Experimental and Numerical Investigation of Airflow Organization in Modular Data Centres Utilizing Floor Grid Air Supply
Buildings (MDPI AG) · Jingping Zhao, Jianlin Wu et al.
A parametric 6SigmaDC study of a modular hall with 160 42U cabinets under raised-floor supply: raised-floor height 400-1000 mm, grille open area 20-60%, and cold-aisle, hot-aisle and dual containment compared, with airflow quality scored by entransy loss rather than RCI or SHI.
CC BY 4.0: share with attribution
On this page
Overview
The study asks how to improve the thermal environment of a modular data centre's computer room, reduce power consumption and keep servers running safely. The hall measures 26.4 m × 16.2 m × 4.5 m with 160 standard 42U cabinets (600 mm × 1200 mm) in a 10 × 16 arrangement; the design has a 600 mm raised floor and 600 × 600 mm grilles at 40% open area. The CFD model was checked against return-air temperature and velocity measurements: average relative errors were 13.24% for temperature and 10.73% for velocity at return inlet 1, and 7.73% and 7.26% at return inlet 2, with maximum errors about 15%.
Raising the floor from 600 to 800 mm cut entransy loss to 10,578.8 kW·K, and going to 1000 mm gave only a further drop to 10,533.1 kW·K, so 600-800 mm is recommended as the cost-benefit range. Raising grille open area from 20% to 40% cut entransy loss from 16,642.0 to 10,933.8 kW·K, while going on to 60% raised it to 15,064.2 kW·K; at 20% or 60% open area, cabinet intake temperatures exceeded 27 °C. A combined pattern (lower opening near the cooling units, higher at the far end, 40% mid-aisle) gave the lowest uncontained entransy loss, 8238.3 kW·K.
With cold-aisle containment entransy loss was 4450 kW·K, and with both cold and hot aisles contained it was 3500 kW·K. The paper recommends 600-800 mm floors with 40% open grilles, cold-aisle containment for typical underfloor halls, and dual containment for high density or long throws.
Limits: validation errors are fairly large, around 7-13% on average at the return grilles; entransy loss measures irreversible mixing and cannot be compared directly with common standard indicators such as RCI or SHI. Results depend on one modular hall geometry.
Key points
- The hall measures 26.4 m × 16.2 m × 4.5 m with 160 standard 42U cabinets (600 mm × 1200 mm) in a 10 × 16 arrangement; the design has a 600 mm raised floor and 600 × 600 mm grilles at 40% open area.
- Average relative errors against measurements were 13.24% for temperature and 10.73% for velocity at return inlet 1, and 7.73% and 7.26% at return inlet 2; maximum errors about 15%.
- Raising the floor from 600 to 800 mm cut entransy loss to 10,578.8 kW·K; 1000 mm gave only a further drop to 10,533.1 kW·K, so 600-800 mm is recommended.
- Raising grille open area from 20% to 40% cut entransy loss from 16,642.0 to 10,933.8 kW·K, while 60% raised it to 15,064.2 kW·K; at 20% or 60%, cabinet intake temperatures exceeded 27 °C.
- A combined pattern (lower opening near the cooling units, higher at the far end, 40% mid-aisle) gave the lowest uncontained entransy loss, 8238.3 kW·K.
- With cold-aisle containment entransy loss was 4450 kW·K, and with both cold and hot aisles contained it was 3500 kW·K.
Using it in design
- Choose raised-floor height of 600-800 mm and grille open area of about 40%; a 1000 mm floor gave only a small extra gain, and 20% or 60% open area pushed cabinet intake above 27 °C.
- Make cold-aisle containment the default in typical underfloor halls and dual containment for high density or long throws; entransy loss fell to 4450 and 3500 kW·K.
- Consider the combined pattern with lower opening near the cooling units and higher at the far end (8238.3 kW·K).
Who should read it
Modular data-centre cooling designers deciding raised-floor height, grille opening and aisle containment.
Document contents
- 1. Introduction
- 2. Materials and Methods (2.1 Experiment: experimental subjects, experimental test; 2.2 Model Building and Verification: basic assumptions, mathematical model; 2.3 Grid Division and Verification; 2.4 Boundary Conditions and Operating Conditions; 2.5 Data Processing and Entransy)
- 3. Results and Discussion (3.1 Model Verification, 3.2 Effect of Raised Floor Height, 3.3 Effect of Floor Grille Opening Rate, 3.4 Effect of Closed Cold/Hot Channels, 3.5 Evaluation: Entransy Loss)
- 4. Conclusions
Related standards
- GB 50174 Code for design of data centers
- ASHRAE TC 9.9 Thermal Guidelines for Data Processing Environments
Read the document
modular-dc-floor-grid-airflow-2024.pdf
CC BY 4.0: share with attribution
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Jingping Zhao; Jianlin Wu; Mengying Li
- Publisher
- Buildings (MDPI AG)
- Year
- 2024
- Volume
- 14
- Issue
- 9
- Pages
- 2750
- Document language
- English
- Source type
- Scientific
- Access
- Open licence (downloadable)
- Licence
- CC BY 4.0: share with attribution
- Licence evidence
- www.mdpi.com
Original licence note
PDF p.1: open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Citation
Jingping Zhao; Jianlin Wu; Mengying Li (2024). Experimental and Numerical Investigation of Airflow Organization in Modular Data Centres Utilizing Floor Grid Air Supply. Buildings (MDPI AG). 14(9), 2750. https://doi.org/10.3390/buildings14092750
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.