Research paperFree to read2024

The Effects of Non-Condensable Gases on the Condensation Heat Transfer of HFE7100 in Immersion Cooling Systems

34th International Symposium on Transport Phenomena / National Central University · L.-H. Chien, C.-H. Lin et al.

An ISTP34 (November 2024) paper measures that 2% non-condensable gas cuts HFE-7100 condensation heat transfer by 30.9% on a plain tube and 80.5% on a fin tube, which is 9.77 times better in pure vapour.

On this page

Overview

The paper experimentally studies condensation heat transfer on condenser tube bundles in two-phase immersion cooling and the effect of non-condensable gas (air). Air is hard to keep out during maintenance; it does not condense, gathers near the condenser tube as an air film, lowers vapour partial pressure and saturation temperature and sharply reduces condensation performance. The introduction notes that cooling is about half of data centre power.

The test used the dielectric fluid HFE-7100 at 50 °C saturation (72.8 kPa), heat flux 8,000 to 18,000 W/m² and cooling rate 680 to 1,421 W. A bundle of four tubes in a vertical row was tested as plain tubes (19.05 mm OD) and fin tubes (18.42 mm OD), with non-condensable gas mass fractions of 0, 0.5, 1 and 2%, cooling water entering from top or bottom, and the bundle at 0° and 30° tilt.

On the plain tube, 0.5% gas has an insignificant effect, 1% lowers the coefficient 8.34% and 2% lowers it 30.9%. The fin tube is 9.77 times better than the plain tube in pure vapour but suffers more: similar at 0.5%, 57.9% lower at 1% and 80.5% lower at 2%. A 30° tilt reduces the effect of dripping condensate and improves performance, and top water entry beats bottom entry. Results apply to one fluid in a laboratory test chamber.

Key points

  1. Fluid HFE-7100, saturation temperature 50 °C (72.8 kPa), heat flux 8,000-18,000 W/m².
  2. Non-condensable gas mass fractions of 0, 0.5, 1 and 2% were tested; cooling rate 680-1,421 W.
  3. Plain tube: coefficient 8.34% lower at 1% gas and 30.9% lower at 2%.
  4. The fin tube is about 9.77 times better than the plain tube in pure vapour.
  5. Fin tube: negligible effect at 0.5%, 57.9% lower at 1%, 80.5% lower at 2%.
  6. A 30° tilted bundle gave better condensation than 0°.
  7. Top water entry gave better heat transfer than bottom entry.
  8. Tube outside diameters: plain 19.05 mm, fin 18.42 mm.

Using it in design

  • Write a post-maintenance air purge and degassing procedure into two-phase immersion tank specifications; even 1-2% gas causes large losses on fin condensers.
  • When choosing fin condensers, weigh the pure-vapour advantage (about 9.77 times) against gas sensitivity.
  • Place condenser tube bundles tilted (for example 30°) where possible and feed cooling water from the top.
  • Use saturation temperature and pressure deviation as an indicator of gas accumulation when monitoring condenser performance.
  • Verify the results separately for other fluids and scales.

Who should read it

Thermal engineers designing two-phase immersion condensers and researchers.

Document contents

  1. Abstract
  2. Introduction
  3. Experimental setup
  4. Results and discussion
  5. Comparison with the literature
  6. Conclusions

Publication details

Authors
L.-H. Chien; C.-H. Lin; C.-W. Hsu; S.-H. Cai
Publisher
34th International Symposium on Transport Phenomena / National Central University
Year
2024
Document language
English
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public source inspected; no document-specific commercial redistribution permission established. Metadata and original short summaries only.

Citation

L.-H. Chien; C.-H. Lin; C.-W. Hsu; S.-H. Cai (2024). The Effects of Non-Condensable Gases on the Condensation Heat Transfer of HFE7100 in Immersion Cooling Systems. 34th International Symposium on Transport Phenomena / National Central University. https://istp34.me.ncu.edu.tw/wp-content/uploads/2024/06/0321-Chien-1.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.