Technical guideFree to read2025

Critical Power Panel User Guide

Mersen

A user guide from Mersen for its Critical Power Panel (CPP) series of fused, selectively coordinated panelboards, covering application, specification, connection and maintenance.

On this page

Overview

The CPP is a UL 67 fused panelboard series designed for UPS systems, data centres, medium-voltage e-houses, emergency circuits (NEC 700.27) and legally required standby systems (NEC 701.18). It features few connection points, a steel back plate and fused main-switch options. The panel, main and branches can be applied up to 600 VAC or 125 VDC; branch circuit fuses are Class CC, up to 30 A.

Selective coordination is the main subject of the guide. According to the guide, if a 2:1 ratio is maintained with upstream Mersen Amp-Trap 2000 fuses the system will coordinate, and no complex short-circuit study is needed. Under the NEC, selective coordination is mandatory for elevator circuits (620.62), emergency systems (700.27) and legally required standby systems (701.18). The guide also states that a surge protective device has been required in emergency system panelboards since 2014 (NEC 700.8), and the optional Surge-Trap SPD in the CPP meets this.

The specification table gives system ampacity of 250 A or 400 A, branch circuit ampacity of 30 A CC, voltage of 600 VAC and 125 VDC, and a delta or wye, 1- or 3-phase, 2-, 3- or 4-wire system type. Withstand (SCCR) is 200 kA with upstream protection and 25 kA standalone. Neutral is 200% on the 100, 200 and 250 A models and 125% on the 400 A model. The enclosure is UL 50 Type 1, protection IP20, with a double-column branch arrangement of 24, 36 or 42 circuits.

The operations and maintenance section states that main incoming terminals are rated Cu/Al with a maximum torque of 275 in-lb, and branch connections are limited to 30 A CC. On unused branch positions the insulating louvers must be raised before energisation; with the louvers up they insulate the bus fingers. The neutral bar is rated at 200% of the panel ampacity. The guide is product-oriented and does not replace a short-circuit study in real designs.

Key points

  1. System ampacity 250 A or 400 A; branch circuits up to 30 A Class CC; 600 VAC and 125 VDC.
  2. SCCR: 200 kA with upstream protection, 25 kA for the standalone panel.
  3. Selective coordination is achieved by keeping a 2:1 ratio with upstream Amp-Trap 2000 fuses.
  4. Selective coordination is mandatory in the NEC for elevators (620.62), emergency systems (700.27) and legally required standby (701.18).
  5. NEC 700.8 (2014) requires an SPD in emergency system panelboards; the CPP meets it with the optional Surge-Trap.
  6. Neutral: 200% on the 100, 200, 250 A models; 125% on the 400 A model.
  7. Enclosure UL 50 Type 1, IP20, UL 67 and CSA 22.2; double-column branch layout, 24, 36 or 42 circuits.
  8. On unused branch positions the insulating louvers must be raised before energisation.
  9. Main incoming terminals Cu/Al, maximum torque 275 in-lb.

Using it in design

  • Compare the panel SCCR with the fault current at the point of use: the 200 kA value applies only with upstream protection, the standalone panel is 25 kA.
  • Document selective coordination by upstream fuse type and the 2:1 ratio; for critical circuits still verify with a system short-circuit study.
  • For NEC emergency and standby circuits, put the surge protective device option into the specification.
  • For loads with high neutral current, check the neutral ratio (200% or 125%) by model.
  • Add to the commissioning checklist that insulating louvers on unused branch positions are raised and terminal torques are applied.

Who should read it

Electrical engineers selecting fused panelboards for UPS output and critical load distribution, panel builders and commissioning teams.

Document contents

  1. Product introduction
  2. Selective coordination with the Critical Power Panel
  3. Surge protection and ordering details
  4. Specifications
  5. Operations and maintenance
  6. Branch circuit protection
  7. Accessories
  8. Dimensions and enclosures

Publication details

Authors
Mersen
Publisher
Mersen
Year
2025
Document number
INS-CRITICAL-POWER-001
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public manufacturer source inspected. No document-specific redistribution permission established; metadata and original brief summaries only. Local downloads are research evidence, not a redistribution package.

Citation

Mersen (2025). Critical Power Panel User Guide. Mersen. INS-CRITICAL-POWER-001. https://www.mersen.com/sites/default/files/medias/files/2026-02/INS-Mersen-Critical-Power-Panel-User-Guide_0.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.