ITK In-Row Precision Air Conditioner, Tables 1-4, pp.8-12

ITK / IEK

The ITK (IEK) in-row precision air conditioner manual covers nine models in three families (air-cooled AIR ROW, glycol-cooled FLUID ROW and chilled-water WATER ROW) with three rating tables and dimension tables.

On this page

Overview

The ITK-branded in-row precision air conditioner (a short bilingual Russian-English IEK manual) is designed for continuous climate control in data-centre rooms. The unit comes with a remote control and monitoring module and is described as combining high cooling capacity with a small footprint. The manual declares conformity with technical regulations TR TS 010/2011, TR TS 004/2011 and TR TS 020/2011.

The product code follows XX1-CV-XXXXXX2-XXX3-X4: AR is an air-cooled-condenser in-row unit, FR a liquid-cooled one and WR one running on chilled water; CV is the in-row body; the last digit gives 1 for an integral and 2 for a remote condenser. An example code is AR-CV-H3221VP-000-1. Table 1 holds the air-cooled models, Table 2 the liquid-cooled, Table 3 the chilled-water models, Table 4 the indoor unit dimensions and Table 5 the AIR ROW external condenser dimensions.

The rating conditions are written separately: for AIR ROW, 36°C indoor air at 28% relative humidity and 35°C outdoor; for FLUID ROW the same indoor air with 40% ethylene glycol at 45-50°C; for WATER ROW the same indoor air with 13-18°C water. The three body sizes are 300, 400 and 600 mm wide, 1200 mm deep and 1980 mm high.

The rest of the manual covers safety and operation: delivery under ultra-pure nitrogen pressure, work with refrigerant and oil, surface temperatures, work at height and fire safety. Storage is -20 to +40°C, warranty is 2 years from sale and service life is at least 15 years. The -2 suffix on external condenser codes does not mean an internal cooler on every row of the same code family.

Key points

  1. Nine models: AR-CV-H3221VP, H4281VP, H6441VP (air-cooled); FR-CV-H6441DP, H4251DP, H6401DP (liquid); WR-CV-C3221XP, C4271XP, C6401XP (chilled water).
  2. Every indoor unit is 1200 mm deep and 1980 mm high; widths are 300, 400 and 600 mm.
  3. AIR ROW external condensers (-2 codes) are 1650×430×753 mm (two smaller models) and 2180×430×903 mm (the larger model).
  4. AIR ROW condition: indoor air 36°C, 28% relative humidity, outdoor air 35°C.
  5. FLUID ROW condition: indoor air 36°C and 28% humidity, 40% ethylene glycol, fluid 45-50°C.
  6. WATER ROW condition: indoor air 36°C and 28% humidity, water 13-18°C.
  7. Warranty is 2 years, service life at least 15 years; storage temperature -20 to +40°C.
  8. The unit ships under nitrogen pressure, which must be released to atmosphere before connecting to the cooling circuit.

Using it in design

  • Specify AR-CV, FR-CV and WR-CV as separate heat-rejection types; the remote-condenser (-2) and integral-condenser (-1) versions do not share dimensions.
  • Use capacity only at the rating condition of its own table (36°C indoor air with 35°C outdoor air, or 13-18°C water).
  • For FLUID ROW compare 40% ethylene glycol at 45-50°C, and for WATER ROW the 13-18°C water, with the plant's secondary circuit.
  • Include the Table 5 dimensions of the external condenser in roof or ground area planning.
  • Allow for Cyrillic labels in the tables and confirm numeric values with the manufacturer.

Who should read it

Data-centre mechanical designers selecting in-row precision air conditioners and specifiers reading ITK/IEK product codes.

Document contents

  1. Basic product information
  2. Technical data (Tables 1-3)
  3. Dimensions (Tables 4 and 5)
  4. Completeness of set (Table 6)
  5. Installation and operation manual
  6. Safety measures
  7. Transportation, storage and disposal
  8. Service life and manufacturer's warranty

Publication details

Authors
ITK / IEK
Publisher
ITK / IEK
Year
Year not stated
Document language
Russian
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ITK / IEK ITK In-Row Precision Air Conditioner, Tables 1-4, pp.8-12. ITK / IEK. https://cdn-01.iek.ru/media/original/76d1aad0f64fc9b86e94962a3fbcf9a6ecc3a167643e3a4a1aa43e7885ad2a0a.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.