Technical guideFree to read2021

Cooling Systems and Equipment in Cogeneration Plants (ISKİD presentation, 2021)

Original title Kojenerasyon Tesislerinde Soğutma Sistem ve Ekipmanları

İSKİD · Toros Arslanyan

A 2021 ISKİD presentation by Toros Arslanyan: absorption chiller types (LiBr-water, ammonia-water) from cogeneration to trigeneration, with working principles and comparison of open and closed cooling towers and adiabatic coolers.

On this page

Overview

The presentation explains that hot water or steam produced alongside electricity in a cogeneration system can be turned into chilled water through an absorption chiller, and that producing electricity, heating and cooling together is called trigeneration. Absorption chiller types are single-effect indirect fired, double-effect indirect fired, triple-effect indirect fired and double-effect direct fired.

Two working pairs are compared. Ammonia-water is preferred at low temperatures (down to -40 °C) and in food cooling, but ammonia is toxic and flammable and, evaporating together with the absorbent, needs a rectification column. LiBr-water is common in comfort cooling, non-toxic, non-flammable and chemically stable, but the refrigerant freezes at 0 °C so minimum evaporator temperature is 3 °C, and the solution is corrosive and viscous.

The working principle is described: LiBr-water solution is pumped from the absorber through a heat exchanger to the generator, the heat source boils off water, the vapour condenses in the condenser with cooling tower water, passes the expansion valve, evaporates at low pressure in the evaporator to make chilled water and is reabsorbed by LiBr in the absorber. Cooling towers follow: site-built and packaged, open and closed, counterflow and crossflow.

The open tower has low first cost, high efficiency and a small footprint, but its water gets dirty and water loss is high. The closed tower keeps the loop water clean and can run dry in winter; its first cost and energy use are higher, it needs antifreeze below 0 °C and has a larger footprint. Adiabatic coolers use pads in front of V-arranged finned coils to bring inlet air toward wet bulb; pads are removed in winter for fully dry operation.

Key points

  1. Cogeneration plus an absorption chiller produces electricity, heating and cooling together, called trigeneration.
  2. Chiller types: single-, double- and triple-effect indirect fired, and double-effect direct fired.
  3. The ammonia-water pair can cool down to -40 °C but is toxic and flammable and needs a rectification column.
  4. With LiBr-water the minimum evaporator temperature is 3 °C (the refrigerant water freezes at 0 °C); the solution is corrosive and viscous.
  5. Open tower: low first cost and high efficiency; dirty tower water, continuous make-up and filtration are needed.
  6. Closed tower: loop water stays clean and it can run dry in winter; higher first cost and energy use, antifreeze needed below 0 °C.
  7. Adiabatic cooler: wetted pads bring inlet air toward wet bulb; pads are removed in winter and the system runs dry.

Using it in design

  • If cogeneration or trigeneration is considered for a data centre, compare absorption chiller outlet water temperature (at least 3 °C evaporator for LiBr) with the cooling circuit design temperature.
  • Size the waste heat source (hot water or steam) together with condenser cooling water need; an absorption chiller needs extra tower capacity.
  • Choose tower type on water quality, water consumption and freezing risk: filtration and water treatment for open towers, antifreeze or a dry-operation strategy for closed towers.
  • At water-scarce sites, evaluate adiabatic coolers together with wet bulb approach and seasonal pad removal.
  • Set the number of tower cells and chillers separately for redundancy.

Who should read it

Mechanical engineers designing cogeneration or trigeneration supported cooling, and designers selecting cooling towers or adiabatic coolers.

Document contents

  1. Cogeneration and trigeneration
  2. Absorption chiller types
  3. Working pairs (ammonia-water, LiBr-water)
  4. Absorption chiller components and working principle
  5. Cooling towers: open and closed type
  6. Adiabatic coolers

Publication details

Authors
Toros Arslanyan
Publisher
İSKİD
Year
2021
Document number
Kojenerasyon Sistemlerinde Soğutma ve Havalandırma semineri sunumu
Document language
Turkish
Source type
Expert / community
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Yayıncının açık PDF dosyası okundu. Açık erişim yeniden dağıtım izni anlamına gelmez; yalnızca künye, özgün kısa özet ve sayfa atıfları kaydedildi. Yazar bilgisi İSKİD sunum dizinindeki kayıtla doğrulandı.

Citation

Toros Arslanyan (2021). Kojenerasyon Tesislerinde Soğutma Sistem ve Ekipmanları. İSKİD. Kojenerasyon Sistemlerinde Soğutma ve Havalandırma semineri sunumu. https://iskid.org.tr/wp-content/uploads/2021/06/TOROS-ARSLANYAN_SUNUM_KOJENERASYON-TESISLERINDE-SOGUTMA.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.