Information technology - Data centres key performance indicators - Part 6: Energy Reuse Factor (ERF)
ISO/IEC · ISO/IEC JTC 1
The standard defining ERF, the KPI for how much of a data centre's consumed energy is reused outside it, typically as waste heat.
This document is sold by ISO/IEC and is available from the publisher’s site. SoSo CAD does not sell or distribute it; this page holds only catalogue details and our own summary.
On this page
Overview
ISO/IEC 30134-6:2021 is the sixth part of the data centre key performance indicator (KPI) series and defines the Energy Reuse Factor (ERF). ERF quantifies how much of the energy consumed in a data centre is reused outside it, typically as waste heat. The standard was published as edition 1 on 11 August 2021 and runs to 14 pages. This page rests on the publisher's public catalogue abstract and product metadata.
The calculation is simple: ERF is the reused energy divided by the sum of all energy consumed in the data centre. Unlike PUE, the indicator does not express efficiency inside the facility boundary but the extent to which the facility's energy finds value outside it. It is therefore a complementary indicator in projects where waste heat goes to district heating or a similar off-taker.
The standard has a clear limit: the reuse process itself is not part of the data centre, and ERF does not reflect its efficiency. How heat is used on the receiving side, or how much electricity a heat pump consumes, falls outside ERF's scope. The indicator counts only the energy that leaves the boundary.
Related documents include ISO/IEC 30134-1, EN 50600-4-6 and EU Energy Efficiency Directive 2023/1791. This framework shows that ERF is gaining importance in reporting and regulatory contexts.
Key points
- ERF is the reused energy divided by the sum of all energy consumed in the data centre.
- The indicator quantifies reuse of energy consumed in a data centre.
- The reuse process is not part of the data centre and ERF does not reflect its efficiency.
- Edition 1, published 2021-08-11, 14 pages.
- Related documents: ISO/IEC 30134-1, EN 50600-4-6, EU Energy Efficiency Directive 2023/1791.
- The standard is paid; the full text is not redistributed.
Using it in design
- Calculate ERF on a 0–1 scale as heat exported at the boundary heat exchanger divided by total facility energy.
- In district-heating scenarios, do not net the off-taker's heat-pump electricity into ERF; show it as a separate line.
- Plan the heat metering point at the boundary heat exchanger, including meter class, at design stage.
Who should read it
Data centre designers and energy engineers planning waste-heat recovery and sustainability reporting.
Related standards
- ISO/IEC 30134-1
- EN 50600-4-6
- EU Energy Efficiency Directive 2023/1791
Publication details
- Authors
- ISO/IEC JTC 1
- Publisher
- ISO/IEC
- Year
- 2021
- Document number
- ISO/IEC 30134-6:2021
- Document language
- English
- Source type
- Standard
- Access
- Paid; available from the publisher
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Paid standard. Record built only from the publisher's public catalogue abstract and product metadata; full text not redistributed.
Citation
ISO/IEC JTC 1 (2021). Information technology - Data centres key performance indicators - Part 6: Energy Reuse Factor (ERF). ISO/IEC. ISO/IEC 30134-6:2021. https://webstore.iec.ch/en/publication/70719
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
