Liang Chi LCTR Engineering Tables

Original title LCTR Low Noise Crossflow Cooling Tower Catalogue

Liang Chi

Liang Chi's LCTR low-noise cross-flow rectangular cooling tower tables give nominal flow at 37/32°C water and 29°C wet bulb; model 1011B starts at 15.3 L/s.

On this page

Overview

Liang Chi's LCTR catalogue presents a series of low-noise, cross-flow rectangular cooling towers designed to international standards. Light structure and standardised components ease transport, lifting and site installation. High-tension V-belt reducers and low-noise axial fans give quiet operation and easy maintenance. The multi-cell combination structure suits large cooling demand and later expansion.

Material and construction details are explicit: casing, fan stack, basin and access door are FRP, fill is PVC, the support frame is light steel and all steel parts are hot-dip galvanised. The gravity distribution system gives low-pressure, slow water flow that prolongs contact time; vacuum-formed fill with a ripple surface spreads water evenly and limits scale. A venturi-type fan stack and low-resistance fill reduce fan motor power.

The tables are organised by model group (LCTR-1011B to 1052E plus SL and ESL variants). Each row gives nominal water flow (L/s), width, length and height, fan diameter and motor power (HP). For example the 1011B is 15.3 L/s with 3 HP and the 1018E 37 L/s with 15 HP. Separate tables give pipe connections (inlet, outlet, drain, overflow, auto and quick fill), dry and operating weight and the tower head needed for the pump.

All nominal flows rest on one condition: inlet water 37°C, outlet 32°C, wet bulb 29°C. Total pump head is the sum of condenser water pressure drop, pipe friction loss and tower head. The catalogue includes concrete foundation drawings (anchor bolt positions, ±2 mm level tolerance) valid for non-isolator foundations, with spring-mount isolators to be discussed with the manufacturer. Multi-cell models are not listed.

Key points

  1. Nominal flow condition: inlet 37°C, outlet 32°C, wet bulb 29°C.
  2. LCTR-1011B is 15.3 L/s and 3 HP; 1011E is 22.9 L/s and 10 HP; fan diameter 1500 mm.
  3. In the 1012 and 1016 group flow is 18.8-32 L/s with 1700 mm fans; the 1018 group is 25.8-37 L/s with 1800 mm fans.
  4. 1022ESL is 25.2 L/s and 7.5 HP; 1025ESL is 29.1 L/s and 10 HP; fan diameter 2000 mm; dry weight 2750 and 2950 kg, operating weight 4800 and 5120 kg.
  5. Tower head for the pump is 3.8-3.9 m.
  6. Materials: FRP casing and basin, PVC fill, hot-dip galvanised steel.
  7. Foundation level tolerance is ±2 mm; drawings are for non-isolator foundations.
  8. Multi-cell models are not in the tables and must be requested from the manufacturer.

Using it in design

  • Nominal flow is valid only for 37/32°C and 29°C wet bulb; if the design wet bulb or approach differs, ask the manufacturer for a correction.
  • Compute total pump head from condenser loss, pipe friction and the tower head in the table (about 3.8-3.9 m).
  • Take the concrete foundation drawings for non-isolator installation; ask the manufacturer if vibration isolation is needed.
  • Carry dry and operating weights into structural load calculations and pipe connection sizes (for example 5B, 6B, 8B) into the pipe routing.
  • If expansion is expected, plan cell count and layout clearance at the start.

Who should read it

Mechanical engineers designing cooling towers and condenser water circuits for data centres.

Document contents

  1. Characteristics and design of integrated system
  2. Structure and standard materials
  3. Recommended concrete foundations
  4. Dimensions and standard specifications (LCTR-1011B to 1052E)
  5. Pipe connections and weights
  6. SL and ESL series
  7. Notes and nominal conditions

Publication details

Authors
Liang Chi
Publisher
Liang Chi
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Liang Chi LCTR Low Noise Crossflow Cooling Tower Catalogue. Liang Chi. https://www.liangchi.com.tw/mobile/web-tw/tech/download.jsp?file=PS1745392027408.pdf&path=dm

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.