ITU-T L.1307 (03/2024): Energy Efficiency in Micro Data Centres for Edge Computing
Original title Recommendation ITU-T L.1307 (03/2024): Energy efficiency of micro data centres for edge computing
International Telecommunication Union (ITU-T) · ITU-T Study Group 5
ITU-T L.1307 (March 2024) defines design requirements for micro data centres and an indicator, EEI(MDC) = ITEUsv / PUE, that relates server CPU utilisation to PUE; it recommends 5-10 minutes of UPS backup.
On this page
Overview
The Recommendation describes how to improve the energy efficiency of micro data centres, the essential equipment of edge computing services, and how to operate them efficiently. Its scope covers deployment and configuration (including redundancy and components), energy-efficiency management functions, and energy efficiency in edge computing. A micro data centre is defined as a solution providing processing, storage and networking in a more compact and modular form; it can be placed at Wi-Fi access points, enterprise premises, base stations and small cells.
The requirements table concentrates on units installed in non-dedicated spaces (office, communication room, base station): a power supply sized for maximum consumption and electrical distribution separated from other services on the site, a UPS with 5-10 minutes of battery backup, all resources provided through virtualisation, offloading to nearby micro data centres or the cloud before physical expansion, a management system monitoring temperature, humidity and power use, and an enclosed rack for noise and vibration plus strong physical security.
The energy-management section lists data to collect for servers, storage, network, racks, services, power and cooling. The indicator section says PUE cannot be used as it is for micro data centres, whose backup power and cooling may differ from a typical data centre. The proposed indicator, EEI(MDC), divides the average server CPU utilisation (ITEUsv, from ISO/IEC 30134-5) by PUE. A higher value means higher efficiency; since a server uses minimum energy even when idle, consolidating onto fewer servers raises efficiency.
The edge-computing section notes the distributed structure, limited terminal resources, data traffic and real-time processing as issues, and proposes data compression, local processing, task offloading (vertical and horizontal) and virtualisation. Informative Appendix I says solar is the most viable renewable source, that a PV plant needs sufficient panels, energy storage and a charge controller, and that it should be combined with the grid through an energy management system. The document gives no numeric PUE target; it defines methods and an indicator.
Key points
- The micro data centre energy-efficiency indicator is EEI(MDC) = ITEUsv / PUE; a higher value means higher efficiency.
- ITEUsv is the average server CPU utilisation (ISO/IEC 30134-5); it is measured at intervals using the maximum value at each interval and does not apply to storage or network equipment.
- PUE (ISO/IEC 30134-2) should not be used as is for micro data centres, whose backup power and cooling may differ from typical data centres.
- Server power model P(u) = k×Pmax + (1−k)×Pmax×u: an idle server uses minimum energy and power rises linearly with utilisation, which is why consolidation is efficient.
- A UPS battery backup time of 5-10 minutes is recommended; server failure can be covered by backup servers in the rack or offloading to another micro data centre.
- Separating the electrical distribution of the micro data centre from other services such as the office is recommended.
- All computing resources should be provided through virtual machines, containers, NFV and SDN.
- In a general office, the micro data centre needs its own cooling, an enclosed rack to cut noise and vibration, and strong physical security.
- Appendix I: the PV plant's average daily generation should exceed the micro data centre's required power, with energy storage and a charge controller, integrated with the grid through an energy management system.
Using it in design
- For edge and micro sites, define EEI(MDC) = ITEUsv / PUE as a success measure instead of PUE alone, and add telemetry for server CPU utilisation to the design.
- For installation in non-dedicated space, write separate electrical distribution, own cooling, an enclosed rack and access control into the requirement checklist.
- Size UPS battery capacity for 5-10 minutes of backup and decide server and power-supply redundancy (backup servers in the rack, offloading to another micro data centre).
- For energy management, decide which of the server, storage, network, power and cooling data in Table 2 will be collected and at what interval.
- For PV-supported micro data centres, size the panels against average daily generation and the battery and charge controller for night and cloudy weather.
Who should read it
Engineers designing edge and micro data centres, telecom operators, and teams building on-premises IT infrastructure in factories and enterprises.
Document contents
- 1 Scope
- 2 References
- 3 Definitions
- 4 Abbreviations and acronyms
- 5 Conventions
- 6 Overview of edge computing and micro data centres
- 7 Considerations on micro data centre for edge computing
- 8 Energy-efficient management of micro data centre
- 9 Energy-Efficient Indicator for micro data centre
- 10 Energy efficiency in edge computing
- Appendix I: Applying renewable energy to micro data centres (recommended renewable energy types, PV power plant requirements, method to incorporate the PV plant)
Related standards
- ITU-T L.1306
Publication details
- Authors
- ITU-T Study Group 5
- Publisher
- International Telecommunication Union (ITU-T)
- Year
- 2024
- Document number
- ITU-T L.1307 (03/2024)
- Document language
- English
- Source type
- Expert / community
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
(c) ITU 2024, all rights reserved; PDF is freely downloadable from ITU.
Citation
ITU-T Study Group 5 (2024). Recommendation ITU-T L.1307 (03/2024): Energy efficiency of micro data centres for edge computing. International Telecommunication Union (ITU-T). ITU-T L.1307 (03/2024). https://www.itu.int/rec/T-REC-L.1307-202403-I/en
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.