Environmental Data Center Management & Monitoring
Legrand
This Legrand white paper explains which environmental sensors a white space needs and how to place them along aisles and on cabinets. As supply temperatures creep toward the top of the ASHRAE envelope, rack-level sensing becomes a design decision rather than an afterthought.
On this page
Overview
The paper opens by noting that legacy rooms were often held near 60 F (16 C), while the ASHRAE recommended range it cites is 65-80 F (18-27 C) and 20-80 % RH. Around 80 F is also where server fans begin to speed up. As operators push toward the top of that range, knowing each rack's inlet condition matters more than a room-average reading, and the text argues that measurement must cover several quantities, not temperature alone.
The sensor inventory has eight headings: temperature, humidity, differential pressure, airflow, leak, door, shock/vibration and air quality. The placement rule is concrete. Put at least one measuring point every 10-30 ft (3-9 m) of aisle or on every fourth cabinet, and measure aisle temperature about 4.9 ft (1.5 m) above the floor. That spacing is meant to expose a hot spot at aisle scale instead of leaving it hidden between sensors.
Psychrometric worked examples show why humidity gets its own sensor. Outside air at 40 F and 50 % RH, warmed to roughly 80 F, ends below 15 % RH, under the 20 % recommendation. In the opposite direction, 75 F air at 50 % RH carries about 0.019 lb of water per lb of air but saturates at about 0.004 lb/lb at 32 F, so the excess condenses on cold glass. Both cases tie economiser operation and cold surfaces to a measurable risk.
For vibration, the limit follows the most sensitive device in the cabinet: if two servers tolerate 5 g and 12 g peak shock, the cabinet should stay below the lower 5 g value. The closing section lists buying criteria, with an example specification of +/-2 C temperature accuracy, +/-5 % RH accuracy and up to 32 sensor packages cascaded over Cat5/6, plus DCIM integration. The author is a manufacturer, so the product-selection part reflects a vendor view.
Key points
- Legacy rooms were often held near 60 F (16 C); the cited ASHRAE recommendation is 65-80 F (18-27 C) and 20-80 % RH.
- About 80 F is near the point where server fans speed up.
- Place one measuring point every 10-30 ft (3-9 m) of aisle or every fourth cabinet.
- Aisle temperature is measured about 4.9 ft (1.5 m) above the floor.
- 40 F / 50 % RH outside air warmed to about 80 F falls below 15 % RH.
- 75 F / 50 % RH air holds about 0.019 lb/lb of water but only about 0.004 lb/lb at 32 F, so it condenses on cold glass.
- Cabinet vibration limit equals the weakest installed device (5 g in a 5 g / 12 g pair).
- Example sensor spec: temperature +/-2 C, RH +/-5 %, up to 32 sensor packages cascaded.
Using it in design
- Plan temperature and humidity monitoring at least every fourth cabinet or every 3–9 m of aisle, at inlet heights including about 1.5 m, and identify unmonitored aisles.
- Warn on direct outside-air economisation in cold climates without humidification, since RH can fall below 20 %.
- Let rack records carry a vibration tolerance and compute the cabinet limit as the minimum across installed devices.
- Add sensor selection criteria for type, accuracy and cascade limit.
Who should read it
Engineers laying out white-space environmental monitoring and operators selecting a sensor system.
Related standards
- ASHRAE TC 9.9 Thermal Guidelines
- ISO 14644
Publication details
- Authors
- Legrand
- Publisher
- Legrand
- Year
- 2024
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Citation
Legrand (2024). Environmental Data Center Management & Monitoring. Legrand. https://www.legrand.com/datacenter/sites/g/files/ocwmcr716/files/2025-05/White%20Paper%20-%20Environmental%20Data%20Center%20Management%20%26%20Monitoring.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.