Alternative and Natural Refrigerants under International Standards (ISKİD seminar, 2020)

Original title Uluslararası Standartlar Çerçevesinde Alternatif ve Doğal Soğutucu Akışkanlar

İSKİD · Kadir İsa

ISKİD Alternative Refrigerants Seminar presentation (2020): hazards of R744, R717, R32, R1234ze, R290 and R1270, ISO 817 safety classes and EN 378 charge limits (R32 worked example: 8.84 kg).

On this page

Overview

The presentation summarises why a move to alternative and natural refrigerants is needed after CFCs and HCFCs, with F-gas regulation (EU 517/2014) pressure on HFCs, and where these refrigerants apply (central systems, split air conditioners and heat pumps, VRV/VRF, chiller derivatives, remote condensing systems). GWP values come from the F-gas regulation and are expressed in tonnes of CO2 equivalent.

Hazards are shown against R404A: R744 (CO2) has high pressure and a solidification risk; R717 (ammonia) is highly toxic; R32 and R1234ze are low flammability with toxic decomposition products; the hydrocarbons R290 and R1270 are highly flammable. ISO 817:2014 safety classification has two parts: A (low toxicity) or B (high toxicity) paired with 1 (non-flammable), 2L (low flammability), 2 or 3 (high flammability).

The working safety section lists ignition sources (arcing switches, thermostats, relays, pressure switches, ballasts); EN 60079 compliant equipment is not an ignition source in zone 2. HFC and HFO type A2L refrigerants release toxic decomposition products, forming hydrofluoric acid, when ignited by open flame. Measures include PPE, continuous detector monitoring, no ignition source within 3 metres, a suitable recovery machine and nitrogen purging before heating pipe joints.

The standards section explains EN 378 charge limits: room access category (A, B, C), equipment location class (I-IV) and refrigerant hazard, using Table C.1 (toxicity) or C.2 (flammability). Example: for an R32 split with a ceiling indoor unit in a 9 x 5.5 m (49.5 m²) room, LFL 0.307 kg/m³ and h 2.2 m, the formula M = 2.5 x LFL^1.25 x h x A gives 8.84 kg; the limit is 12 kg, so it is acceptable. Leak test frequency depends on the CO2 equivalent charge.

Key points

  1. ISO 817:2014 classes: A low, B high toxicity; 1 non-flammable, 2L low, 2 medium, 3 high flammability.
  2. R744 carries high pressure, R717 high toxicity, R290/R1270 high flammability, R32 and R1234ze low flammability hazards.
  3. Decomposition of A2L (HFC/HFO) refrigerants in flame forms hydrofluoric acid and is highly toxic.
  4. Arcing electrical devices can ignite A3 (HC) and possibly 2L refrigerants; EN 60079-7/-15 compliant devices are not ignition sources in zone 2.
  5. When working with flammable refrigerants, keep the area free of ignition sources within 3 metres and monitored continuously.
  6. EN 378 Table C.2 formula: M = 2.5 x LFL^1.25 x h x A; LFL is 0.307 kg/m³ for R32.
  7. Example: 49.5 m² room, h = 2.2 m: M = 8.84 kg; limit 12 kg (26 x 0.307 x 1.5 via m2 x 1.5 kg).
  8. Leak test frequency: 1 per 2 years for 5-50 t CO2 equivalent (with fixed detection), 4 per year above 500 t.

Using it in design

  • For data centre cooling equipment, check the selected refrigerant's ISO 817 class and EN 378 charge limit against machine room or hall volume.
  • For A2L and A3 units, write the equipment location class (II-IV) and alternative safety measures (detection, shut-off valve, ventilation) into the design.
  • Convert system charge to CO2 equivalent to set leak test frequency and the need for fixed leak detection.
  • Carry out an ignition source assessment in the plant room; check the need for zone 2 compliant electrical equipment.
  • Add recovery and nitrogen purge steps suited to flammable refrigerant to maintenance procedures.

Who should read it

Mechanical designers doing refrigerant selection and safety assessment, and service and operations engineers.

Document contents

  1. Why alternative and natural refrigerants
  2. General properties and GWP
  3. Application areas
  4. Refrigerant hazards
  5. Safety classification (ISO 817, EN 378-1)
  6. Flammability and ignition sources
  7. Asphyxiation and toxicity
  8. Risk assessment
  9. EN 378 charge limits and worked example
  10. Leak test frequency

Publication details

Authors
Kadir İsa
Publisher
İSKİD
Year
2020
Document number
Alternatif Soğutucu Akışkanlar Semineri, 15 Ocak 2020
Document language
Turkish
Source type
Expert / community
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Yayıncının açık PDF dosyası okundu. Açık erişim yeniden dağıtım izni anlamına gelmez; yalnızca künye, özgün kısa özet ve sayfa atıfları kaydedildi. 2020 tarihli eğitim içeriğidir; standart baskıları ve F-gaz mevzuatı güncel kabul edilmemelidir. Yeniden dağıtım lisansı doğrulanmadı.

Citation

Kadir İsa (2020). Uluslararası Standartlar Çerçevesinde Alternatif ve Doğal Soğutucu Akışkanlar. İSKİD. Alternatif Soğutucu Akışkanlar Semineri, 15 Ocak 2020. https://iskid.org.tr/wp-content/uploads/2020/01/5-KAD%C4%B0R-%C4%B0SA_SUNUM_DogalSogutkanlarSemineri.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.