Technical guideFree to read2017

Kirloskar Three Phase Monobloc Pumps, SP-10-2017-01

Original title Kirloskar Three Phase Monobloc Pumps, SP-10-2017-01, hosted by Mittal Machinery

Kirloskar Brothers

Kirloskar Brothers' 50 Hz monobloc pump catalogue: per-model discharge, total head and 0.37-22 kW motor ratings for the SRF, KS+, KDS, KDI and KDT series.

On this page

Overview

The document is Kirloskar Brothers' 2017 three-phase monobloc pump catalogue, coded SP-10-2017-01; the copy hosted on a distributor's site was reviewed. It consists of performance charts for several pump series at 50 Hz and rated voltage.

Each chart lists the model, motor rating (kW and HP), suction and delivery pipe size, rated voltage and discharge in litres per second at set total heads. For example, the 2-pole SRF-2570 with an 18.3 kW motor gives 23.0 l/s at 44 m and 12.0 l/s at 72 m; the 4-pole KS-810+ with a 5.5 kW motor gives 66.0 l/s at 5 m.

According to the technical specification table the series ranges are: KDS up to 76 m and 49 l/s, KDI up to 76 m and 39 l/s, KDT up to 110 m and 20 l/s, KS up to 22 m and 72.5 l/s, SRF up to 94 m and 28.5 l/s. A note states that all pumps except KS-810+ and KS-1012+ are ISI certified.

The tables give the general operating range of the model family; they are not duty points selected for a particular plant. Motor rating differs from measured electrical consumption at the chosen flow, so the pump curve and efficiency data must be obtained separately for energy calculations.

Key points

  1. The KDS series reaches 76 m and 49 l/s with 0.37-22 kW motors.
  2. KDI reaches 76 m and 39 l/s with 1.5-22 kW; KDT reaches 110 m and 20 l/s with 3.7-15 kW.
  3. KS reaches 22 m and 72.5 l/s with 2.2-7.5 kW; SRF reaches 94 m and 28.5 l/s with 18.3-22 kW motors.
  4. SRF-3085 (22 kW, 415 V, 100/100 mm) gives 28.5 l/s at 32 m and 13.6 l/s at 76 m.
  5. KS-810+ (5.5 kW, 150 mm, 1420 rpm) gives 66.0 l/s at 5 m and 43.5 l/s at 10 m.
  6. KS-1012+ (7.5 kW, 150 mm) gives 72.5 l/s at 6 m; the KS+ series is 4-pole and runs at 1400-1430 rpm.
  7. Voltage in the tables is 400 or 415 V.
  8. All pumps except KS-810+ and KS-1012+ are ISI certified.

Using it in design

  • In pump pre-selection, match design flow and total head to the nearest table value and check motor rating and pipe sizes (suction and delivery).
  • Use the chart values as a family range, not as an operating point; confirm the real duty at the intersection of system and pump curves.
  • Do not substitute motor rating for electrical consumption; request shaft power and efficiency at the selected flow for energy calculations.
  • Compare voltage (400 or 415 V) and frequency (50 Hz) with the plant electrical design.
  • Match certification status (ISI) with the document requirements of the project specification.

Who should read it

Mechanical engineers and purchasing teams selecting cooling-water and auxiliary water pumps.

Document contents

  1. Performance chart: SRF series (2 pole)
  2. Performance chart: KS+ series (4 pole)
  3. Technical specification comparison (KDS, KDI, KDT, KS, SRF)
  4. Performance chart: KDS+ / KDS++ / GMC series

Publication details

Authors
Kirloskar Brothers
Publisher
Kirloskar Brothers
Year
2017
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Kirloskar Brothers (2017). Kirloskar Three Phase Monobloc Pumps, SP-10-2017-01, hosted by Mittal Machinery. Kirloskar Brothers. https://mittalmachinery.in/downloads/products/KIRLOSKAR_PUMP/KDS-KS-KDT-SRF-KDI%20Catalogue%20FINAL%20Folder_CTP%20V2.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.