Technical guideFree to read2024

Kuken CT-9 Cooling Tower General Catalog, December 2024

Original title Kuken Cooling Tower Catalogue CT-9-2412

Kuken

Kuken Kogyo's Japanese-language CT-9 catalog (December 2024) presents open and closed cooling towers with low-noise and plume-abatement series, an underblow pipe cutting blowdown time by about 40%, and freeze protection options.

On this page

Overview

The document is the CT-9 general cooling tower catalog issued at the end of 2024 by the Japanese manufacturer Kuken Kogyo (Kuken), written in Japanese. A cooling tower is described as an auxiliary of the chiller, a machine that cools water using the latent heat of evaporation. The catalog offers open (water in direct contact with air) and closed (indirect contact) towers in standard, low-noise (R), ultra-low-noise (S), energy-saving ultra-low-noise (N, open type only), extremely-low-noise (E, standard only) and plume-abatement (M) series.

The selection section explains the model code: open or closed, single or double inlet, series, capacity, chiller type (inlet water 37 °C for centrifugal, 37.5 °C for absorption), noise class and plume preference. The method is to pick the column matching inlet and outlet water temperature and outdoor wet-bulb, then the row exceeding the required water flow. In the example, an absorption chiller with 37.5/32 °C water, 27 °C wet-bulb and 11.0 m³/h flow selects SKCL-11 GRo.

It also introduces the underblow pipe, which discharges concentrated water first; in an SKBL-225R test (ΔTw 5 °C, 102 m³/h, 8 hours) the blowdown time needed to cut conductivity by 25% falls from about 6.0 hours to 3.5 hours (about 40% shorter). Other products are large-capacity open towers, a heating tower system, radiators, the Ultra Fan direct-drive fan and the HFD flat-belt system. The technical data section covers freeze protection, vibration isolation, water quality, maintenance and installation cautions.

The document is a general HVAC and industrial cooling tower product catalog, not a data-center-specific design guide, but its tower selection method, noise classes and water-saving features serve as a reference for cooling water plant design.

Key points

  1. Open (direct contact) and closed (indirect contact) towers; in closed models the circulating water stays enclosed, which eases water quality management.
  2. Noise classes: R (low), S (ultra-low), N (energy-saving ultra-low, open type only), E (extremely low, standard only); M is the plume-abatement series.
  3. Selection needs inlet and outlet water temperature and outdoor wet-bulb; tables assume 37 °C inlet water for centrifugal chillers and 37.5 °C for absorption chillers.
  4. Selection example: 37.5/32 °C water, 27 °C wet-bulb, 11.0 m³/h gives SKCL-11 GRo.
  5. The underblow pipe shortens blowdown time by about 40% (6.0 to 3.5 hours, SKBL-225R, ΔTw 5 °C, 102 m³/h) and reduces make-up water.
  6. Plume abatement mixes dry and wet fill sections; M7, M4 and M2 types exist, with no moving or controlled parts.
  7. Shipping forms: one-piece, two- or three-section, or split into parts; the part-split form suits elevator delivery.
  8. Options include freeze protection parts (plug heaters, basin heaters), vibration isolation, tower-integrated chemical dosing and a water quality guideline.
  9. Since 2022 a LEED-compatible drift eliminator option is offered.

Using it in design

  • When selecting a cooling tower, set tower inlet temperature by chiller type (37 or 37.5 °C), design wet-bulb and flow, and confirm capacity against the manufacturer's tables.
  • Where siting limits apply (neighbours, noise limits), check the noise class (R, S, N, E) against dB(A) values after capacity selection.
  • For water-saving targets, include the underblow pipe and blowdown management options in make-up water (WUE) calculation.
  • A closed tower can reduce the need for an intermediate heat exchanger on critical circuits that must avoid circulating-water fouling; compare efficiency and approach.
  • In cold climates evaluate freeze protection heaters and drain arrangements; on dense sites evaluate the plume-abatement series.

Who should read it

Mechanical engineers and procurement teams selecting cooling towers and designing water-cooled chiller plants.

Document contents

  1. Kuken cooling towers and the role of a cooling tower
  2. Model selection by application and conditions
  3. Water saving with the underblow pipe
  4. Open cooling towers (standard, low-noise, ultra-low-noise, plume abatement)
  5. Closed cooling towers
  6. Other products (large-capacity open tower, heating tower, radiator, Ultra Fan, HFD system)
  7. Technical data (parts specifications, noise standard, options, freeze protection, vibration isolation, chemical dosing, water quality, maintenance, design, transport, installation and maintenance cautions)

Publication details

Authors
Kuken
Publisher
Kuken
Year
2024
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Kuken (2024). Kuken Cooling Tower Catalogue CT-9-2412. Kuken. https://www.kuken.com/wp-content/uploads/2024/12/CT-9-2412.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.