Modulair Fan Wall Unit eDCC Datasheet
Original title Modulair Fan Wall Unit: eDCC data sheet
Modulair
The Modulair eDCC fan wall air handling unit comes in three models (eDCC018, 028, 038) of 206-413 kW (36°C air, 20/28°C water), with performance certified to EN 1216 in an accredited German laboratory.
On this page
Overview
Modulair delivers bespoke air handling units at scale in close collaboration with data-centre operators. The fan wall AHU range uses 4, 6 or 8 plug fans with EC motors; an active filter brings power factor to 0.99 and total harmonic distortion stays at or below 5%. The cooling coil has copper tubes and aluminium fins with a stainless steel condensate tray. Filters are pleated ePM10 70% (ISO 16890, M5 per EN 779) or alternatively Coarse 70% (G4).
On controls there is a valve with power, temperature and water flow control, inlet and outlet water temperature monitoring, thermal power consumption, Modbus TCP/IP, RTU and BACnet communication, monitoring through web browser or HMI and an Android/iOS app. The control philosophy is a closed-loop PID with redundancy, fault tolerance and fault detection algorithms; dual ATS power supply, a UPS for quick response and an energy meter are added. The damper is multi-blade with 3-position spring-return actuators.
The structure uses 60 mm aluminium profile with thermal break (T2, TB2, EN 1886:2007), double Magnelis ZM310 panels with 50 mm rock wool insulation. Air tightness is class L1 and mechanical resistance class D1. Front access to fans and panels eases maintenance. The system can be expanded with VCDs (volume control dampers), filters, coils and fans.
The technical table gives three models: eDCC018 (2600 mm wide, 13.89 m³/s, 206 kW), eDCC028 (3890 mm, 20.83 m³/s, 310 kW) and eDCC038 (5140 mm, 27.78 m³/s, 413 kW); height 2760 mm, length 2330 mm; airside pressure drop 100 Pa. At the second condition (38°C air, 20/30°C water) capacity is 223, 335 and 447 kW. Performance was tested in Essen by DMT GmbH (a TÜV Nord subsidiary) to EN 1216:2003-04+A1:2002.
Key points
- eDCC018, 028, 038: airflow 13.89, 20.83 and 27.78 m³/s; airside pressure drop 100 Pa.
- Condition 1 (air 36°C/30% rH with 24°C, water 20/28°C): capacity 206, 310, 413 kW; waterside loss 28, 26 and 22 kPa.
- Condition 2 (air 38°C/25% with 25°C, water 20/30°C): capacity 223, 335, 447 kW; waterside loss 22, 25, 25 kPa.
- Size: height 2760 mm, length 2330 mm, width 2600, 3890, 5140 mm.
- Weight (empty/service): 1475/1725, 1990/2340, 2480/2925 kg.
- Fan count 4, 6 or 8; EC plug fans; power factor 0.99; THD 5% or less.
- Casing EN 1886: T2, TB2, air tightness L1, mechanical resistance D1.
- Performance is certified at DMT GmbH to EN 1216; communication Modbus TCP/IP, RTU, BACnet.
Using it in design
- Read capacity from the condition matching the design air and water temperatures; the two conditions differ by about 8-10% in capacity.
- Add the waterside loss (22-28 kPa) to pump selection and keep the 20/28°C or 20/30°C fluid temperatures consistent with the chiller or dry cooler design.
- Show the dual ATS and UPS supply as separate power lines in the redundancy scheme.
- Carry width, length and service weight (up to 2925 kg) into room layout and structural load calculations.
- Compare filter class (ePM10 70% or G4) with the air quality specification.
Who should read it
Mechanical designers selecting fan wall air handling units for large data halls, and commissioning engineers.
Document contents
- Fans
- Cooling
- Filters
- Smart intelligent control
- Damper
- Technical characteristics (eDCC018, 028, 038)
- Product features
- Certified performance
Publication details
- Authors
- Modulair
- Publisher
- Modulair
- Year
- Year not stated
- Document number
- modulair-ahu-fan-wall-edcc-data-sheet-en-eu-v1
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Modulair Modulair Fan Wall Unit: eDCC data sheet. Modulair. modulair-ahu-fan-wall-edcc-data-sheet-en-eu-v1. https://modulair.info/media/2ajie2zi/spec-sheet-design-final-v3.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.