Kılavuz Notu: Yapı Malzemeleri Yönetmeliği
Nexans Türkiye
A 20-page Turkish-language guidance note from Nexans Türkiye on how the Construction Products Regulation (CPR, 305/2011) applies to cables: seven reaction-to-fire classes (Aca to Fca), additional criteria for smoke, flaming droplets and acidity, mandatory CE marking from 1 July 2017, and class B2ca-s1, d1, a1 as the sector recommendation for data-centre buildings.
On this page
Overview
The guide describes the purpose of the CPR as a common technical language that allows construction products to move freely within the European Economic Area. Its scope covers power, control and communication cables installed permanently in buildings and other civil works and subject to reaction-to-fire requirements. Two properties are expected of cables: reaction to fire and release of dangerous substances. Harmonised standards for fire-resistant cables (those that keep circuit integrity) were still under development when the document was written, so those cables continue to be assessed under national standards.
The reaction-to-fire classification rests on Decision 2006/751/EC and has seven classes: Aca, B1ca, B2ca, Cca, Dca, Eca and Fca. The main criteria are heat release and flame spread. Three additional criteria are defined for classes B1ca, B2ca, Cca and Dca: smoke production (s1a to s3, where s1a means visibility stays above 80%), flaming droplets (d0 to d2) and acidity of combustion gases (a1 to a3). The smoke and acidity criteria focus on the quality of emissions, which is decisive during evacuation.
Three systems of assessment and verification of constancy of performance apply to cables. System 1+, the strictest, includes initial type testing, sample testing and continuous surveillance of factory production by a notified certification body, and is mandatory for the upper classes. In System 3 a third-party laboratory performs the initial type test; in System 4 testing and production control rest with the manufacturer. The manufacturer issues a Declaration of Performance and affixes the CE mark. The legal timetable is explicit: the regulation took effect for cables on 10 June 2016 and the transition period ended on 1 July 2017.
The guide summarises the obligations of manufacturers, importers and distributors by article number and shows the information required on a label using an example. The last section recommends cable classes for Türkiye by building type: Eca for low buildings, Cca-s1, d2, a1 for mid-height and high-rise buildings, and B2ca-s1, d1, a1 for buildings with a structure height above 51.50 m, hospitals and data-centre buildings. The document states plainly that this table is not part of any regulation and is offered as sector advice.
Key points
- There are seven reaction-to-fire classes for cables under the CPR: Aca, B1ca, B2ca, Cca, Dca, Eca, Fca; the ca subscript marks the class as cable specific.
- Additional criteria apply only to B1ca, B2ca, Cca and Dca: smoke (s1, s1a, s1b, s2, s3), flaming droplets (d0, d1, d2) and acidity (a1, a2, a3).
- s1a is the lowest smoke class, with visibility above 80%; d0 means no flaming droplets and a1 very low corrosivity.
- The regulation took effect for cables on 10 June 2016; after 1 July 2017 all cables for construction works must carry CE marking under the CPR.
- Three verification systems apply to cables: System 1+ (strictest, with notified body surveillance), System 3 and System 4.
- The label carries the manufacturer's name and address, product identification code, reaction-to-fire class, reference to EN 50575, notified body number, Declaration of Performance number and intended use.
- In the recommendation table for Türkiye, data-centre buildings and IT server buildings inside a structure fall under class B2ca-s1, d1, a1.
- Per the application notes, no cable in a structure may be of a lower class than that set for the building; fibre optic cables are to be Eca where Eca power cables are used and Cca-s1, d2, a1 in all other areas.
Using it in design
- Write the reaction-to-fire class with its additional criteria in full in the cable specification (B2ca-s1, d1, a1, for example); the term halogen-free alone is not a sufficient definition.
- In data-centre buildings, specify power and extra-low-voltage cables in the same class and give fibre optic cables their own line.
- At delivery, check the Declaration of Performance for each cable type and the notified body number on the label.
- For circuits feeding generators, fire pumps and emergency systems, define the fire-resistance requirement separately from the reaction-to-fire class, under the national standards in force.
- Determine building class and height from the definitions in the Turkish Regulation on Fire Protection of Buildings, and use the recommendation table as a design target above the legal minimum.
Who should read it
Electrical engineers writing cable specifications, fire safety consultants, procurement teams and contractors.
Document contents
- Bölüm 1: Yapı Malzemeleri Yönetmeliği
- A. Kapsam
- B. Kablo performansları: yangına tepki
- C. Performansların değerlendirilmesi: PDDD sistemleri
- Bölüm 2: Yasal şartlar
- A. Performans Beyanı ve etiketlendirme
- B. İktisadi işletmelerin yasal zorunlulukları
- Bölüm 3: Nexans sizi nasıl destekler?
- Türkiye için tavsiye notu: kablolar için yapı tiplerine göre performanslar
Related standards
- EN 50575
Publication details
- Authors
- Nexans Türkiye
- Publisher
- Nexans Türkiye
- Year
- Year not stated
- Document number
- Turkish CPR guide; 20 pages
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
Public publisher source inspected on 2026-11-16. No document-specific redistribution permission established. PDF downloaded and text extracted; broken font encoding required OCR of pages 6 and 19. Original year not established. Historical legal-transition descriptions are not current compliance evidence.
Citation
Nexans Türkiye Kılavuz Notu: Yapı Malzemeleri Yönetmeliği. Nexans Türkiye. Turkish CPR guide; 20 pages. https://www.nexans.com.tr/tr/dam/jcr%3Af79408a5-7b4c-4982-a6e7-b45d03ed0b13/NEXANS%20CPR%20K%20lavuz%20Notu_5.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
