030) or 600 mm (040, 050, 060), height 2000 mm.
  4. Weight runs from 200/210 kg (VCR012) to 335/345 kg (VCR060); depth is 1100/1200 mm optional.
  5. Outdoor units range from VCP018 (64 kg, 5000 m³/h) to VCP088 (188 kg, 28000 m³/h), with 1 or 2 fans.
  6. Supply is 380 V (380/220 V for VCR012), 50/60 Hz.
  7. Compressor capacity range is 20-100%; CAN networking supports up to 64 units.
  8. A full cabinet delivers at most 60 kW and a half cabinet at most 35 kW.

Using it in design

  • Use a row only at a rating temperature confirmed by the manufacturer; the table does not state those temperatures.
  • Depth and weight carry two values, so confirm separately which variant is chosen for room layout and floor loading.
  • Specify each indoor unit together with its matched outdoor unit code from the table (for example VCR030 with VCP045).
  • The 20% lower limit restricts compressor cycling at part load; check the part-load scenario against this range.
  • The natural cooling module and dual power input are optional, so state them separately when redundancy is required.

Who should read it

Mechanical designers and procurement engineers selecting in-row DX air conditioners for modular and container data centres.

Document contents

  1. Product description
  2. High reliability
  3. High efficiency and energy saving
  4. Diversified configuration
  5. Intelligent management
  6. Specifications table (indoor and outdoor units)

Publication details

Authors
INVT
Publisher
INVT
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

INVT INVT In-row Precision Cooling System (12.5-60kW), Specifications table. INVT. https://www.invt-power.com/product/In-row-Precision-Cooling-System.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.