KDCC Green Data Centre Certification, Version 5
Original title Green Data Centre Certification: assessment version 5
Korea Data Center Council (KDCC)
The Korea Data Center Council's voluntary Green Data Centre certification scores Version 5 as 60 of 100 points for PUE and 40 for green activities, with four grades from Bronze to Platinum.
On this page
Overview
The Green Data Centre (GDC) certification is a voluntary, privately run scheme that verifies a data centre's energy efficiency through criteria and conformity review. It awards a grade to facilities that achieve efficiency above a threshold, or verifies efficiency. Its background is rising data-centre energy use, negative perception, the national energy-saving goal and operators' growing demand for third-party verification of efficiency for ESG management.
There are three certification types: the main certification that awards a grade (one year of operating data), a preliminary certification for sites with limited operating data (at least three months of data) and a design certification in which an evaluation panel quantitatively verifies PUE at design stage. The data centre must exceed a set size under Article 40 of the Framework Act on Intelligent Informatization enforcement rule (500 square metres or more), be owned by the applicant and measure and manage cumulative electricity consumption.
In Version 5 the assessment has two parts: 60 points for the data-centre infrastructure efficiency indicator, PUE (ISO/IEC 30134-2 measurement method is followed), and 40 points for the green activity indicator. Grades are Bronze at 60 to under 70 points, Silver 70 to under 80, Gold 80 to under 90 and Platinum 90 and above. The certificate is valid for one year from the certification date.
Benefits listed include system-by-system energy efficiency diagnosis and identifying TCO-reducing factors, improvement recommendations, external communication use, meeting K-taxonomy green finance conditions and, when applying for best available techniques (BAT), exemption from an additional adjustment coefficient on greenhouse gas allocation through third-party verification. The page does not give scoring detail such as the green activity items.
Key points
- A voluntary, privately run certification with three types: main, preliminary and design.
- Version 5 scoring: PUE indicator 60 points, green activity indicator 40 points; PUE measurement follows ISO/IEC 30134-2.
- Grades: 60 to 70 points Bronze, 70 to 80 Silver, 80 to 90 Gold, 90 and above Platinum.
- Certificate validity is one year from the certification date.
- The facility must be 500 square metres or larger and owned by the applicant.
- Cumulative electricity metering is required: one year for the main certification, at least three months for preliminary, not applicable for design.
- In the design certification, PUE is quantitatively verified by the evaluation panel at design stage.
- Benefits: system-level energy diagnosis, TCO-reducing factors, K-taxonomy green finance conditions and BAT-related greenhouse gas allocation exemption.
Using it in design
- For a facility of 500 square metres or more in Korea, treat the design certification as a stage for third-party verification of the PUE target.
- Add the cumulative energy metering needed for certification (12 months for main, 3 months for preliminary) to the metering plan and diagram from the start.
- Design PUE measurement to ISO/IEC 30134-2 boundaries and points; 60% of the certification score rests on it.
- Use the 60/40 score split to plan green activity items too; a PUE-only design leaves points unclaimed.
- Add the green finance and emission allocation benefits to the investment case.
Who should read it
Teams designing and operating data centres in the Korean market and sustainability managers comparing a national third-party efficiency certification.
Document contents
- Introduction to the certification
- Certification types (main, preliminary, design)
- Background
- Eligibility and requirements
- Assessment criteria (Version 5)
- Certification grades
- Benefits
- Certification mark and symbol
Publication details
- Authors
- Korea Data Center Council (KDCC)
- Publisher
- Korea Data Center Council (KDCC)
- Year
- Year not stated
- Document number
- Assessment version 5
- Document language
- Korean
- Source type
- Industry body
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public publisher text inspected. No document-specific commercial redistribution permission established; metadata and original short summaries only.
Citation
Korea Data Center Council (KDCC) Green Data Centre Certification: assessment version 5. Korea Data Center Council (KDCC). Assessment version 5. https://kdcc.or.kr/green/pageview.do?keyvalue=green&url=green01
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.