Technical guideFree to readYear not stated

LEO LVS/LVR Stainless Steel Vertical Multistage Pump, hosted by Famco

LEO

The LEO LVS/LVR vertical multistage pump catalogue gives limits of 0.7-240 m³/h flow, 33 bar operating pressure and -20 to +120°C liquid temperature, with model codes and an NPSH method.

On this page

Overview

LEO's LVS/LVR catalogue (a copy hosted by the distributor Famco) presents vertical multistage pumps for low-viscosity, non-flammable, non-explosive liquids free of solid particles or fibres. LVS has stainless steel wetted parts, while LVR has a cast iron base and pump cover. Applications listed include high-rise water supply, mains pressure boosting, boiler feed, cooling water circulation, water treatment, reverse osmosis, swimming pools and fire fighting.

Operating conditions are explicit: flow 0.7-240 m³/h, liquid temperature -20 to +120°C, liquid pH 4-10, maximum ambient temperature 40°C, maximum operating pressure 33 bar and altitude up to 1000 m. Liquids denser or more viscous than water call for a larger motor. When ambient exceeds 40°C or altitude exceeds 1000 m, motor output P2 falls; 88% above 3500 m and 78% at 70°C ambient are quoted.

The motor is IE2 (IE3 optional), totally enclosed fan-cooled, IP55, with standard voltage 1×220 V or 3×380 V at 50 Hz. The code structure is explained with LVS 45-10-2-B-K: rated flow (m³/h), number of stages, small-impeller stages, material (B for AISI316, blank for AISI304) and pipe connection (oval flange, clamp or threaded).

For suction the catalogue gives H = Pb×10.2 - NPSH - Hf - Hv - Hs and recommends the calculation for high liquid temperature, flow well above rated, drawing from depth or through long pipes. Maximum permitted inlet pressure is tabulated by model and stage count (from 4 up to 20 bar). The document does not present a duty point selected for a particular plant; flow and head pairs in the curve tables serve model comparison.

Key points

  1. Flow range is 0.7-240 m³/h; maximum operating pressure 33 bar.
  2. Liquid temperature is -20 to +120°C; pH 4-10; maximum ambient +40°C; altitude up to 1000 m.
  3. Above 3500 m altitude motor output P2 falls to 88%, and at 70°C ambient to 78%.
  4. Motor is IE2 (IE3 optional), IP55, 50 Hz 1×220 V or 3×380 V.
  5. LVS has stainless wetted parts; LVR has a cast iron base and cover.
  6. Model code carries rated flow, stage count, material and connection type (LVS 45-10-2-B-K).
  7. Maximum inlet pressure is tabulated by model and stage count, with values from 4 to 20 bar.
  8. NPSH method: H = Pb×10.2 - NPSH - Hf - Hv - Hs; safety margin at least 0.5 m.

Using it in design

  • For cooling water circulation, reflect the effect of liquid temperature and glycol content on density and viscosity in motor power.
  • If the pump room is above 40°C or 1000 m, upsize the motor according to the derating curve.
  • Perform the NPSH calculation at duty points above rated flow and avoid the far right of the curve.
  • Check that maximum inlet pressure plus closed-valve pressure stays below the operating pressure limit.
  • Write the correct variant (LVS/LVR, AISI304/316, connection type) into the specification by code.

Who should read it

Mechanical designers selecting cooling water and auxiliary system pumps and water treatment loop engineers.

Document contents

  1. Ambient temperature
  2. Application
  3. Operating conditions
  4. Motor
  5. Identification codes
  6. Minimum inlet pressure and NPSH
  7. Maximum inlet pressure
  8. How to read the curve charts
  9. Performance curves and tables

Publication details

Authors
LEO
Publisher
LEO
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

LEO LEO LVS/LVR Stainless Steel Vertical Multistage Pump, hosted by Famco. LEO. https://famcocorp.com/uploads/product/Pump/Brands/Leo/Catalogue/Leo-Pump-Stainlesssteel-Vertical-Multistage-LVR-LVS.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.