Determining the Outdoor Air Intake Dry-Bulb Temperature Range for Economizer Applications in Data Centers
Buildings (MDPI AG) · Ahmin Jang, Minho Kim et al.
A 2025 Buildings study sweeps 10-18 °C outdoor-air thresholds in a Daejeon data-centre model using EnergyPlus and finds humidity-driven latent load raises total energy above 14 °C.
On this page
Overview
The study seeks the optimal outdoor air intake temperature range for a dry-bulb temperature-based air-side economiser. A parametric simulation uses EnergyPlus 24.1.0 and a previously validated small-to-medium data-centre model in Daejeon (ASHRAE climate zone 4A, South Korea). The maximum allowable outdoor air intake dry-bulb temperature is varied from 10 to 18 °C in 2 °C steps.
The results show outdoor air intake is limited in summer by high humidity and more viable in winter and the shoulder seasons. When the threshold exceeds 14 °C, the added latent heat load raises overall energy use. To widen the economiser's usable range, cooling system capacity is adjusted. The 14 °C threshold gives the best balance between energy efficiency and compliance with operating environmental criteria. The authors note field validation is still needed.
Key points
- Model: Daejeon, South Korea, ASHRAE climate zone 4A; EnergyPlus 24.1.0.
- Maximum outdoor-air intake dry-bulb limit swept from 10 to 18 °C in 2 °C steps.
- Above 14 °C the latent load of humid air raises total energy.
- A 14 °C threshold gives the best balance of energy and environmental compliance.
- Outdoor air intake is limited by humidity in summer and more viable in winter and shoulder seasons.
Using it in design
- For dry-bulb economiser control, set the outdoor air threshold with a simulation that includes humidity effects, not temperature alone.
- In similar climates take 14 °C as a starting threshold and verify with local climate data.
- Consider adjusting cooling system capacity to widen the economiser operating range.
- Verify simulation results by measurement in operation.
Who should read it
Mechanical and controls engineers designing air-side economiser control.
Related standards
- ASHRAE climate zones
Publication details
- Authors
- Ahmin Jang; Minho Kim; Dongsu Kim; Suh-hyun Kwon; Sung Lok Do
- Publisher
- Buildings (MDPI AG)
- Year
- 2025
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Ahmin Jang; Minho Kim; Dongsu Kim; Suh-hyun Kwon; Sung Lok Do (2025). Determining the Outdoor Air Intake Dry-Bulb Temperature Range for Economizer Applications in Data Centers. Buildings (MDPI AG). https://doi.org/10.3390/buildings15162913
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.