Dry-Type Transformer User Manual

Original title Kuru Tip Transformatör Kullanım Kılavuzu

Legrand Türkiye / Bticino

A Legrand Türkiye/Bticino manual defines transport, installation, torque values, ventilation, thermal protection, energisation and maintenance of dry-type transformers with numerical values.

On this page

Overview

The manual is a Turkish-language user document for dry-type transformers manufactured by Bticino S.p.A. Its sections are standards, nameplate, transport and storage, installation, operation, maintenance and further information. Referenced standards are IEC 60076-11 (dry type), 60076-1, -2, -3, -5, IEC 60085 (insulation class), IEC 60270, IEC 60529 (IP code) and IEC 60905. It stresses at the start that all work be done de-energised and that the unit not be energised without earthing.

The transport section requires fixing the transformer through the holes in the upper frame, moving it no more than 10 m on wheels, reporting transport damage within 3 days, and in storage keeping the PVC packaging on and the ambient temperature above -25 °C. For installation the transformer is for indoor use: maximum operating temperature +40 °C, daily average +35 °C, yearly average +20 °C. For outdoor or special temperatures a metal enclosure of at least IP21 is needed.

Distances are given by voltage class: for enclosure-free (IP00) installation the distance between cables and transformer is ≥125 mm for ≤12 kV, ≥170 mm for ≤17.5 kV, ≥225 mm for ≤24 kV and ≥320 mm for ≤36 kV. The screw torque table gives separate electrical-connection values for steel and brass (for example M12: 60-70 Nm steel, 40-50 Nm brass). Because the transformer is not fully insulated against touch, it must be installed in an enclosure or lockable compartment accessible only to authorised persons.

For ventilation about 3.5-4 m³ of air per minute is needed for each kW the transformer loses; if fans are used they sit at least 500 mm from each side and have a life of about 20,000 hours. PT100 thermal probes are standard; with an electronic temperature control unit, alarm and trip settings are 140/155 °C for class H, 130/140 °C for F and 110/120 °C for B. The earth conductor is at least 16 mm² or sized by fault current; tap settings are -5%, -2.5%, 0, +2.5%, +5%. In maintenance, windings are cleaned every 6 months with air at a maximum of 3 bar and a dry cloth; insulation resistance must be at least 5 MΩ LV-earth and 20 MΩ HV-earth and HV-LV.

Key points

  1. Standards: IEC 60076-11, 60076-1/-2/-3/-5, IEC 60085, 60270, 60529 and 60905.
  2. Indoor use: maximum +40 °C, daily average +35 °C, yearly average +20 °C; storage must not go below -25 °C.
  3. Wheeled transport at most 10 m; transport damage reported within 3 days.
  4. Enclosure-free clearance: ≤12 kV ≥125 mm, ≤17.5 kV ≥170 mm, ≤24 kV ≥225 mm, ≤36 kV ≥320 mm.
  5. Torque example: M12 electrical connection 60-70 Nm steel, 40-50 Nm brass; mechanical connection M12 60 Nm.
  6. Ventilation: about 3.5-4 m³ per minute per kW of transformer loss; fan life about 20,000 hours.
  7. PT100 probes standard; alarm/trip: H 140/155 °C, F 130/140 °C, B 110/120 °C.
  8. Earth conductor ≥16 mm² or by fault current; taps ±2.5% and ±5%.
  9. Minimum insulation resistance: LV-earth 5 MΩ, HV-earth 20 MΩ, HV-LV 20 MΩ (megger above 1000 V).

Using it in design

  • Limit access to the transformer room to authorised staff; an enclosure or lockable compartment is mandatory.
  • Put the in-enclosure clearances (A, B, C) by voltage class into the plan and use the minimum distances for enclosure-free installation.
  • Calculate ventilation airflow from transformer losses (3.5-4 m³/min per kW); if fans are used, add their placement and 20,000-hour replacement life to the maintenance plan.
  • Set thermal protection relay values by insulation class (H, F, B).
  • Include torque, earthing, transport-damage and insulation-resistance checks in the commissioning acceptance procedure.

Who should read it

Electrical engineers and technicians installing, commissioning and maintaining dry-type transformers in data centres and facilities.

Document contents

  1. Protection level
  2. Standards
  3. Nameplate
  4. Transport, receipt and storage
  5. Installation (enclosure installation, enclosure-free installation, LV and HV connections, torque values, location, ventilation, overvoltage, thermal management systems)
  6. Operation (earthing, connections, cleaning, tap settings, energisation)
  7. Maintenance (maintenance recommendations, troubleshooting, after-sales service)
  8. Further information

Publication details

Authors
Legrand Türkiye / Bticino
Publisher
Legrand Türkiye / Bticino
Year
Year not stated
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official publisher material inspected. No document-specific commercial redistribution permission established; retain metadata and original short summaries only.

Citation

Legrand Türkiye / Bticino Kuru Tip Transformatör Kullanım Kılavuzu. Legrand Türkiye / Bticino. https://www.legrand.com.tr/pdf/Kuru-tip-trafo-garanti-belgesi-ve-kullanim-klavuzu.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.