KSTAR FocusAir In-Row Precision Cooling Technical Specifications

KSTAR

Technical table for the KSTAR FocusAir in-row precision cooling family: 300, 400 and 600 mm wide DX models give 25.1 to 40.4 kW and chilled-water models 25.1 to 67 kW total capacity.

On this page

Overview

The document contains the technical specification tables of the KSTAR FocusAir in-row precision cooling family. The first block is direct-expansion (DX) units: FS 20, 25 and 40 give 25.1, 25.5 and 40.4 kW total and sensible capacity and 4920, 5050 and 8080 m3/h air volume. Sensible heat ratio is 1, so total and sensible capacity are equal. Every model has one compressor, 380-415 V 50 Hz 3-phase supply, 3 and 6 kW heating and 3 kg/h humidifying; units are offered in single-cooling and constant temperature and humidity configurations.

The second block covers chilled-water units: for FS 25, 35 and 65 total capacity is 25.1, 35.5 and 67 kW, air volume 5100, 6500 and 12000 m3/h, water flow 4.7, 6.5 and 12 m3/h, pressure drop 45, 55 and 60 kPa and pipe size 28, 32 and 42 mm. Width is 300, 400 and 600 mm, depth 1100 mm, height 2000 mm; weights are 230-315 kg for DX and 190-275 kg for chilled-water models. Chilled-water models come in 200-240 V single-phase and 380-415 V 3-phase variants.

Per the footnotes, air- and water-cooled unit data are based on 37 °C and 25% RH return air; chilled-water data use the same return air with 10/15 °C inlet/outlet water. Noise data are sound pressure at 10 m free field. Minimum working temperature is -20 °C for the standard outdoor unit and -40 °C for the low-temperature unit. The second table block is headed 'DX Unit' but contains water flow and a water footnote; the models should be read as chilled-water, and the FS*** name is not a full order code.

Key points

  1. DX models: FS 20/25/40 give 25.1, 25.5, 40.4 kW; air volume 4920-8080 m3/h.
  2. Chilled-water models: FS 25/35/65 give 25.1, 35.5, 67 kW; water flow 4.7-12 m3/h.
  3. Return air 37 °C and 25% RH; chilled water 10/15 °C.
  4. Sensible heat ratio 1; total and sensible capacity equal.
  5. Width 300/400/600 mm, depth 1100 mm, height 2000 mm.
  6. DX models: one compressor, 3-6 kW heating, 3 kg/h humidifying; 380-415 V 3-phase.
  7. Outdoor unit minimum working temperature -20 °C (standard) and -40 °C (low temperature).

Using it in design

  • Use capacity at the 37 °C return-air condition; 10/15 °C water differs from a typical data-hall water regime, so have capacity confirmed by the maker.
  • Carry chilled-water flow and the 45-60 kPa pressure drop into pipe and pump calculation.
  • Take full load current (22.7-38.5 A for DX models) into UPS and panel sizing.
  • Do not confuse the unit name with an order code; confirm model and configuration (front air supply, constant temperature/humidity) with the maker.
  • Choose the outdoor-unit lower temperature limit by site climate (-20 or -40 °C).

Who should read it

Mechanical designers selecting in-row precision cooling and data-hall planners.

Document contents

  1. DX unit technical specification (FS 20, 25, 40)
  2. Chilled-water unit technical specification (FS 25, 35, 65)
  3. Parameter table notes

Publication details

Authors
KSTAR
Publisher
KSTAR
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

KSTAR KSTAR FocusAir In-Row Precision Cooling Technical Specifications. KSTAR. https://www.datasphere.com.sg/wp-content/uploads/2023/10/In-Row-Precision-Cooling-FocusAir-Family-Technical-Specs.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.