Development of High-Performance Centrifugal Chillers with Global-Warming-Potential of 1, Focusing on Energy-Saving and Miniaturization

Mitsubishi Heavy Industries · Noriyuki Matsukura, Naoya Miyoshi et al.

An MHI Technical Review paper (March 2025) raises the COP of the ETI-Z73 centrifugal chiller using HFO-1233zd(E) from 5.52 to 5.99, up to 12% better than the conventional ETI-Z70.

On this page

Overview

This technical review from Mitsubishi Heavy Industries Thermal Systems introduces new high-performance models of the ETI-Z centrifugal chiller series using HFO-1233zd(E), a refrigerant with GWP of 1. ETI-Z is the most widely used centrifugal chiller in Japan and, as a low-pressure refrigerant unit, falls outside the High Pressure Gas Safety Act and needs no qualified operator. Growth in data centres and semiconductor demand is cited as a reason for the need for higher efficiency.

A low-pressure refrigerant has a large gas volume, which normally enlarges the chiller. Two methods are used. The first is refrigerant flow path improvement: the shape and arrangement of cushion components are redone for uniform distribution into the evaporator, and pressure loss on the evaporator-to-compressor path is cut by about 78%. The second is miniaturisation based on an operating database: space is created above the evaporator and internal components are arranged to prevent droplets reaching the compressor.

The comparison table gives ETI-Z70 and ETI-Z73 at maximum capacity. Capacity rises from 700 USRt (2,461 kW) to 730 USRt (2,567 kW). Under JIS conditions (chilled water 12/7 °C, cooling water 32/37 °C), two-compressor COP rises from 5.52 to 5.99 and IPLV from 8.410 to 8.663. Power per compressor falls from 222.6 kW to 214.2 kW. Size grows from 4.3 x 2.0 x 2.1 m to 4.9 x 2.0 x 2.1 m. The highest COP in the series is 6.52.

The paper reports that the developed models' footprint shrinks to about 60% of competing R1233zd(E) models. The capacity range is 150-370 USRt for single-compressor and 370-730 USRt for two-compressor models (1 USRt = 3.516 kW). The table describes one specific ETI-Z73 selection and should not be generalised to the nominal performance of the whole ETI-Z family.

Key points

  1. Refrigerant HFO-1233zd(E): zero ODP, GWP of 1 (carbon-dioxide equivalent).
  2. ETI-Z70 700 USRt (2,461 kW) and ETI-Z73 730 USRt (2,567 kW) maximum capacity.
  3. COP (JIS, 2 compressors): 5.52 to 5.99; IPLV: 8.410 to 8.663.
  4. Power per compressor: 222.6 kW to 214.2 kW.
  5. Chilled water 12/7 °C with flow 422.3 to 440.4 m³/h; cooling water 32/37 °C with flow 502.3 to 517.8 m³/h.
  6. COP improvement over the conventional model is up to 12%; the highest COP in the series is 6.52.
  7. Pressure loss in the refrigerant flow path is cut by about 78%.
  8. Footprint shrinks to about 60% of competing R1233zd(E) models.
  9. Capacity range: single compressor 150-370 USRt, two compressors 370-730 USRt.

Using it in design

  • When selecting centrifugal chillers, compare COP not at the JIS condition (12/7 °C, 32/37 °C) but at the project's real chilled water and condenser water temperatures; IPLV is more representative of part load.
  • Because of the low-pressure refrigerant, check the compact footprint (4.9 x 2.0 x 2.1 m) and weight distribution in the plant room layout.
  • Carry the choice of a GWP 1 refrigerant into regulatory and sustainability requirements.
  • Use the table only as a maximum-capacity ETI-Z73 selection; ask the manufacturer for performance data at other capacities.
  • Compare the part-load profile with IPLV weights and the data-centre load curve.

Who should read it

Mechanical engineers designing large chiller plants and decision makers evaluating low-GWP centrifugal chillers.

Document contents

  1. Introduction
  2. High performance and miniaturization design optimized for low-GWP refrigerant specifications
  3. Comparison with conventional models and competitors' models in the market
  4. Conclusion

Publication details

Authors
Noriyuki Matsukura; Naoya Miyoshi; Yusuke Ira; Yoshiki Oya; Tomonori Nitta
Publisher
Mitsubishi Heavy Industries
Year
2025
Document number
Technical Review Vol. 62 No. 1
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Noriyuki Matsukura; Naoya Miyoshi; Yusuke Ira; Yoshiki Oya; Tomonori Nitta (2025). Development of High-Performance Centrifugal Chillers with Global-Warming-Potential of 1, Focusing on Energy-Saving and Miniaturization. Mitsubishi Heavy Industries. Technical Review Vol. 62 No. 1. https://mhi.com/technology/review/sites/g/files/jwhtju2326/files/tr/pdf/e621/e621140.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.