Mitsubishi Heavy Industries ETI-Z Low-GWP Variable Speed Centrifugal Chiller Technical Catalogue

Original title MHI Low GWP Refrigerant VSD ETI-Z, printed pp.5–6

Mitsubishi Heavy Industries

MHI's ETI-Z series is a variable speed centrifugal chiller using HFO-1233zd(E) with a GWP of 1, spanning 527 kW (150 RT) to 2461 kW (700 RT) with COP up to 6.6.

On this page

Overview

The Mitsubishi Heavy Industries catalogue presents the ETI-Z, which it calls Japan's first variable speed drive centrifugal chiller using a new low-GWP refrigerant. The series uses HFO-1233zd(E) with zero ozone depletion potential and a global warming potential (GWP) of 1; the earlier ETI series used HFC-134a. A high-speed direct motor-drive compressor, a built-in inverter panel and an advanced microcomputer control panel are highlighted. Capacity spans 150 RT to 700 RT.

The catalogue gives a cost and carbon comparison: the ETI-Z50 cuts annual electricity cost and annual CO2 emissions by about 64% against a constant-speed model from 20 years ago (building air conditioning use, annual electricity cost from 9.75 to 3.53 million yen). A table compares the ETI-Z, GART-ZE, GART-ZE HR and GART-ZEI series by capacity (150-5000 RT), chilled water leaving lower limit (3-5°C), cooling water entering lower limit (12°C), control range and refrigerant.

The standard specification tables give capacity (RT and kW), motor output, inverter input, auxiliary power and COP per model. The ETI-Z15 is 527 kW with motor output 71-76 kW and COP 6.19-6.58; the ETI-Z70 is 2461 kW with a 408 kW motor. COP is given with and without auxiliary power (for example 6.58 and 6.55). Weight tables give shipping weight (4.3 to 10.4 tons) and operating weight (5.1 to 12.5 tons) by size group.

All specifications rest on AHRI Standard 550/590 (I-P) temperature and fouling conditions. Installation notes call for avoiding rain, wind, direct sun, salt and steam, a site free of oil mist, dust and corrosive gas, flexible joints in piping, and state that foundation construction and anchor bolts are in the purchaser's scope. Standard control range is 100-10% load; with the continuous operation option it can run down to 0%.

Key points

  1. ETI-Z capacity is 527 kW (150 RT) to 2461 kW (700 RT); the whole catalogue spans 150-6000 RT.
  2. Refrigerant is HFO-1233zd(E): ODP 0, GWP 1.
  3. COP is up to 6.58 (ETI-Z15, without auxiliary power); about 6.2-6.4 in the ETI-Z50 class.
  4. The ETI-Z50 cuts annual electricity cost and CO2 by about 64% against the earlier constant-speed model.
  5. Load control range is 100-10% as standard, 100-0% with the option.
  6. Chilled water leaving lower limit is 4°C for ETI-Z and 3°C for GART-ZE; cooling water entering lower limit is 12°C.
  7. Shipping weight is 4.3-10.4 tons and operating weight 5.1-12.5 tons (by size group).
  8. Specifications are on AHRI 550/590 conditions.

Using it in design

  • Check the 4°C chilled water leaving limit and the 12°C cooling water entering limit against free-cooling and winter operation scenarios.
  • Separate COP without and with auxiliary power; take the one including auxiliary power for energy calculations.
  • Use IPLV and the COP curve for part-load efficiency, and confirm data-centre load stays in the 100-10% range.
  • For projects needing low-GWP refrigerant, compare the HFO-1233zd(E) and HFO-1234ze(E) options.
  • Carry the operating weight (up to 12.5 tons) into floor loading and anchor design, and leave enough entry and service clearance.

Who should read it

Mechanical designers selecting centrifugal chillers for large data-centre chilled water plants and decision makers weighing low-GWP refrigerants.

Document contents

  1. Low GWP refrigerant
  2. Environment, high performance and compact
  3. Cost and CO2 saving
  4. Product line comparison
  5. Features
  6. Standard specification tables
  7. Dimensions and weight
  8. Installation notes
  9. Controls and load functions

Publication details

Authors
Mitsubishi Heavy Industries
Publisher
Mitsubishi Heavy Industries
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Mitsubishi Heavy Industries MHI Low GWP Refrigerant VSD ETI-Z, printed pp.5–6. Mitsubishi Heavy Industries. https://www.mhi-mth.co.jp/catalogue/index.php?mode=download&contentsNumber=648

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.