Characterization of high-resolution AI data center training workloads on single and multiple GPU nodes
Scientific Data (Springer Science and Business Media LLC) · Ahmed Abd Elaziz Elsayed, Abdullah Azhar Al-Obaidi et al.
A 2026 Scientific Data dataset records 32 AI training sessions on H100 and B200 8-GPU nodes and 40 on RTX 3060 GPUs at sub-second resolution, with over 1.8 million samples.
On this page
Overview
The paper presents an open-access dataset recording the power, utilisation, memory and temperature behaviour of AI training workloads at sub-second resolution. The aim is to understand the strain on data-centre infrastructure and grid stability and to link the energy consumption profiles of AI workloads with power grid dynamics. It notes that existing datasets typically have sampling intervals of minutes to hours, too coarse to capture the sub-second fluctuations that dominate AI training.
The dataset contains 32 training sessions on H100 and B200 8-GPU nodes and 40 sessions on consumer-grade NVIDIA GeForce RTX 3060 GPUs, with over 1.8 million samples. Each session records node power, per-GPU power, CPU and GPU utilisation, memory usage and temperature. Tasks cover forecasting, classification, reinforcement learning, and text and image generation. Node-scale experiments ran on a Lambda Cloud virtual machine with 208 virtual CPU cores and 8 GPUs.
Technical validation examines sampling-interval stability, conformance to hardware power and thermal limits, cross-comparison of separate measurement sources, and correlations among power, utilisation, temperature and current. Measurements stay within manufacturer-specified thermal and power envelopes, and the correlations are consistent with processor and GPU behaviour. Raising batch size from 128 to 512 lifts peak node GPU power from about 4.5 kW to 6.6 kW and shortens epoch time by about 30-35%.
A stated limit: ambient temperature and data-centre cooling configuration are not included and may influence absolute thermal readings. The dataset is a foundation for modelling AI data-centre energy behaviour, system-level performance analysis and grid connection impact assessment studies; code is open in a GitHub repository.
Key points
- 32 training sessions were recorded on H100 and B200 8-GPU nodes and 40 on RTX 3060 GPUs.
- Over 1.8 million samples are at sub-second resolution.
- Recorded quantities: node power, per-GPU power, CPU and GPU utilisation, memory and temperature.
- Tasks cover forecasting, classification, reinforcement learning, and text and image generation.
- Node experiments ran on a Lambda Cloud virtual machine with 208 vCPUs and 8 GPUs (H100 or B200).
- Raising batch size from 128 to 512 lifts peak node GPU power from about 4.5 kW to 6.6 kW and shortens epoch time by about 30-35%.
- Measurements stayed within manufacturer power and thermal limits; correlations of power, utilisation, temperature and current match expected behaviour.
- The introduction cites power densities that in some cases exceed 60 kW per cabinet.
- Ambient temperature and cooling configuration are not included.
Using it in design
- In AI hall electrical design, use the sub-second fluctuation profile (peak and rate of change), not average power, as input to UPS, generator and grid connection studies.
- Allow margin in rack and node power budgets, noting that training parameters such as batch size change peak power.
- Consider this open dataset as a source of realistic load profiles for grid connection impact assessment and load modelling.
- Because the dataset has no cooling or ambient information, model facility conditions separately for thermal design.
Who should read it
Electrical and grid connection engineers, researchers and capacity planners modelling AI data-centre load profiles.
Document contents
- Abstract
- Background and summary
- Methods (measurements and dataset scope, AI training and monitoring tools setup)
- Data records
- Technical validation
- Usage notes
- Data and code availability
Publication details
- Authors
- Ahmed Abd Elaziz Elsayed; Abdullah Azhar Al-Obaidi; Hany E. Z. Farag
- Publisher
- Scientific Data (Springer Science and Business Media LLC)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY-NC-ND 4.0: share unaltered with attribution for noncommercial purposes
Original licence note
Licence CC-BY-NC-ND-4.0 stated on publisher landing page (fetched 2026-11-16); matches Crossref licence metadata. Non-commercial licence: link/cite only in a commercial product.
Citation
Ahmed Abd Elaziz Elsayed; Abdullah Azhar Al-Obaidi; Hany E. Z. Farag (2026). Characterization of high-resolution AI data center training workloads on single and multiple GPU nodes. Scientific Data (Springer Science and Business Media LLC). https://doi.org/10.1038/s41597-026-07496-6
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.