Midea Fan Wall: Datacenter Solutions Product Page (250-520 kW)

Original title Fan Wall: Data Center Solutions

Midea

Midea Building Tech fan wall: 250-520 kW (853-1,774 MBH), 62,500-130,000 m³/h, 460 V/60 Hz; the maker claims a 10% lower initial investment from raised-floor-free design and free cooling extended from 10% to 28%.

On this page

Overview

The product page introduces Midea's factory-integrated fan wall for data centres. The unit uses high-efficiency EC fans and advanced heat exchanger technology; because key components and optional functions are integrated at the factory, quick on-site installation is intended. Specifications: 250-520 kW (853-1,774 MBH) cooling capacity, 36,786-76,516 CFM (62,500-130,000 m³/h) airflow and 460 V/60 Hz supply.

The maker states its benefits numerically: raised-floor-free design reduces initial data centre investment by 10%; a medium to high temperature fan wall extends free cooling duration from 10% to 28%; chilled water unit efficiency improves by 15%; modular design cuts installation time by 30%; and 15-20 kW per cabinet is supported. The page does not give the calculation method or reference condition for these figures.

Other features: in the dual-module design each module can be serviced independently, up to 32 fan wall groups can be networked for group control sharing real-time sensor data, water flow is regulated by a pressure independent control (PIC) valve, and an optional ATS with integrated capacitor supports uninterrupted power. The page links to downloadable documents such as the catalogue, IOM manual and product image; rating conditions are not stated on the page.

Key points

  1. Cooling capacity 250-520 kW (853-1,774 MBH).
  2. Airflow 62,500-130,000 m³/h (36,786-76,516 CFM); supply 460 V/60 Hz.
  3. Maker claim: raised-floor-free design cuts initial investment by 10%.
  4. Maker claim: a medium to high temperature fan wall extends free cooling duration from 10% to 28%.
  5. Maker claim: chilled water unit efficiency up 15%; modular design cuts installation time by 30%.
  6. Supports a high-density solution of 15-20 kW per cabinet.
  7. Dual-module design with one module serviceable independently; networked group control of up to 32 groups.
  8. PIC valve for water flow control; optional ATS with integrated capacitor.

Using it in design

  • Do not base an early investment decision on the page's percentages (10%, 28%, 15%, 30%) without recalculating with your own climate data and water temperatures.
  • Read capacity and airflow together with the rating condition in the catalogue and IOM; this page gives no water or air temperatures.
  • For a medium to high temperature chilled water design, derive free cooling hours from local climate data.
  • Check the 460 V/60 Hz supply against the project's voltage system.
  • For N+1, state group control of up to 32 groups and the dual-module service feature in the redundancy scheme.

Who should read it

Mechanical designers comparing fan wall CRAH solutions and investment decision makers.

Document contents

  1. Product summary
  2. Features
  3. Product specifications
  4. Product literature

Publication details

Authors
Midea
Publisher
Midea
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Midea Fan Wall: Data Center Solutions. Midea. https://hvac.midea.com/products/datacentersolutions/fanwall/833994379755589.shtml

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.