Technical guideFree to read2021

Munters Oasis Indirect Evaporative Cooling Treats 10 MW at DigiPlex

Original title Case Study: Oasis indirect evaporative cooling treats 10 MW at DigiPlex (Fetsund, Norway)

Munters

A Munters case study from October 2021: at the DigiPlex Fetsund campus in Norway, 52 Oasis indirect evaporative cooling units serve over 10 MW of IT load at a PUE of 1.12 and cooling pPUE of 1.06.

On this page

Overview

The case study describes Munters Oasis indirect evaporative cooling (IEC) at the DigiPlex Fetsund data centre near Oslo. The system is at the heart of DigiPlex's air-to-air (A2A) cooling and is designed for a PUE of 1.12. Fifty-two Oasis units cool over 10 MW of IT power; the site can run 25,000 servers and has 4,200 m² of white space.

The principle uses two separate airstreams. Outdoor air passes over the wetted exterior of Munters' patented polymer tube indirect evaporative heat exchanger and is expelled to the atmosphere. Air drawn from the data hall hot aisle passes through the inside of the tubes, is cooled by evaporative heat transfer from the wetted surfaces and returns to the cool aisles through the under-floor void. Outdoor air never enters the hall, avoiding contamination and humidity problems that could cause corrosion.

Results stated in the document: PUE of 1.12, cooling pPUE of 1.06, 65 percent lower energy than common free-cooling solutions and 40 percent annual cost saving. The system needs one-third of the water flow of conventional economizers, can use rainwater harvesting and lowers mechanical cooling and switchgear costs. It keeps servers at 24 °C (75 °F) while halving energy use. The results belong to a Northern European climate and this site.

Key points

  1. 52 Oasis units cool over 10 MW of IT power; the site can operate 25,000 servers.
  2. White space is 4,200 m², divided into modules to fit customer requirements.
  3. Design PUE is 1.12 and cooling pPUE is 1.06.
  4. Total energy consumption falls 65 percent and annual cost 40 percent against common high-efficiency free-cooling solutions.
  5. Data hall air is fully separated from outdoor air; no outdoor air enters the hall.
  6. The system needs one-third of the water flow rate of conventional economizer systems.
  7. It holds server conditions at 24 °C (75 °F) while halving energy use.
  8. Constant temperature without mechanical cooling is targeted all year (Northern European climate).

Using it in design

  • When considering indirect evaporative cooling, verify with hourly climate data that local wet bulb distribution allows mechanical-free operation through the year.
  • Assess the air separation's benefit for contamination and humidity safety against your corrosion air quality criteria.
  • Calculate water consumption, rainwater harvesting potential and water treatment need early in the cooling design.
  • Treat PUE 1.12 and pPUE 1.06 as references for this climate and load only; run hourly simulation for your own site.
  • Compare the reduced mechanical cooling and switchgear capital cost with the cost of the evaporative units and water infrastructure.

Who should read it

Data centre designers and operators evaluating free cooling and indirect evaporative solutions.

Document contents

  1. The Munters solution
  2. A data center giant
  3. Case study summary and advantages
  4. The system explained
  5. A word from the client

Publication details

Authors
Munters
Publisher
Munters
Year
2021
Document number
DigiPlex-CS-EN-202110
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Vendor case study; no open licence stated

Citation

Munters (2021). Case Study: Oasis indirect evaporative cooling treats 10 MW at DigiPlex (Fetsund, Norway). Munters. DigiPlex-CS-EN-202110. https://datacenter.munters.com/wp-content/uploads/2026/04/DigiPlex-CS-EN-202110.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.