Mokon Iceman SC Series Single Circuit Portable Chiller System
Original title Mokon Iceman SC Series, SC 1/26 MOK8174, p.1 specifications
Mokon
Mokon's 2026 Iceman SC catalogue lists air- and water-cooled single-circuit portable chillers from 9,684 to 575,760 BTU/h for -12 to 18 °C process fluid, using low-GWP refrigerants.
On this page
Overview
The document is a two-page product sheet for Mokon's Iceman SC single-circuit portable chiller range. The series cools process fluid between 10 and 65 °F (-12 to 18 °C) using a low-GWP refrigerant, mostly with scroll compressors and reciprocating compressors on some models.
The model table pairs air-cooled (AC/AS) and water-cooled (WC/WS) variants. Capacity at 50 °F (10 °C) chilled water runs from 9,684 BTU/h (AC-1) to 575,760 BTU/h (AS-50). Small units use R-513A and the rest R-454B (A2L). Pump power is 1 to 7 1/2 hp and nominal process pressure 30 to 65 psi.
Rating conditions are given in the notes: chilled water at 2.4 GPM/ton and 90 °F (32 °C) ambient air, with water-cooled models at 85 °F (29 °C) condensing water and 3 GPM/ton. Standard equipment includes a stainless steel centrifugal pump, brazed plate evaporator, hot gas bypass, freeze and flow protection and a 1/16 DIN microprocessor controller.
The catalogue is a process-cooling product, not designed specifically for data centres, and gives limited part-load, redundancy or enclosure data. It is still a reference for sizing portable chilled water sources for laboratory, test and auxiliary cooling loads.
Key points
- Process fluid range 10 to 65 °F (-12 to 18 °C).
- Capacity from 9,684 BTU/h (AC-1) to 575,760 BTU/h (AS-50).
- Refrigerant: R-513A for AC-1 and WC-1, R-454B (A2L) for other models.
- Rating basis: 2.4 GPM/ton chilled water, 90 °F (32 °C) ambient; water-cooled 85 °F (29 °C) condensing water at 3 GPM/ton.
- Pump 1 to 7 1/2 hp; tanks 10 to 150 gallons.
- Shipping weight from 330 lb (AC-1) to 5,495 lb (AS-50/WS-50).
- Warranty: 1 year on the system, 5 years on the standard controller.
- Controller is a non-proprietary 1/16 DIN microprocessor type.
Using it in design
- Correct capacities for the design ambient temperature; the catalogue rates at 90 °F (32 °C) air and 50 °F (10 °C) chilled water.
- Check ventilation and layout requirements for the flammability class of R-454B (A2L).
- For water-cooled models, compare the 85 °F (29 °C) condensing water assumption with the dry cooler or tower water temperature.
- Match pump pressure (30 to 65 psi nominal) with process loop losses.
- If N+1 is required, plan bypass and valving to run portable units in parallel.
Who should read it
Engineers selecting small and mid-size chillers for test, laboratory and auxiliary process cooling.
Document contents
- Model and capacity table
- Standard features
- Options and accessories
- Pump curve
- Product testing and warranty
- Controls
Publication details
- Authors
- Mokon
- Publisher
- Mokon
- Year
- 2026
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Mokon (2026). Mokon Iceman SC Series, SC 1/26 MOK8174, p.1 specifications. Mokon. https://www.mokon.com/products/portable-chiller-systems/iceman-sc-series/iceman-sc-series.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.