NEWIN NST Series Single-Cell Cross Flow Open Cooling Tower, Mechanical Table

Original title NST series Cross Flow Open Type Cooling Tower

NEWIN

The NEWIN NST series CTI-certified cross-flow open cooling tower gives a single-cell mechanical table with 1.5-11 kW motors, 1500-2400 mm fans and 1030-2480 kg dry and 2480-7390 kg wet weight.

On this page

Overview

The NEWIN NST series is an induced-draft, axial-fan, wet-cooling, cross-flow open cooling tower. It is used in small and medium industry, HVAC systems and places with lower water quality requirements; multi-cell designs are available per working condition. The product is CTI certified. The body is a galvanised steel frame with FRP shell (SUS304/316 or NWN-Armour anti-corrosion coated steel optional); heat exchange uses PVC fill with an integrated drift eliminator and air inlet grille.

Main parts are listed: a forward-blade high-strength axial fan with belt reduction drive (IP55, class F motor; two-speed or variable frequency, explosion-proof or permanent-magnet motor optional), densely spaced anti-clogging PP nozzles with gravity water distribution (optional variable-flow nozzles for even distribution at low flow), and an internal maintenance platform. Additional options include two-speed VFD, vibration cut-off switch, electronic descaler, anti-freeze automatic heating, noise reduction and an external maintenance platform.

Upgraded types are defined for working conditions: air inlet grilles on both sides to stop the PVC fill freezing in cold seasons, a noise reduction system above the fan stack, a stainless steel frame for corrosion resistance, and a full FRP solution for poor water quality with a design life up to 30 years and non-clogging L-type splash fill.

The model table gives width, length and height by code, motor power, fan diameter, connecting pipe sizes (inlet, outlet, drain, overflow, auto and manual make-up) and dry and wet weight. The table holds single-cell rows; thermal capacity, flow and rating condition are not in the table, so capacity must be taken from the CTI selection programme.

Key points

  1. Single-cell rows from NST-18-A15 through the NST-33 series: width 3310-5150 mm, length 1800-3300 mm, height 3500-4890 mm.
  2. Motor power is 1.5 to 11 kW; fan diameter 1500, 1800, 2100 and 2400 mm.
  3. Dry weight is 1030 to 2480 kg; wet (operating) weight 2480 to 7390 kg.
  4. NST-18-A15 inlet connection 100×2, outlet 125 mm; NST-33 inlet 150×2, outlet 250 mm.
  5. Body is a galvanised steel frame with FRP shell; SUS304/316 or NWN-Armour coated steel optional.
  6. CTI certified; the full FRP version has a design life up to 30 years.
  7. Options: two-speed VFD, permanent-magnet motor, anti-freeze heating, noise reduction, inlet grilles.

Using it in design

  • The table has no thermal capacity or rating condition; verify capacity from the CTI selection programme against the design wet bulb and approach.
  • Carry the wet weight into structural load and anchor calculations (for example 2480 to 7390 kg).
  • Carry connection sizes (inlet, outlet, drain, overflow, make-up) into pipework and pump selection.
  • In cold climates, specify inlet grilles and anti-freeze heating; for poor water quality consider the full FRP version.
  • Plan cell count and redundancy (N+1) separately from the single-cell table.

Who should read it

Mechanical designers and procurement engineers selecting open cooling towers for data-centre condenser water circuits.

Document contents

  1. Features
  2. Main parts
  3. Axial fan drive system
  4. PVC filler, drift eliminator and air inlet grille
  5. Water distribution
  6. Internal maintenance platform
  7. Optional additional functions
  8. Anti-freezing, noise reduction and anti-corrosion upgraded types
  9. Full FRP cooling tower solution
  10. Reference projects
  11. NST data table

Publication details

Authors
NEWIN
Publisher
NEWIN
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

NEWIN NST series Cross Flow Open Type Cooling Tower. NEWIN. https://www.newincoolingtower.com/product/nst-series-open-type-cooling-tower-.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.