Mesan MXL crossflow cooling towers
Original title MXL Cross Flow Cooling Tower: engineering data
MESAN
MESAN MXL is a crossflow open cooling tower series of 19 box sizes and 140 models, with single-cell water flow of 117-1,011 m³/h, designed to exceed ASHRAE 90.1 efficiency levels.
On this page
Overview
This document is the engineering data sheet for MESAN's MXL crossflow open cooling tower series, designed for urban installations. The line has 19 box sizes and 140 models, and each cell handles between 117 and 1,011 m³/h (516-4,461 gpm) of water. The sheet is bilingual (Chinese and English) and consists of a model designation key, a structure diagram, optional equipment and model-by-model tables.
The model code encodes box size, fan motor power, structural material and number of cells. The casing is high-density fibreglass, with galvanised steel or 304/316 stainless steel as alternatives. The fan is axial with hollow aluminium blades. Options include a velocity recovery stack, a super-low-noise fan, drift eliminators, inlet louvers, a permanent-magnet direct-drive motor and a variable-flow water distribution system.
All water flows in the tables refer to a design condition of 37 °C entering water, 32 °C leaving water and 28 °C wet bulb. For a given box size a larger fan motor gives more flow; for box 01A, 3 kW delivers 121 m³/h and 7.5 kW delivers 162 m³/h. The notes also state that rated capacity assumes a well-ventilated site.
The sheet is a manufacturer catalogue and does not include data-centre-specific temperature levels, water consumption or energy calculations. It states that drift eliminators can cut drift loss below 0.001% of the recirculating flow; this applies to the optional equipment and the sheet gives no test method.
Key points
- 19 box sizes and 140 models; single-cell water flow 117-1,011 m³/h (516-4,461 gpm).
- All flows are given at 37/32 °C water and 28 °C wet bulb.
- Design efficiency is stated to exceed ASHRAE 90.1 and to suit LEED applications.
- Casing is high-density fibreglass, with galvanised steel and 304/316 stainless options.
- Optional high-efficiency drift eliminators reduce drift to below 0.001% of recirculating flow.
- Options include permanent-magnet direct-drive motors, super-low-noise fans with attenuators, variable-flow distribution and filtration for legionella control.
- Shipping modes are container, trailer and multi-module knocked-down; factory pre-assembled modules reduce installation cost.
- For box 01A, motor power from 3 kW to 7.5 kW raises flow from 121 to 162 m³/h.
Using it in design
- Compare the project wet-bulb and water temperatures with the sheet's 37/32/28 °C condition; request corrected capacity from the manufacturer where they differ.
- Check the well-ventilated site assumption against the actual layout and derate capacity if recirculation of discharge air is a risk.
- For sound-restricted urban sites, decide whether the super-low-noise fan and attenuator are needed against the specified sound pressure limit.
- Plan redundancy through cell count (for example two-cell sets) and align the shipping mode with site access and crane capacity.
- Include drift eliminators and filtration options in the water-treatment and legionella management plan.
Who should read it
Mechanical designers and procurement engineers selecting open cooling towers for data-centre condenser water systems.
Document contents
- Overview
- Model designation
- Design features
- Tower structure
- Optional requirements
- Engineering data tables
Publication details
- Authors
- MESAN
- Publisher
- MESAN
- Year
- 2024
- Document language
- Multilingual
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
MESAN (2024). MXL Cross Flow Cooling Tower: engineering data. MESAN. https://www.mesanct.com/qfy-content/uploads/2024/08/MESAN-MXL-CNEN.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
