TTMD Uluslararası Sempozyumu – Yapay Zeka ve Veri Merkezleri oturumları (TTMD International Symposium report: AI and data-centre sessions)

Türk Tesisat Mühendisleri Derneği (TTMD) - TTMD Dergisi · Ömer Yiğit Türkarslan, İsmail Can et al.

Report of TTMD's international symposium on AI and data centres, summarising a technical session on AI for thermal management and a 'Future of Data Centres' panel.

On this page

Overview

This document is the report of the international symposium of the Turkish Society of HVAC and Sanitary Engineers (TTMD) focused on AI and data centres. It was published in issue 150 of TTMD Dergisi (April-June 2026, 'Bizden Haberler' section); its authors are Omer Yigit Turkarslan, Ismail Can, Sinan Alkas and Kivanc Aslantas. The report reflects the current priorities of practitioner engineers in Turkey.

The technical session addressed AI in data centre thermal management. One talk presented a physics-constrained neural network (PCNN) that reconstructs the full temperature field of a data hall from sparse sensors: mean absolute error fell from 4.35 °C to 0.75 °C against a classic neural network (about 83% better), and prediction time fell from about 60 minutes for a typical CFD run to milliseconds, enabling real-time monitoring and control, with the model's deviations being conservative. AI methods were mapped to thermal problems as surrogate models, PINNs, reinforcement learning and evolutionary optimisation.

The 'Future of Data Centres' panel covered free cooling, liquid and hybrid cooling, cooling strategy from an operator's view, the role of commissioning and TAB, and natural/low-GWP refrigerants with total equivalent warming impact (TEWI). The operator panellist stressed commissioning and TAB as essential parts of data centre cooling strategy for investment, operation and continuity. The source is an event report, not a peer-reviewed paper; results are given as presented in the talks.

Key points

  1. A physics-constrained deep learning model (PCNN) reconstructed DC temperature fields from sparse sensors, cutting mean absolute error from 4.35 °C to 0.75 °C (about 83% better) versus a classic neural network.
  2. Prediction time fell from about 60 minutes for a typical CFD run to milliseconds, enabling real-time monitoring and control; the model's deviations are conservative.
  3. AI methods mapped to DC thermal problems: surrogate models, PINNs, reinforcement learning and evolutionary optimisation.
  4. The operator panellist stressed commissioning and TAB as essential parts of cooling strategy for investment, operation and continuity.
  5. Refrigerant selection was discussed via natural refrigerants and total equivalent warming impact (TEWI).
  6. The panel also covered free cooling and liquid and hybrid cooling.
  7. The report appeared in TTMD Dergisi issue 150 (April-June 2026).

Using it in design

  • Assess sparse-sensor temperature reconstruction as a faster alternative to CFD for monitoring and digital-twin studies, explicitly identifying it as model-based.
  • Record refrigerant GWP and include it in TEWI calculations for cooling options.
  • Define commissioning and TAB (testing, adjusting, balancing) as an explicit step in the cooling design workflow.

Who should read it

Engineers designing and operating data centre cooling in Turkey, and specialists following the role of AI in thermal management.

Publication details

Authors
Ömer Yiğit Türkarslan; İsmail Can; Sinan Alkaş; Kıvanç Aslantaş
Publisher
Türk Tesisat Mühendisleri Derneği (TTMD) - TTMD Dergisi
Year
2026
Document number
TTMD Dergisi Sayı 150 (Nisan-Haziran 2026), Bizden Haberler
Event
TTMD Uluslararası Sempozyumu 2026 - Yapay Zeka ve Veri Merkezleri oturumları
Document language
Turkish
Source type
Industry body
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

Ömer Yiğit Türkarslan; İsmail Can; Sinan Alkaş; Kıvanç Aslantaş (2026). TTMD Uluslararası Sempozyumu – Yapay Zeka ve Veri Merkezleri oturumları (TTMD International Symposium report: AI and data-centre sessions). Türk Tesisat Mühendisleri Derneği (TTMD) - TTMD Dergisi. TTMD Dergisi Sayı 150 (Nisan-Haziran 2026), Bizden Haberler. TTMD Uluslararası Sempozyumu 2026 - Yapay Zeka ve Veri Merkezleri oturumları. https://www.ttmd.org.tr/upload/files/95817Dergi150.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.