SNMP Application Note (Mikrodev)
Original title SNMP Uygulama Notu
Mikrodev
A Mikrodev application note showing how its devices act as SNMP agents, with UDP 161 listening, the OID format (.1.3.6.1.2.1.block type.block number) and a threshold-driven Trap block, demonstrated with a MIB Browser.
On this page
Overview
The note describes SNMP (Simple Network Management Protocol) as a technology designed to supervise units as networks grow. The components are the agent application (runs on the device, holds information and passes it to the manager), the manager application and the network management system (NMS). Mikrodev products run as SNMP agents. MIBs are introduced as hierarchical collections of information.
The SNMP Agent block defines the device as an agent. The listening port is UDP 161 by default; read and write community values work like a user name and password and must be entered identically on the manager. The SNMP Trap block sends data from the device to the manager on certain changes. There are four alarm conditions: greater than threshold, smaller than threshold, level change by the threshold and percent change. Manager IP address, port and threshold are set in the block settings.
OID calculation requires the query in the form .1.3.6.1.2.1.[block type].[block number]. Block types: 1 Bool, 2 Word, 3 Float, 4 Long. The block number in Mikrodiagram is converted; for example 3004 becomes 30*100+4 = 30.4. In the example application, a binary register with block 2 is queried with .1.3.6.1.2.1.1.0.2 and a word register with block 3000 with .1.3.6.1.2.1.2.30.0. A MIB Browser can serve as the manager.
The document is a product-specific configuration note; it does not address SNMP versions, security (SNMPv3) or standard MIB trees. It should be noted that read and write community values are used in clear text. Since SNMP is widely used to connect power and cooling equipment to monitoring systems in data centres, it is a practical example of agent, trap and OID logic.
Key points
- SNMP components: agent application, manager application and network management system (NMS); Mikrodev products work as agents.
- The agent listens on UDP port 161 by default.
- Read and write community values work like a user name and password and must match on the manager.
- Trap alarm conditions: Greater Than, Smaller Than, Level Change and Percent Change.
- OID format: .1.3.6.1.2.1.[block type].[block number]; types are 1 Bool, 2 Word, 3 Float, 4 Long.
- Block numbers are converted: 3004 becomes 30*100+4 = 30.4.
- Example: the OID for a word register with block 3000 is .1.3.6.1.2.1.2.30.0.
- Traps let the agent send data without a manager query; they are tested with a MIB Browser.
Using it in design
- Document SNMP agent and trap configuration (UDP 161, community, threshold condition) per device in monitoring system design for power and cooling equipment.
- Restrict clear-text community values to an isolated management VLAN; prefer devices supporting SNMPv3 where security requirements are high.
- Decide whether alarm thresholds (greater, smaller, change) are defined on the device or in the NMS together with the alarm management strategy.
- Verify the OID mapping in commissioning with a MIB Browser or the NMS.
Who should read it
BMS, DCIM and monitoring system engineers and technicians integrating Mikrodev devices with SNMP.
Document contents
- SNMP Protocol (general information)
- Block Definitions (SNMP Agent, SNMP Trap)
- OID Calculation and Example Application
- SNMP Trap Application
Publication details
- Authors
- Mikrodev
- Publisher
- Mikrodev
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Official public manufacturer documentation inspected. No redistribution permission established. Metadata and original brief summaries only; local downloads are research evidence, not a redistribution package.
Citation
Mikrodev SNMP Uygulama Notu. Mikrodev. https://docs.mikrodev.com/tr/docs/SNMP-Application-Notes/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.