CNN-Based Server State Monitoring and Fault Diagnosis Using Infrared Thermography
İstanbul Teknik Üniversitesi · Beltus Nkwawir Wiysobunri
A 2022 Istanbul Technical University M.Sc. thesis classifies five server operating states from 1,350 infrared images: DenseNet121 averages 98.83% accuracy and beats an SVM by 4-8 points.
On this page
Overview
The thesis studies automatic diagnosis of server operating state from infrared thermography (IRT) images of the server surface. In data-centre thermal management, CFD models are computationally expensive and data-driven machine learning depends on data type and feature extraction, so the work evaluates image-based deep learning as an alternative. It was submitted to the Istanbul Technical University Informatics Institute in January 2022 and defended on 1 February 2022.
Five operating conditions are classified: partial processor load, maximum processor load, main fan failure, CPU fan failure and server entrance blockage. The dataset consists of 1,350 IRT images taken with a FLIR E8 thermal imager. Seven pretrained deep CNN architectures and two shallow CNN architectures are evaluated; for the deep models a network pretrained on ImageNet is fine-tuned on IRT images by transfer learning. Performance is measured by stratified five-fold cross-validation across five data split ratios.
Deep models outperform shallow ones, and most architectures exceed 98% test accuracy across several split ratios. DenseNet121 is chosen as the most effective and robust model with an average validation accuracy of 98.83% and a standard deviation of 0.007 across all split ratios. Against a support vector machine (SVM) classifier trained on handcrafted features, the CNN models achieve roughly 4 to 8 percentage points higher test accuracy.
The author states that the approach can give operators a non-contact intelligent monitoring tool that improves thermal management, reliability and energy efficiency. The study is limited to five predefined states; predicting continuous operating states and server power consumption is described as ongoing work with data from the ITU National Center for High Performance Computing (UHeM).
Key points
- Five states: partial CPU load, maximum CPU load, main fan failure, CPU fan failure and server entrance blockage.
- The dataset has 1,350 IRT images captured with a FLIR E8 thermal imager.
- Seven pretrained deep CNN and two shallow CNN architectures were evaluated.
- Evaluation used stratified 5-fold cross-validation across five data split ratios.
- DenseNet121 is best, with 98.83% average validation accuracy and 0.007 standard deviation.
- Most CNN architectures exceeded 98% test accuracy across many split ratios.
- At the 60/40 split ResNet50 reached the highest validation accuracy of 99.63%; the shallow 1-CNN model scored lowest at 88.00%.
- CNN models are roughly 4 to 8 percentage points more accurate than an SVM with handcrafted features.
Using it in design
- Add a periodic thermal-camera survey procedure to the operations plan to reveal conditions such as fan failure and inlet blockage.
- Treat infrared monitoring as a non-contact layer on top of existing temperature sensors, and plan camera positions in the cold-aisle design.
- Define at commissioning the need to collect labelled fault data (enough images per state) for machine-learning diagnosis.
- Note that the results come from one laboratory and a limited set of states; run validation tests in your own facility.
Who should read it
Engineers working on data-centre thermal management and predictive maintenance, and researchers exploring image-based monitoring.
Document contents
- Introduction
- Background and Literature Review
- Methodology and Proposed Solution
- Results and Discussions
- Conclusions and Future Work
Publication details
- Authors
- Beltus Nkwawir Wiysobunri
- Publisher
- İstanbul Teknik Üniversitesi
- Year
- 2022
- Document number
- M.Sc. thesis, Informatics Institute, January 2022
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official publisher or university publicly accessible text; no open redistribution licence established.
Citation
Beltus Nkwawir Wiysobunri (2022). CNN-Based Server State Monitoring and Fault Diagnosis Using Infrared Thermography. İstanbul Teknik Üniversitesi. M.Sc. thesis, Informatics Institute, January 2022. https://polen.itu.edu.tr/bitstreams/59f8c889-5512-403f-a75a-e890da799329/download
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.