Mark AWS Dry Coolers: Delta and Star Connection Selection
Original title Mark AWS Dry Coolers technical brochure
Mark Climate Technology
Mark's AWS single-row-fan dry cooler catalogue lists standard and low-noise versions of 44-217 kW (800 mm fans) and 71-560 kW (910 mm fans), rated for delta and star fan motor connection.
On this page
Overview
Mark AWS is a series of dry coolers with a single row of fans. The compact, robust galvanised steel units can be mounted horizontally or vertically with the right kit and carry a RAL 9002 corrosion-resistant paint system; they use copper-tube aluminium-fin heat exchangers with steel threaded connections. The fans use IP54, class F, 3-phase asynchronous external-rotor motors that can be connected in star or delta, giving two speeds.
The catalogue has three table groups. Dimension tables for the 800 mm AWSN (standard) and AWSB (low noise) and the 910 mm AWSN series give surface area, internal volume, connection diameter, dimensions A-E and weight. The technical tables give, for 400 V and 50 Hz, capacity, mass flow, pressure drop, power consumption and sound level in separate columns for delta and star connection.
All values rest on one condition: ambient 25°C, water inlet 40°C and water outlet 35°C. Delta connection gives higher capacity with higher sound and power; star connection lowers capacity and sound. For example the AWSN-44E-217M gives 217 kW and 56 dB(A) in delta and 171 kW and 50 dB(A) in star. Capacity and sound must be read for the chosen connection type of the same model.
In the 910 mm series with four, five and six fans, capacity rises from 71 kW to 560 kW; the AWSN-56F-560L gives 560 kW in delta and 457 kW in star and weighs 2183 kg. The catalogue gives no correction factors for fluid, altitude or fin material; it holds only values at the stated water condition.
Key points
- The 800 mm AWSN series is 44-217 kW and the low-noise AWSB series 35-162 kW (delta connection).
- The 910 mm AWSN series is 71-560 kW (delta connection); models with 1 to 6 fans.
- Condition: ambient 25°C, water 40/35°C, 400 V, 50 Hz.
- AWSN-44E-217M: 217 kW, 38 m³/h, 34 kPa, 56 dB(A) in delta; 171 kW, 30 m³/h, 22 kPa, 50 dB(A) in star.
- AWSB-41C-035M: 35 kW and 39 dB(A) in delta; 30 kW and 34 dB(A) in star.
- Power consumption in the 800 mm AWSN runs 1.94 to 7.76 kW by fan count (delta) and 1.21 to 4.84 kW (star); 2.48-14.88 kW in the 910 mm series.
- Weight is 271 kg (AWSN-41C) to 2183 kg (AWSN-56F); connection diameter 2 to 4 inch.
- Fan motors are IP54, class F; star or delta connection gives two speeds.
Using it in design
- Read capacity and sound level for the chosen connection (delta or star); if the noise limit is binding, choose star connection or the AWSB series.
- When the design condition is not 25°C air and 40/35°C water, request a corrected selection from the manufacturer; the table offers no other condition.
- Add the pressure drop (9-114 kPa) to the total pump head of the dry cooler loop.
- Carry weight and dimension tables into roof structure and layout, and connection diameter into pipe sizing.
- Delta and star are two fixed speeds; if continuous speed control is needed, assess EC fans or a frequency drive separately.
Who should read it
Mechanical designers selecting dry coolers for data-centre heat rejection and engineers comparing connection options for noise-limited sites.
Document contents
- AWS dry coolers: single row of fans
- Dimensions: AWSN 800 mm
- Dimensions: AWSB 800 mm low noise
- Dimensions: AWSN 910 mm
- Technical information: AWSN 800 mm
- Technical information: AWSB 800 mm
- Technical information: AWSN 910 mm
Publication details
- Authors
- Mark Climate Technology
- Publisher
- Mark Climate Technology
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Mark Climate Technology Mark AWS Dry Coolers technical brochure. Mark Climate Technology. https://www.markclimate.com/app/uploads/sites/4/2022/09/Brochure-Mark-AWS-Dry-Cooler.pdf?x56617=
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.