Modine MFS/MFV Air Cooled Fluid Coolers (500 and 800 mm series, 2019)

Original title Air Cooled Fluid Coolers

Modine

Modine's 2019 air cooled fluid cooler catalogue: 500 and 800 mm fan series, single speed or variable speed EC fans, 8-14 FPI fin spacing, 320 psig design pressure and nominal application conditions.

On this page

Overview

The catalogue presents Modine's MFS (standard single speed) and MFV (variable speed EC) air cooled fluid coolers. There are two series with 500 mm (19.7 inch) and 800 mm (31.5 inch) fans. The model code encodes number of fans (wide and long), fin spacing (8, 10, 12 or 14 FPI), circuiting, connections, motor voltage (230/3/60, 230/1/60, 575/3/60) and control voltage.

Standard features: direct drive external rotor fan motors, a large weatherproof electrical enclosure with door-interlocked main disconnect (standard panel 5 kA SCCR), venturi fan panels, fully baffled fan cells (preventing wind milling on 800 mm models), pre-painted galvanised steel cabinet and a coil of smooth wall copper tube with sinusoidal aluminium fins. All Modine fluid coolers carry a 320 psig design pressure and connections are steel pipe (MPT). They can be mounted for vertical or horizontal airflow.

Options include ambient or pressure fan cycling, variable speed EC fans and advanced control panels. Nominal performance data is a general guideline and Modine Select software is recommended for actual design conditions. Nominal application parameters: condenser (95 °F ambient, 110 °F fluid, 5-15 °F TD), economizer (40 °F ambient, 55 °F fluid) and industrial (95 °F ambient, 140 °F fluid, 20-40 °F TD), all with water at sea level and 10 FPI.

The document also holds 500 mm and 800 mm series specification tables, control panels and wiring diagrams. The catalogue is for general fluid coolers with no data-centre-specific selection rules; glycol performance correction is covered in a separate section on factors influencing performance.

Key points

  1. Two series: 500 mm (19.7 inch) and 800 mm (31.5 inch) fans; MFS standard single speed, MFV variable speed EC.
  2. Fin spacing is selectable at 8, 10, 12 or 14 FPI.
  3. Design pressure is 320 psig; connections are steel pipe (MPT).
  4. Standard control panels are 5 kA SCCR; the main disconnect is door-interlocked.
  5. Motor voltage options are 230/3/60, 230/1/60 and 575/3/60; single speed three-phase motors can be changed in the field between 208-230 V and 460 V.
  6. Nominal conditions: condenser 95 °F ambient and 110 °F fluid; economizer 40 °F and 55 °F; industrial 95 °F and 140 °F.
  7. Nominal TD ranges: condenser and economizer 5-15 °F, industrial 20-40 °F.
  8. Nominal data is not enough for real conditions; Modine Select selection software is recommended.

Using it in design

  • When selecting a dry cooler, compare design ambient, fluid temperature and TD with the nominal conditions; use manufacturer software where they deviate.
  • For circuits that work as economizers at low ambient, set freeze protection (glycol) and fan staging.
  • If noise and energy targets exist, evaluate the EC variable speed MFV series.
  • Choose motor and control voltage (230/3/60 or 575/3/60) to match supply voltage for the project.
  • Compare the pipe connections (MPT) and 320 psig design pressure with circuit test pressure.

Who should read it

Mechanical designers selecting air cooled fluid coolers for data centre and process cooling circuits.

Document contents

  1. Nomenclature
  2. Standard features and options
  3. Nominal performance
  4. 500 mm series specifications
  5. 800 mm series specifications
  6. Control panels
  7. Wiring diagrams

Publication details

Authors
Modine
Publisher
Modine
Year
2019
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Modine (2019). Air Cooled Fluid Coolers. Modine. https://www.modinecoolers.com/document/Modine-Fluid-Coolers-Updated-11_22_19.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.