Mitsubishi Electric MEWALL Data Centre Fan Wall
Original title MEWALL Data Centre Fan Wall
Mitsubishi Electric
The Mitsubishi Electric MEWALL fan wall gives 430 and 446 kW gross total capacity in two sizes for hyperscale data centres, with EER of 17.8 and 19.2 and no raised floor needed.
On this page
Overview
MEWALL is a horizontal-airflow fan wall for hyperscale and large colocation data centres. Horizontal flow allows taller heat exchangers and elevated water temperatures, eases separation of the white space from the technical corridor and removes the need for a raised floor. The brochure offers two sizes in the 350-400 kW class, EC fans, front-accessible low-pressure-drop filters and a side-filter version.
The table shows two models (MEWALL 402, frame 3B2; MEWALL 462, frame 3H2). Condition: return air 37 °C, 25% RH, water inlet 20 °C, water delta T 12 K, no glycol. Total capacity is 430 and 446 kW with SHR of 1. EER is 17.8 and 19.2 kW/kW for the indoor unit only. Airflow is 129,000 and 134,000 m³/h, external static pressure 50 Pa, fan power 24.2 and 23.2 kW, water flow 8.61 and 8.93 L/s and total pressure drop 134 and 118 kPa (heat exchanger and hydronic valve included).
There are eight EC radial fans. Sound power is 88 dB(A) and average sound pressure at 1 m is 68 dB(A) (ISO 3744, non-binding value). Electrical supply is 400 V/3+N/50 Hz with maximum current 44.8 A. Dimensions are a 3,600 x 1,600 mm footprint and 3,500 or 4,000 mm height; weight is 2,460 and 2,545 kg. The table defines capacity as gross total, and dimensions exclude optional accessories. Options include hydronic control valves, harmonic filters, fast restarts and a touchscreen.
Key points
- Two models: MEWALL 402 (frame 3B2) and 462 (frame 3H2).
- Gross total capacity 430 and 446 kW; SHR 1.
- Condition: return air 37 °C, 25% RH, water inlet 20 °C, water delta T 12 K, no glycol.
- EER is 17.8 and 19.2 kW/kW for the indoor unit only.
- Airflow 129,000 and 134,000 m³/h; external static pressure 50 Pa; fan power 24.2 and 23.2 kW.
- Water flow 8.61 and 8.93 L/s; total pressure drop 134 and 118 kPa.
- Sound power 88 dB(A); sound pressure 68 dB(A) at 1 m.
- 3,600 x 1,600 x 3,500 (402) or 4,000 mm (462); weight 2,460 and 2,545 kg.
- 400 V/3+N/50 Hz, maximum current 44.8 A.
Using it in design
- Read capacity as gross total; confirm net capacity with the manufacturer including fan heat and accessory losses.
- Add the 134 and 118 kPa water-side pressure drop (heat exchanger and valve included) to pump selection.
- Compare the 37 °C return air and 20 °C water condition with the project's real conditions.
- In white space design without raised floor, plan the fan wall's technical corridor layout and service clearances.
- Remember EER covers the indoor unit only; add pump and chiller energy separately.
Who should read it
Mechanical engineers designing cooling infrastructure for hyperscale and colocation data centres.
Document contents
- Key features and benefits
- Performance and technical data
- Dimensions and clearances
Publication details
- Authors
- Mitsubishi Electric
- Publisher
- Mitsubishi Electric
- Year
- 2025
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Mitsubishi Electric (2025). MEWALL Data Centre Fan Wall. Mitsubishi Electric. https://library.mitsubishielectric.co.uk/pdf/download_full/4897
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.