Kingair Integrated Evaporative Condensing Chiller, Technical Catalogue
Original title Kingair Integrated Evaporative Condensing Chiller, printed pp.15–16 (PDF p.9)
Kingair
Kingair (Guoxiang) catalogue for integrated evaporative condensing screw chillers that fold the cooling tower and pumps into the unit, with R22 and R134a tables and a condensing temperature about 4°C below a conventional water-cooled unit.
On this page
Overview
Kingair's catalogue introduces an integrated chiller series that combines a full-liquid-evaporator screw compressor with an evaporative condenser and a refrigeration hydraulic module in one frame. The functions of a traditional water-cooled chiller, cooling tower, condenser, chilled water pumps and constant-pressure make-up are gathered in one unit, so the customer only connects chilled water pipes and power. Uses suggested include metro, hotel, school, mall and hospital central air conditioning and process cooling in pharmaceuticals, chemicals and power electronics.
The efficiency claims are numeric: full liquid evaporation is said to raise thermal efficiency more than threefold over dry evaporators and refrigeration efficiency by 14%; the evaporative condenser lowers condensing temperature by about 4°C, raises efficiency by 12% and removes the cooling water pump. Compressor volumetric efficiency is stated up to 95%, water temperature control accuracy ±0.5°C and bearing life up to 100000 hours.
The catalogue explains the model code: prefix KCWF, capacity number, design version, C for year-round cooling (ambient above -15°C), T/W structure type, M for hydraulic module, V for compressor frequency control, S for a dual-compressor single unit and the refrigerant code (1: R134a, blank: R22). Examples are KCWF1200CZTMV, KCWF2280CZCT1 and KCWF2420CZCTMV-S. It holds separate R22 and R134a performance tables for the standard series and the hydraulic-module series.
On application, site and operating rules are given: altitude above 1000 m, winter temperature below -15°C and salt-spray or corrosive gas environments require consulting the manufacturer. Supply voltage must stay within ±10% of rated, phase-to-phase difference within 2% and current difference within 3%. Below 2°C ambient the chilled water circuit needs antifreeze or draining, and a separate parameter table covers water quality.
Key points
- The unit integrates cooling tower, pumps and make-up functions; the customer only connects chilled water and power.
- The evaporative condenser lowers condensing temperature about 4°C versus a conventional water-cooled unit and raises efficiency by 12%.
- The full liquid evaporator raises efficiency by 14%; its thermal efficiency is stated as more than three times a dry evaporator.
- Screw compressor volumetric efficiency is up to 95%; bearing life up to 100000 hours.
- Stepless capacity control brings water temperature accuracy to ±0.5°C.
- Refrigerant is R22 (no code) or R134a (code 1); the C version is for year-round cooling with ambient above -15°C.
- Controls: Siemens PLC, 10-inch touch screen, dry contact, RS485 and DP communication.
- Supply voltage within ±10% of rated, phase-to-phase voltage difference at most 2%, current difference 3%.
Using it in design
- If altitude exceeds 1000 m, winter falls below -15°C or the atmosphere is salty, share the design condition with the manufacturer before selection.
- For a data centre needing year-round cooling, settle the C version and the antifreeze or draining strategy early; the antifreeze rule applies below 2°C.
- Verify site water supply and treatment design for the evaporative condenser's water use and water quality (hardness, chloride, bacteria).
- Compare the voltage and phase imbalance limits (±10, 2 and 3 percent) with UPS and generator output.
- Pick the correct table, standard or hydraulic module; on hydraulic-module rows the pump power is included in the system total.
Who should read it
Mechanical designers weighing an integrated evaporative solution against water-cooled chillers, and project engineers selecting a self-contained cooling source.
Document contents
- Product overview
- Model description
- Operating range
- Product features and technical advantages
- Standard series performance parameter table (R22 and R134a)
- Performance parameter table with hydraulic module (R22 and R134a)
- Outline dimension diagram and table
- Table of performance correction factors for variable operating conditions
- Unit hoisting and handling
- Installation requirements and water system piping
- Winter operation and antifreeze
- Water quality management
- Electrical wiring
- Standard supply details
Publication details
- Authors
- Kingair
- Publisher
- Kingair
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Kingair Kingair Integrated Evaporative Condensing Chiller, printed pp.15–16 (PDF p.9). Kingair. https://hvacvn.com/wp-content/uploads/2025/10/hvacvn-may-lam-lanh-nuoc-ngung-tu-bay-hoi-tich-hop-kingair-2025.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.