Battery Energy Storage Overcurrent Protection Guide: EES Application Guide #1

Mersen

Mersen's application guide to fuse selection in energy storage systems (EES) from module to container, covering current correction factors, fault-current protection, coordination with the contactor and a 5 MWh worked example.

On this page

Overview

The guide argues that EES systems face voltages up to 1500 VDC and fault currents of several hundred kA, that protection architectures are not standardised, and that fuses remain the safest solution once everything else has failed. It defines the module, rack, section and container hierarchy: racks are modules in series, sections are racks in parallel and containers are sections in parallel. Current-limiting fuses protect not only against faults but also protect other devices such as contactors and switches.

The rated current section explains that a fuse is type-tested under laboratory conditions and must be corrected in the field for ambient temperature (A1), air cooling (Bv), terminal connection size (C1), altitude (CALT) and current cycling (A'2). Ifuse must be at least IRMS / (A1 x Bv x C1 x A'2 x CALT), and the fuse is sized at a minimum of 1.25 x IRMS. 40 C is given as the baseline ambient for rack fuses and 30 C for section fuses.

The fault section covers four fault locations: in the PCS, between the PCS and section fuse, between section and rack fuse, and inside a rack. Interrupting rating (IR) and minimum breaking capacity (MBC) are assessed together: a rack typically gives 1-12 kA of fault current and combined systems reach 250 kA or more, while EES fuse MBC can be 3-15 times the rated current (up to 16500 A for an 1100 A fuse). A DC contactor and fuse work in series, with MBC at or below the contactor's maximum current.

The standards section covers NEC Article 706.31 (overcurrent protection at least 125 percent, current limiting, DC rated, adjacent to the ESS for each DC output) and IEC 60269-7 (aBat partial-range and gBat full-range DC breaking; breaking capacity above 30 kA; gBat clears 2 times rated current). The worked example uses a 5 MWh system (1216 VDC maximum, 8 racks, 3 sections, 50 A continuous per rack) and checks rated current and peak let-through current at the PCS interface separately.

Key points

  1. Hierarchy: module, rack (series modules), section (parallel racks), container (parallel sections).
  2. Ifuse >= IRMS / (A1 x Bv x C1 x A'2 x CALT); fuse selected at a minimum of 1.25 x IRMS.
  3. Ambient baselines: rack fuse surroundings 30-45 C (40 C), section fuse surroundings 25-35 C (30 C); range -5 to 70 C.
  4. Conditions: IR > available fault current, MBC < smallest current the fuse must open, peak let-through < component DC short-circuit withstand.
  5. Fault current per rack is typically 1-12 kA; systems can reach 250 kA or more.
  6. MBC is 3-15 times rated current for EES fuses; up to 16500 A for an 1100 A fuse.
  7. A low MBC of 2-3 In on the rack fuse helps contactor coordination; fuse MBC must not exceed the contactor's maximum current.
  8. IEC 60269-7: aBat and gBat categories; breaking capacity above 30 kA; gBat clears 2 times rated current.
  9. NEC 706.31: at least 125 percent protection, current limiting, DC rated.
  10. Example: 5 MWh, 1216 VDC maximum, 7806 A prospective fault per rack, L/R 0.68 ms, 8 racks x 3 sections, PCS withstand 100 kA.

Using it in design

  • When calculating fuse current, apply the ambient, airflow, terminal size, altitude and cycling factors one by one.
  • Check IR and MBC together: if the battery's limited fault current falls below the MBC, the fuse may not open.
  • Verify DC contactor and fuse coordination on the time-current curve.
  • At the PCS interface compare not only rated current but also peak let-through current with the withstand of components.
  • Write NEC 706 and IEC 60269-7 requirements into the specification as the project's rules require; the guide is simplified, so work with the manufacturer for a detailed study.

Who should read it

Electrical engineers designing battery energy storage, UPS battery and DC distribution protection.

Document contents

  1. Introduction to energy storage and fuses
  2. Adjusting the fuse rated current for real-world working conditions
  3. Protection from fault currents
  4. International standards
  5. Case study

Publication details

Authors
Mersen
Publisher
Mersen
Year
2022
Document number
10633
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Official public manufacturer source inspected. No document-specific redistribution permission established; metadata and original brief summaries only. Local downloads are research evidence, not a redistribution package.

Citation

Mersen (2022). Battery Energy Storage Overcurrent Protection Guide: EES Application Guide #1. Mersen. 10633. https://mersen.com/sites/default/files/medias/PIM/files/BR-Guide-EES-Mersen-EN.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.