Data Center UPS: The Essential Characteristics of an Optimised Solution
Legrand
A Legrand white paper that frames data-centre UPS selection around continuity, total cost of ownership and adaptability; its main message is that the efficiency curve at partial load matters more than peak efficiency.
On this page
Overview
The paper organises UPS selection under three themes: continuity (availability, MTTR, N+1, hot-swap), total cost of ownership (efficiency, battery management, component life, serviceability) and adaptability to load, electrical infrastructure, room and user. It contrasts conventional parallel UPSs with modular and scalable-modular architectures.
On continuity, MTTR for modular UPSs can be about 30 minutes (power-module swap) versus roughly 1-4 h for conventional units; the vendor table lists Keor MOD/UPSaver 0.5 h, Keor HPE 1-4 h and Keor XPE 3-6 h. In the N+1 example, a 1000 kW N+1 modular system built from 333 kW modules needs 1333 kW installed, whereas conventionally it could be 6 x 200 kW, 5 x 250 kW or 3 x 500 kW units in parallel. Scalable systems reach 2.1 MW with 250/300 kW power units, and 2.67 MW (up to 21 MW in parallel) with 333 kW units.
On energy, the cited split is IT equipment about 55%, cooling about 30%, power infrastructure including UPS losses about 12% and lighting about 3%. UPS load is usually below 50%, and the cited efficiency curve peaks (up to 96.6%) in the 20-50% load band. For a 10 MW data centre a 1-point efficiency gain (95.5% to 96.5%) saves about USD 1.3 million of OpEx over 10 years; OpEx is typically 60-75% of UPS TCO.
The pay-as-you-grow examples show capacity added in steps with efficiency staying nearly flat, and the load-variation cases (a maintenance week from 75% to 50%, a cooling UPS varying up to 35%) change efficiency by only about 0.5%. This is a vendor publication, with figures drawn from Legrand product families.
Key points
- MTTR is about 30 minutes for modular UPSs (module swap) versus roughly 1-4 h for conventional units.
- A 1000 kW N+1 modular system from 333 kW modules needs 1333 kW installed; conventional alternatives are 6 x 200, 5 x 250 or 3 x 500 kW.
- Energy split: IT about 55%, cooling about 30%, power infrastructure incl. UPS losses about 12%, lighting about 3%.
- For a 10 MW data centre, raising UPS efficiency from 95.5% to 96.5% saves about USD 1.3 million OpEx over 10 years.
- OpEx is typically 60-75% of UPS TCO; CapEx plus installation 25-40%.
- UPS load is usually below 50%; the efficiency curve peaks (up to 96.6%) in the 20-50% load band.
- Scalable systems: 250/300 kW units reach 2.1 MW per system; 333 kW units 2.67 MW, up to 21 MW in parallel.
- Load-variation examples change efficiency by only about 0.5%.
Using it in design
- Compare conventional, modular and scalable modular UPS architecture, module rating, maximum parallel units, MTTR and hot-swap capability. Record efficiency at 25%, 50%, 75% and 100% load.
- Compute installed kW for N+1 as ceil(load/module)+1 modules and show the over-provisioning percentage.
- Warn when the expected operating point (2N halves the load) falls outside the vendor's peak-efficiency band.
- Treat an OpEx share of 60–75% as a scenario assumption in the TCO study, and calculate ten-year loss costs for each efficiency point.
Who should read it
Electrical designers and cost owners choosing UPS architecture, module granularity and efficiency curve.
Related standards
- IEC 62040-3
Publication details
- Authors
- Legrand
- Publisher
- Legrand
- Year
- 2022
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Legrand (2022). Data Center UPS: The Essential Characteristics of an Optimised Solution. Legrand. https://legrand.com/datacenter/sites/g/files/ocwmcr716/files/2025-05/Data%20Center%20UPS%20The%20Essential%20Characteristics%20of%20an%20Optimised%20Solution.zip
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.