LG Oil-Free Magnetic Bearing VSD Centrifugal Chiller Catalogue (RCWFL, 2020)

Original title LG Oil Free Magnetic VSD Centrifugal Chiller 2020 catalogue

LG

LG's April 2020 catalogue: R-134a active-magnetic-bearing, variable-speed (VSD) oil-free centrifugal chillers; 200-700 usRT (703-2,461 kW) standard, with the line extending to 2,200 usRT.

On this page

Overview

The catalogue presents the RCWFL series of centrifugal chillers using LG's own active magnetic bearing. The series uses chlorine-free HFC-134a refrigerant, oil-free technology for easy maintenance and chilled water leaving temperature control within ±0.1 °C. Heat rejection is water-cooled; the model code encodes refrigerant, water-cooled construction, compressor and condenser/evaporator codes, and the line is planned from 100 to 2,200 usRT.

In the oil-free design, a contactless magnetic bearing and a direct impeller-to-shaft connection reduce lubrication losses by 2-3 percent versus a conventional oil-lubricated system. Inlet guide vanes (IGV) secure a stable operating range. Two-stage compression with a flash-type economizer reduces first-stage compressor energy at both full and part load. The variable speed drive (VSD) runs up to about 330 Hz, keeps THDv below 5 percent with a built-in DC reactor and raises part-load COP. Sound can be as low as 73 dBA.

The standard summary and specification table lists ten models across 200-700 usRT: RCWFLAL (200 usRT, 703 kW), 250 (879 kW), 280 (985 kW), 300 (1,055 kW), 400 (1,407 kW), 450 (1,582 kW), 500 (1,758 kW), 550 (1,934 kW), 600 (2,110 kW) and 700 usRT (2,461 kW). Supply is 380-460 V, 50 or 60 Hz. Safety devices include voltage low/high protection, excessive motor amps protection and bearing temperature sensors; the LGC-X30 controller has a 10.2 inch touch panel.

The catalogue is a product data sheet with no method or application guide. Its value to a data centre designer is seeing an oil-free, part-load-efficient, precise-outlet-temperature centrifugal chiller candidate and its capacity steps for large campus chilled water plants.

Key points

  1. The standard table has ten models of 200-700 usRT (703-2,461 kW); the line is planned for 100-2,200 usRT.
  2. Refrigerant is HFC-134a; chilled water leaving temperature control accuracy is ±0.1 °C.
  3. The magnetic bearing and direct drive cut lubrication losses by 2-3 percent versus a conventional oil-lubricated system.
  4. Two-stage compression and a flash-type economizer reduce first-stage energy at full and part load.
  5. The VSD runs up to about 330 Hz; THDv is below 5 percent.
  6. Sound can be as low as 73 dBA; supply is 380-460 V, 50/60 Hz.
  7. Example models: RCWFLAL 200 usRT (703 kW), RCWFLBN 450 usRT (1,582 kW), RCWFLCP 700 usRT (2,461 kW).
  8. The LGC-X30 controller uses a 10.2 inch touch panel and modular solutions are possible.

Using it in design

  • For a large campus chilled water plant, choose capacity steps of 200-700 usRT (703-2,461 kW) to suit the N+1 redundancy arrangement.
  • If the hall heat load is continuous at part load, verify the VSD and economizer part-load efficiency (COP/IPLV) from the manufacturer's full-load and part-load table.
  • Write the oil-free maintenance advantage and the magnetic bearing's need for uninterrupted power (backup power, ride-through) into the operating plan.
  • Include the VSD harmonic effect (THDv < 5 percent) in power quality calculations.
  • Match the chilled water temperature accuracy (±0.1 °C) requirement to the hall supply temperature tolerance.

Who should read it

Mechanical designers selecting centrifugal chillers for large data centre chilled water plants.

Document contents

  1. Nomenclature
  2. Line-up and introduction
  3. Features
  4. Safety devices
  5. Accessories and options
  6. Specification (200-700 usRT)
  7. Machine components
  8. Field wiring
  9. Piping and wiring
  10. Guide specification

Publication details

Authors
LG
Publisher
LG
Year
2020
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

LG (2020). LG Oil Free Magnetic VSD Centrifugal Chiller 2020 catalogue. LG. https://www.lg.com/content/dam/channel/wcms/vn/business/download/airsolution/LG%20Oil%20Less%20Magnetic%20VSD%20Centrifugal%20Chiller%20Catalog_20250214_190659_.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.