StandardCitation2024

NFPA 75: Standard for the Fire Protection of Information Technology Equipment

NFPA

The US standard for fire protection of IT equipment areas; its 2024 edition adds provisions for immersion cooling equipment.

On this page

Overview

NFPA 75 is the US standard for protecting IT equipment areas, available as free read-only access after registration. It offers two paths: a prescriptive path or a documented risk/performance-based approach, and the risk assessment in Chapter 4 can justify alternative protection. The facts on this page come not from the standard itself but from publicly available engineering-press summaries, notably CSE magazine.

The structural requirements are concrete: IT equipment rooms are separated from other occupancies by construction rated at least 1 hour, with 3/4-hour doors. On sprinklers, IT areas in sprinklered buildings must be sprinklered; in non-sprinklered buildings, sprinklers and/or a gaseous clean agent are used and water mist may be considered. For early warning, automatic smoke detection per NFPA 72 is required (Sec. 8.2).

A raised-floor void that holds combustibles or cables needs sprinkler or gaseous protection, and if only an under-floor gaseous system is used, the agent must be CO2 or an inert gas. The standard also addresses emergency power off (EPO) and utilities. The 2024 edition added requirements for ITE immersion cooling equipment. The authority having jurisdiction (AHJ) has the final word.

Key points

  1. IT rooms separated from other occupancies by at least 1-hour rated construction; doors 3/4-hour.
  2. Sprinklered buildings: IT areas sprinklered; non-sprinklered: sprinklers and/or gaseous clean agent (water mist may be considered).
  3. Automatic smoke detection per NFPA 72 is required for early warning (Sec. 8.2).
  4. A raised-floor void with combustibles or cables needs sprinkler or gaseous protection; under-floor-only gaseous means CO2 or inert gas.
  5. The 2024 edition adds requirements for immersion cooling equipment.
  6. The Chapter 4 risk assessment can justify alternative protection.

Using it in design

  • Defaults for white space in NFPA jurisdictions: 1-hour rated walls, 3/4-hour doors and rated fire/smoke dampers at penetrations.
  • Detection default is NFPA 72 smoke plus optional VESDA; suppression default is pre-action sprinkler with optional clean agent (check room integrity and hold time).
  • If immersion tanks are placed, flag the NFPA 75-2024 immersion provisions.
  • Add an "AHJ governs" note to every output.

Who should read it

Engineers designing fire protection for an IT hall under US codes.

Related standards

  • NFPA 75
  • NFPA 72
  • NFPA 13
  • NFPA 2001
  • NFPA 76

Publication details

Authors
NFPA
Publisher
NFPA
Year
2024
Document number
NFPA 75-2024
Document language
English
Source type
Standard
Access
Citation only
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

NFPA (2024). NFPA 75: Standard for the Fire Protection of Information Technology Equipment. NFPA. NFPA 75-2024. https://www.nfpa.org/codes-and-standards/nfpa-75-standard-development/75

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Standards pre-assessment in SoSo CAD

Run TS EN 50600 and Tier pre-checks on the model, with missing inputs and items for engineering review listed separately.

Selected rule packs and findings in the SoSo CAD standards panel

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.