Determining the Outdoor Air Intake Dry-Bulb Temperature Range for Economizer Applications in Data Centers

Buildings (MDPI AG) · Ahmin Jang, Minho Kim et al.

A 2025 Buildings study sweeps 10-18 °C outdoor-air thresholds in a Daejeon data-centre model using EnergyPlus and finds humidity-driven latent load raises total energy above 14 °C.

On this page

Overview

The study seeks the optimal outdoor air intake temperature range for a dry-bulb temperature-based air-side economiser. A parametric simulation uses EnergyPlus 24.1.0 and a previously validated small-to-medium data-centre model in Daejeon (ASHRAE climate zone 4A, South Korea). The maximum allowable outdoor air intake dry-bulb temperature is varied from 10 to 18 °C in 2 °C steps.

The results show outdoor air intake is limited in summer by high humidity and more viable in winter and the shoulder seasons. When the threshold exceeds 14 °C, the added latent heat load raises overall energy use. To widen the economiser's usable range, cooling system capacity is adjusted. The 14 °C threshold gives the best balance between energy efficiency and compliance with operating environmental criteria. The authors note field validation is still needed.

Key points

  1. Model: Daejeon, South Korea, ASHRAE climate zone 4A; EnergyPlus 24.1.0.
  2. Maximum outdoor-air intake dry-bulb limit swept from 10 to 18 °C in 2 °C steps.
  3. Above 14 °C the latent load of humid air raises total energy.
  4. A 14 °C threshold gives the best balance of energy and environmental compliance.
  5. Outdoor air intake is limited by humidity in summer and more viable in winter and shoulder seasons.

Using it in design

  • For dry-bulb economiser control, set the outdoor air threshold with a simulation that includes humidity effects, not temperature alone.
  • In similar climates take 14 °C as a starting threshold and verify with local climate data.
  • Consider adjusting cooling system capacity to widen the economiser operating range.
  • Verify simulation results by measurement in operation.

Who should read it

Mechanical and controls engineers designing air-side economiser control.

Related standards

  • ASHRAE climate zones

Publication details

Authors
Ahmin Jang; Minho Kim; Dongsu Kim; Suh-hyun Kwon; Sung Lok Do
Publisher
Buildings (MDPI AG)
Year
2025
Document language
English
Source type
Scientific
Access
Free to read
Licence
CC BY 4.0: share with attribution
Original licence note

Publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.

Citation

Ahmin Jang; Minho Kim; Dongsu Kim; Suh-hyun Kwon; Sung Lok Do (2025). Determining the Outdoor Air Intake Dry-Bulb Temperature Range for Economizer Applications in Data Centers. Buildings (MDPI AG). https://doi.org/10.3390/buildings15162913

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.