KSTAR FocusAir In-Row Precision Cooling Technical Specifications
KSTAR
Technical table for the KSTAR FocusAir in-row precision cooling family: 300, 400 and 600 mm wide DX models give 25.1 to 40.4 kW and chilled-water models 25.1 to 67 kW total capacity.
On this page
Overview
The document contains the technical specification tables of the KSTAR FocusAir in-row precision cooling family. The first block is direct-expansion (DX) units: FS 20, 25 and 40 give 25.1, 25.5 and 40.4 kW total and sensible capacity and 4920, 5050 and 8080 m3/h air volume. Sensible heat ratio is 1, so total and sensible capacity are equal. Every model has one compressor, 380-415 V 50 Hz 3-phase supply, 3 and 6 kW heating and 3 kg/h humidifying; units are offered in single-cooling and constant temperature and humidity configurations.
The second block covers chilled-water units: for FS 25, 35 and 65 total capacity is 25.1, 35.5 and 67 kW, air volume 5100, 6500 and 12000 m3/h, water flow 4.7, 6.5 and 12 m3/h, pressure drop 45, 55 and 60 kPa and pipe size 28, 32 and 42 mm. Width is 300, 400 and 600 mm, depth 1100 mm, height 2000 mm; weights are 230-315 kg for DX and 190-275 kg for chilled-water models. Chilled-water models come in 200-240 V single-phase and 380-415 V 3-phase variants.
Per the footnotes, air- and water-cooled unit data are based on 37 °C and 25% RH return air; chilled-water data use the same return air with 10/15 °C inlet/outlet water. Noise data are sound pressure at 10 m free field. Minimum working temperature is -20 °C for the standard outdoor unit and -40 °C for the low-temperature unit. The second table block is headed 'DX Unit' but contains water flow and a water footnote; the models should be read as chilled-water, and the FS*** name is not a full order code.
Key points
- DX models: FS 20/25/40 give 25.1, 25.5, 40.4 kW; air volume 4920-8080 m3/h.
- Chilled-water models: FS 25/35/65 give 25.1, 35.5, 67 kW; water flow 4.7-12 m3/h.
- Return air 37 °C and 25% RH; chilled water 10/15 °C.
- Sensible heat ratio 1; total and sensible capacity equal.
- Width 300/400/600 mm, depth 1100 mm, height 2000 mm.
- DX models: one compressor, 3-6 kW heating, 3 kg/h humidifying; 380-415 V 3-phase.
- Outdoor unit minimum working temperature -20 °C (standard) and -40 °C (low temperature).
Using it in design
- Use capacity at the 37 °C return-air condition; 10/15 °C water differs from a typical data-hall water regime, so have capacity confirmed by the maker.
- Carry chilled-water flow and the 45-60 kPa pressure drop into pipe and pump calculation.
- Take full load current (22.7-38.5 A for DX models) into UPS and panel sizing.
- Do not confuse the unit name with an order code; confirm model and configuration (front air supply, constant temperature/humidity) with the maker.
- Choose the outdoor-unit lower temperature limit by site climate (-20 or -40 °C).
Who should read it
Mechanical designers selecting in-row precision cooling and data-hall planners.
Document contents
- DX unit technical specification (FS 20, 25, 40)
- Chilled-water unit technical specification (FS 25, 35, 65)
- Parameter table notes
Publication details
- Authors
- KSTAR
- Publisher
- KSTAR
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
KSTAR KSTAR FocusAir In-Row Precision Cooling Technical Specifications. KSTAR. https://www.datasphere.com.sg/wp-content/uploads/2023/10/In-Row-Precision-Cooling-FocusAir-Family-Technical-Specs.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.