Leveraging Intelligent PDUs and Monitoring: Rack Power Solutions for Modern AI Applications
Legrand
This Raritan/Server Technology (Legrand) paper works out how to feed 60-100 kW AI racks through inlet plug choice, server PSU redundancy and PDU count. Three worked applications apply the arithmetic to named server models.
On this page
Overview
The starting point is the density jump: racks that used to run 15-20 kW now exceed 60 kW for AI and can reach 100 kW. The question therefore becomes less how many outlets a PDU offers and more how many kW the inlet plug and circuit can carry. Table 2 converts common high-current inlets to usable kW with the 20 % UL/NEC derating: 208 V 60 A gives 17.3 kW, 208 V 100 A gives 28.8 kW, 415 V 60 A gives 34.5 kW, 415 V 100 A gives 57.5 kW and 480 V 100 A gives 66.5 kW.
IEC-market equivalents follow: 400 V 63 A gives 41.5-43.6 kW and 400 V 125 A gives 82.3-86.6 kW. On the server side, Table 3 lists maximum power: A100 6.5 kW (3+3 PSU), H100/H200/B100 HGX 10.2 kW (4+2), B200 12 kW and MI300X 10.2 kW. Because PSU redundancy may be 3+3, 4+2 or 5+1, the PDU count and per-path load for the same server change with the scheme chosen.
Hardware details get their own treatment. C21 outlets carry the same 20 A/250 V as C20 but with a thermal rating up to 155 C, while Saf-D-Grid and RF-203 support 480/277 V operation. The paper notes that traditional 5 kAIC branch breakers may be inadequate for AI racks and recommends 10 kAIC breakers or fuses. It also cites an ASHRAE supply range of 15-32 C and 20-80 % RH.
Three applications close the calculation. Eight Dell XE8640 servers at 208 V/60 A exceed 60 kW. Six XE9680 servers at 415 V/60 A use 5+1 PSU redundancy and need 4 PDUs, or 6 if PDU redundancy is also required. Temperature, leak and vibration sensors are added to the examples. This is a manufacturer publication using mostly North American figures, so comparison with local rules is left to the reader.
Key points
- Racks that ran 15-20 kW now exceed 60 kW for AI and can reach 100 kW.
- Derated inlet capacities: 208 V 60 A 17.3 kW; 208 V 100 A 28.8 kW; 415 V 60 A 34.5 kW; 415 V 100 A 57.5 kW; 480 V 100 A 66.5 kW.
- IEC inlets: 400 V 63 A 41.5-43.6 kW; 400 V 125 A 82.3-86.6 kW.
- GPU server maximum power: A100 6.5 kW (3+3), H100/H200/B100 HGX 10.2 kW (4+2), B200 12 kW, MI300X 10.2 kW.
- C21 outlets match C20's 20 A/250 V with a thermal rating to 155 C.
- Saf-D-Grid and RF-203 outlets support 480/277 V operation.
- 5 kAIC branch breakers may be inadequate; 10 kAIC breakers or fuses are recommended for AI racks.
- 6 x XE9680 at 415 V/60 A with 5+1 PSUs needs 4 PDUs, or 6 with PDU redundancy.
Using it in design
- Calculate rack power from voltage, current and connector ratings, applying the 80% continuous-load factor to establish usable kW per feed.
- Check rack IT load against N+N feed capacity so each path can carry the whole rack alone.
- Catalogue GPU servers with PSU count and redundancy scheme (N+N vs N+M) so PDU count and per-path load compute correctly.
- Flag AI racks using 5 kAIC branch protection and check outlet type against PSU inlet (C19/C20/C21, Saf-D-Grid).
Who should read it
Electrical designers sizing rack power distribution for AI racks above 60 kW.
Related standards
- IEC 60309
- UL 60950/62368
- NEC Article 645
- ASHRAE 90.4
Publication details
- Authors
- Legrand
- Publisher
- Legrand
- Year
- 2026
- Document number
- LIT# V2295 R5
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Legrand (2026). Leveraging Intelligent PDUs and Monitoring: Rack Power Solutions for Modern AI Applications. Legrand. LIT# V2295 R5. https://cdn10.servertech.com/assets/documents/documents/1159/original/PAC_Power-White-Paper_Solutions-for-Modern-AI-Applications_R5_V2295.pdf?1769113152
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.