Data Centers of the Future: Powered by Superconducting Cables for Scalable and Sustainable Growth

Nexans · Gabriel Hajiri

A Nexans article on the possibility of solving medium- and low-voltage internal distribution in gigawatt-scale data centres with superconducting cables, and fault current with superconducting limiters (SFCL).

On this page

Overview

The article says that since 2010 the number of global internet users has more than doubled to 5.5 billion in 2024, traffic has grown 25-fold, and data centres have gone from tens or hundreds of megawatts into the gigawatt era. Data-centre electricity use is today about 1-1.5% of the global total and, if current trends continue, could rise to 10% by 2030. It argues that conventional copper-cable internal distribution adds space, cooling and capital burden.

The problem is described at two voltage levels. At medium voltage a next-generation data centre may need 100-400 MW per data hall, requiring a very large number of parallel buried cables: an example is given of 36 large-section (600 mm²) cables for six 300 MW data halls. At low voltage (480 V or 600 V), delivering 100-400 MW means very high currents, with many cables inside the data hall, EMC constraints and thermal load.

The superconducting answer is given as four advantages: zero resistance means virtually no energy loss and efficiency above 99.99%; second-generation high-temperature superconducting (2G HTS) tapes carry up to 500 times the current of copper (a tape 4 mm x 0.5 mm can carry 200 A) and a 300 MW data hall could be fed by a single superconducting cable under 250 mm in diameter; the magnetic shield produces no external field; and the vacuum-insulated cryostat does not release heat to the surroundings. At low voltage a single cable at 480/600 V is said to carry up to 10 kA.

The article also describes superconducting fault current limiters (SFCLs): in normal operation resistance is zero, and when fault current exceeds the nominal limit the superconductor immediately changes to a resistive state and sharply reduces the fault current. It says that on a data-centre grid with medium-voltage fault currents of 20 kA to over 50 kA, an SFCL can cut these values in half or more. The document is a manufacturer perspective article: it describes a possible technology direction, without establishing a commissioned data-centre design or a validated whole-system efficiency model.

Key points

  1. Global internet users reached 5.5 billion in 2024; traffic has grown 25-fold since 2010.
  2. Data-centre electricity use is about 1-1.5% of the global total; at current trends it could reach 10% by 2030.
  3. Next-generation data hall of 100-400 MW; example of 36 medium-voltage 600 mm² cables for six 300 MW data halls.
  4. Delivering 100-400 MW at low voltage (480/600 V) needs very high currents and many cables.
  5. 2G HTS tape carries up to 500 times the current of copper; a 4 mm x 0.5 mm tape can carry 200 A.
  6. A 300 MW data hall could be fed by a single superconducting cable under 250 mm in diameter; one cable at 33 kV in place of 36 copper cables.
  7. At low voltage a single superconducting cable can carry up to 10 kA.
  8. An SFCL has zero resistance in normal operation, becomes resistive during a fault, and can halve or more of medium-voltage fault currents of 20-50 kA and above.
  9. External high/medium-voltage connections are treated separately from internal low-voltage distribution.

Using it in design

  • In gigawatt-scale projects calculate the internal medium-voltage cable count and buried-corridor need; record the superconducting cable only as an option to be evaluated.
  • On high-fault-current grids study the SFCL together with selective coordination and breaker short-circuit rating decisions; the article describes the effect as halving or more, and a project calculation is needed.
  • In low-voltage internal distribution calculate the thermal load and HVAC need of copper cable with your own site data; the article says these losses reduce site efficiency.
  • Treat the reliability, maintenance and operating cost of the cooling (cryogenic) infrastructure as a separate risk item; the article does not discuss them in detail.
  • Since it is a manufacturer narrative, verify these claims in an independent feasibility study and supplier quotations.

Who should read it

Electrical designers evaluating internal distribution architecture and fault current management in very high-power data centres.

Document contents

  1. Meeting the demands of an expanding digital world
  2. Powering next-generation data centers: medium and low voltage
  3. Digital infrastructure in numbers
  4. Superconductivity for next-generation data centers
  5. Enabling resilient, sustainable operations: SFCL
  6. Empowering the future of digital infrastructure

Publication details

Authors
Gabriel Hajiri
Publisher
Nexans
Year
2025
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

Public manufacturer document or page inspected. No document-specific redistribution permission established; retain metadata and original short summaries only.

Citation

Gabriel Hajiri (2025). Data Centers of the Future: Powered by Superconducting Cables for Scalable and Sustainable Growth. Nexans. https://nexans.com/perspective/data-centers-of-the-future-powered-by-superconducting-cables-for-scalable-and-sustainable-growth

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.