CNN-Based Server State Monitoring and Fault Diagnosis Using Infrared Thermography

İstanbul Teknik Üniversitesi · Beltus Nkwawir Wiysobunri

A 2022 Istanbul Technical University M.Sc. thesis classifies five server operating states from 1,350 infrared images: DenseNet121 averages 98.83% accuracy and beats an SVM by 4-8 points.

On this page

Overview

The thesis studies automatic diagnosis of server operating state from infrared thermography (IRT) images of the server surface. In data-centre thermal management, CFD models are computationally expensive and data-driven machine learning depends on data type and feature extraction, so the work evaluates image-based deep learning as an alternative. It was submitted to the Istanbul Technical University Informatics Institute in January 2022 and defended on 1 February 2022.

Five operating conditions are classified: partial processor load, maximum processor load, main fan failure, CPU fan failure and server entrance blockage. The dataset consists of 1,350 IRT images taken with a FLIR E8 thermal imager. Seven pretrained deep CNN architectures and two shallow CNN architectures are evaluated; for the deep models a network pretrained on ImageNet is fine-tuned on IRT images by transfer learning. Performance is measured by stratified five-fold cross-validation across five data split ratios.

Deep models outperform shallow ones, and most architectures exceed 98% test accuracy across several split ratios. DenseNet121 is chosen as the most effective and robust model with an average validation accuracy of 98.83% and a standard deviation of 0.007 across all split ratios. Against a support vector machine (SVM) classifier trained on handcrafted features, the CNN models achieve roughly 4 to 8 percentage points higher test accuracy.

The author states that the approach can give operators a non-contact intelligent monitoring tool that improves thermal management, reliability and energy efficiency. The study is limited to five predefined states; predicting continuous operating states and server power consumption is described as ongoing work with data from the ITU National Center for High Performance Computing (UHeM).

Key points

  1. Five states: partial CPU load, maximum CPU load, main fan failure, CPU fan failure and server entrance blockage.
  2. The dataset has 1,350 IRT images captured with a FLIR E8 thermal imager.
  3. Seven pretrained deep CNN and two shallow CNN architectures were evaluated.
  4. Evaluation used stratified 5-fold cross-validation across five data split ratios.
  5. DenseNet121 is best, with 98.83% average validation accuracy and 0.007 standard deviation.
  6. Most CNN architectures exceeded 98% test accuracy across many split ratios.
  7. At the 60/40 split ResNet50 reached the highest validation accuracy of 99.63%; the shallow 1-CNN model scored lowest at 88.00%.
  8. CNN models are roughly 4 to 8 percentage points more accurate than an SVM with handcrafted features.

Using it in design

  • Add a periodic thermal-camera survey procedure to the operations plan to reveal conditions such as fan failure and inlet blockage.
  • Treat infrared monitoring as a non-contact layer on top of existing temperature sensors, and plan camera positions in the cold-aisle design.
  • Define at commissioning the need to collect labelled fault data (enough images per state) for machine-learning diagnosis.
  • Note that the results come from one laboratory and a limited set of states; run validation tests in your own facility.

Who should read it

Engineers working on data-centre thermal management and predictive maintenance, and researchers exploring image-based monitoring.

Document contents

  1. Introduction
  2. Background and Literature Review
  3. Methodology and Proposed Solution
  4. Results and Discussions
  5. Conclusions and Future Work

Publication details

Authors
Beltus Nkwawir Wiysobunri
Publisher
İstanbul Teknik Üniversitesi
Year
2022
Document number
M.Sc. thesis, Informatics Institute, January 2022
Document language
English
Source type
Scientific
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official publisher or university publicly accessible text; no open redistribution licence established.

Citation

Beltus Nkwawir Wiysobunri (2022). CNN-Based Server State Monitoring and Fault Diagnosis Using Infrared Thermography. İstanbul Teknik Üniversitesi. M.Sc. thesis, Informatics Institute, January 2022. https://polen.itu.edu.tr/bitstreams/59f8c889-5512-403f-a75a-e890da799329/download

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Redundancy scenarios in SoSo CAD

Compare normal operation with equipment failures and see served loads and capacity shortfalls in the same view.

Normal operation and failure scenario comparison in SoSo CAD

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.