Fire Suppression Simulation and Risk Assessment for a Lithium-Ion Battery Energy Storage Station
Fire (MDPI AG) · Junwei Shi, Ziyan Zhang et al.
A 2026 Fire (MDPI) study combining grey relational analysis, system dynamics and FDS for a 30 ft containerised lithium-ion BESS: without suppression, high temperature spreads along the module layer from 30 to 50 s, and water mist slows spread.
On this page
Overview
The study treats fire risk of lithium-ion BESS stations through interacting factors: cell thermal runaway, equipment failure, operating environment, personnel behaviour, management systems and information systems. Arguing that static risk methods cannot represent feedback among factors or link risk results to the physical-field evolution of a compartment fire, it develops a framework combining grey relational analysis (factor weights), system dynamics (time evolution of overall and subsystem risk) and FDS fire simulation.
The FDS simulation examines fire spread in a 30 ft containerised lithium-ion BESS compartment under no-suppression and water mist conditions. The central fire-source region and the battery module layer are identified as key areas of gas-phase high-temperature accumulation and potential spread. Without suppression the high-temperature region stays near the source at 3.0 s, expands along the module layer from 30.0 to 50.0 s, and approaches a relatively stable distribution after 70.0 s. Under the investigated conditions, water mist reduces near-source heating, weakens smoke layer development and slows spatial spread through evaporative cooling, reduced thermal radiation feedback and disturbance of the hot smoke layer.
Key points
- Method: integrated grey relational analysis, system dynamics and FDS framework.
- Risk factors: personnel, equipment, environment, management and information systems.
- Simulated setting: 30 ft containerised lithium-ion BESS compartment, with and without water mist.
- No suppression: high temperature near the source at 3.0 s, spreading along the module layer from 30.0 to 50.0 s, relatively stable after 70.0 s.
- Water mist reduces near-source heating, weakens smoke layer development and slows spread.
Using it in design
- When simulating spread in a battery container or room with FDS, treat the module layer and source region as key areas.
- Check the effect of water mist on near-source heating and the smoke layer for your own configuration by simulation.
- Include personnel, management and information-system factors in the risk assessment, not only equipment.
- Use the results as a method reference limited to the conditions stated in the study.
Who should read it
Engineers and researchers modelling fire risk and designing suppression for battery energy storage and data-centre battery systems.
Related standards
- NFPA 855
Publication details
- Authors
- Junwei Shi; Ziyan Zhang; Ziming Xu
- Publisher
- Fire (MDPI AG)
- Year
- 2026
- Document language
- English
- Source type
- Scientific
- Access
- Free to read
- Licence
- CC BY 4.0: share with attribution
Original licence note
Publisher-deposited Crossref licence metadata: https://creativecommons.org/licenses/by/4.0/ (OpenAlex: cc-by); landing page blocks automated fetch, abstract read via Crossref/OpenAlex. Round 1 ingestion retains bibliographic metadata only; no local full text is redistributed.
Citation
Junwei Shi; Ziyan Zhang; Ziming Xu (2026). Fire Suppression Simulation and Risk Assessment for a Lithium-Ion Battery Energy Storage Station. Fire (MDPI AG). https://doi.org/10.3390/fire9090395
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.