Ultimate Tool Residual Current Monitoring (Janitza RCM White Paper, 07/2025)
Original title Ultimate Tool Residual Current Monitoring
Janitza electronics · Gerald Fritzen
A Janitza white paper covering the working principle of residual current monitoring (RCM), residual current types and RCD types, its link to TN-S systems, limit values and use in data centres.
On this page
Overview
The document stresses that data centres, hospitals and continuous-process industry need at least 99.9% and often 99.9999% power availability: 99% availability means about 87.7 hours of downtime per year in 24-hour operation, against 0.53 minutes for six nines. Residual current monitors (RCMs) are not protective devices; they give an audible or visible signal when a preselected residual current value is exceeded. They thus provide early warning without tripping the circuit and can reduce the shutdowns needed for insulation resistance measurement in the periodic inspections of IEC 60364-6. Visual inspection, protective measures, loop resistance and continuity, and functional tests must still be carried out.
The working principle rests on a summation current transformer: the phases and neutral of the feeder are led through it and the protective conductor is excluded. In the fault-free state the summation current is near zero; if residual current flows to ground, the imbalance is measured in the secondary circuit. Measurement follows IEC/TR 60755:2017. Residual current types are sinusoidal (type AC), pulsating (type A), including smooth DC (type B) and up to 20 kHz (type B+); a type A RCD saturates at 6 mA DC or more, whereas a type A RCM is only affected above 20,000 mA DC. All-current sensitive equipment is needed for frequency converters and three-phase UPS loads.
The document says a TN-S system is mandatory for information technology because it has better EMC properties than TN-C and enables RCM. Vagabond currents flowing through the PE system, data lines and metal parts cause electromagnetic fields, data transmission disturbance, higher capacitor currents and pipe corrosion. DIN EN 50600-2-4 section 6.5 and ISO/IEC 22237-3 require equipment capable of measuring and recording residual currents between protective and neutral conductors in the building's power distribution. In circuits with an RCD, which opens at about 15-18 mA, RCM gives early warning ahead of the disconnection.
The limit values section gives a fixed 30 mA for final circuits up to 32 A and higher values for circuits above 32 A (for example 300 mA for fire protection); fire risk rises from about 300 mA. For frequency converters, at most 5% of phase conductor current is allowed, and for total current at the central grounding point 0.2% to at most 0.5% of the phase current of the feeding transformers. At initial commissioning the typical 'healthy' leakage current should be measured and alarm thresholds set accordingly. The document refers to the manufacturer's devices and GridVis software; limit values are empirical and must be set per consumer type.
Key points
- 99% availability means about 87.7 hours of downtime a year in 24-hour operation; 99.9999% means 0.53 minutes.
- An RCM is not a protective device; it signals when a threshold is exceeded. In an RCD circuit the RCD opens at about 15-18 mA, and RCM can warn beforehand.
- Measurement uses a summation current transformer through which phases and neutral pass, with the protective conductor outside; measurement follows IEC/TR 60755:2017.
- A type A RCD saturates at 6 mA DC or more; a type A RCM is only affected above 20,000 mA DC; type B and B+ are sensitive to all currents up to 20 kHz.
- Frequency converter loads and controlled systems such as three-phase UPS need an all-current sensitive (type B) device.
- Fixed limit: 30 mA for final circuits up to 32 A; higher values for larger circuits (for example 300 mA for fire protection); fire risk rises from about 300 mA.
- Frequency converters: at most 5% of phase current; total current at the central grounding point 0.2% to at most 0.5% of the feeding transformers' phase current.
- DIN EN 50600-2-4 section 6.5 and ISO/IEC 22237-3 require residual current measurement in data centres.
- At commissioning the 'healthy' leakage current level is determined; dynamic limit values avoid false alarms at partial load or insufficient protection at full load.
Using it in design
- Design data centre power distribution as TN-S and show on the single-line diagram the RCM points that measure and record residual current between protective and neutral conductors at building supply points (EN 50600-2-4 section 6.5.1).
- Choose the RCM device type by load: type B or B+ for frequency converter, three-phase UPS and rectifier loads, type A only for sinusoidal and pulsating loads.
- Start final-circuit alarm thresholds at 30 mA (up to 32 A) and 300 mA on fire protection circuits; manage the difference between partial and full load with dynamic limits.
- Add the 'healthy' leakage measurement and the central grounding point total-current limit (0.2%-0.5%) to the commissioning procedure.
- Connect RCM data to the BMS or EPMS by Modbus, SNMP, BACnet or similar, and write into the maintenance plan that RCM can replace insulation resistance inspections while visual and continuity tests continue.
Who should read it
Electrical engineers designing data centre grounding, protection and monitoring architecture, and maintenance teams.
Document contents
- Higher system availability and lower fire hazard
- Continuous monitoring instead of inspections
- RCM as an alternative form of safety
- Required RCDs
- RCM in data centers and EN 50600-2-4
- How residual current monitoring works
- Residual current types and device type selection
- Effects of residual currents on operating equipment
- Limit values and troubleshooting
- Initial commissioning and dynamic limit values
- RCM network system
Publication details
- Authors
- Gerald Fritzen
- Publisher
- Janitza electronics
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public manufacturer source inspected. No document-specific redistribution permission established; metadata and original brief summaries only. Local downloads are research evidence, not a redistribution package.
Citation
Gerald Fritzen (2025). Ultimate Tool Residual Current Monitoring. Janitza electronics. https://assets.janitza.com/2sy6zv1cbi8q/5ti9AKYd3xRUIyNMqZlsUk/b67ecbac731c78863cb0e1a69c19fd66/Whitepaper_EN_RCM.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.