The Effects of Non-Condensable Gases on the Condensation Heat Transfer of HFE7100 in Immersion Cooling Systems
34th International Symposium on Transport Phenomena / National Central University · L.-H. Chien, C.-H. Lin et al.
An ISTP34 (November 2024) paper measures that 2% non-condensable gas cuts HFE-7100 condensation heat transfer by 30.9% on a plain tube and 80.5% on a fin tube, which is 9.77 times better in pure vapour.
On this page
Overview
The paper experimentally studies condensation heat transfer on condenser tube bundles in two-phase immersion cooling and the effect of non-condensable gas (air). Air is hard to keep out during maintenance; it does not condense, gathers near the condenser tube as an air film, lowers vapour partial pressure and saturation temperature and sharply reduces condensation performance. The introduction notes that cooling is about half of data centre power.
The test used the dielectric fluid HFE-7100 at 50 °C saturation (72.8 kPa), heat flux 8,000 to 18,000 W/m² and cooling rate 680 to 1,421 W. A bundle of four tubes in a vertical row was tested as plain tubes (19.05 mm OD) and fin tubes (18.42 mm OD), with non-condensable gas mass fractions of 0, 0.5, 1 and 2%, cooling water entering from top or bottom, and the bundle at 0° and 30° tilt.
On the plain tube, 0.5% gas has an insignificant effect, 1% lowers the coefficient 8.34% and 2% lowers it 30.9%. The fin tube is 9.77 times better than the plain tube in pure vapour but suffers more: similar at 0.5%, 57.9% lower at 1% and 80.5% lower at 2%. A 30° tilt reduces the effect of dripping condensate and improves performance, and top water entry beats bottom entry. Results apply to one fluid in a laboratory test chamber.
Key points
- Fluid HFE-7100, saturation temperature 50 °C (72.8 kPa), heat flux 8,000-18,000 W/m².
- Non-condensable gas mass fractions of 0, 0.5, 1 and 2% were tested; cooling rate 680-1,421 W.
- Plain tube: coefficient 8.34% lower at 1% gas and 30.9% lower at 2%.
- The fin tube is about 9.77 times better than the plain tube in pure vapour.
- Fin tube: negligible effect at 0.5%, 57.9% lower at 1%, 80.5% lower at 2%.
- A 30° tilted bundle gave better condensation than 0°.
- Top water entry gave better heat transfer than bottom entry.
- Tube outside diameters: plain 19.05 mm, fin 18.42 mm.
Using it in design
- Write a post-maintenance air purge and degassing procedure into two-phase immersion tank specifications; even 1-2% gas causes large losses on fin condensers.
- When choosing fin condensers, weigh the pure-vapour advantage (about 9.77 times) against gas sensitivity.
- Place condenser tube bundles tilted (for example 30°) where possible and feed cooling water from the top.
- Use saturation temperature and pressure deviation as an indicator of gas accumulation when monitoring condenser performance.
- Verify the results separately for other fluids and scales.
Who should read it
Thermal engineers designing two-phase immersion condensers and researchers.
Document contents
- Abstract
- Introduction
- Experimental setup
- Results and discussion
- Comparison with the literature
- Conclusions
Publication details
- Authors
- L.-H. Chien; C.-H. Lin; C.-W. Hsu; S.-H. Cai
- Publisher
- 34th International Symposium on Transport Phenomena / National Central University
- Year
- 2024
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public source inspected; no document-specific commercial redistribution permission established. Metadata and original short summaries only.
Citation
L.-H. Chien; C.-H. Lin; C.-W. Hsu; S.-H. Cai (2024). The Effects of Non-Condensable Gases on the Condensation Heat Transfer of HFE7100 in Immersion Cooling Systems. 34th International Symposium on Transport Phenomena / National Central University. https://istp34.me.ncu.edu.tw/wp-content/uploads/2024/06/0321-Chien-1.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.