Technical guideFree to read2022

Nihon Spindle KG Series Cooling Tower Heat Rejection Capacity (KG-L Line)

Original title KG-L Heat Rejection Capacity: IP units

Nihon Spindle

Nihon Spindle heat rejection capacity tables for KG-L line normal-type cooling towers: circulating water flow (gpm) at 49 operating conditions, wet bulb 50-90 °F.

On this page

Overview

The document is a wide selection table giving heat rejection capacity in IP units for the standard type and the VR stack version of the Nihon Spindle KG series KG-L line cooling towers. Each model is listed with the circulating water flow (gpm) it can handle at a given condition; model codes span KG-LE31, KG-LG31/41/51/61, KG-LJ31/41/51/61 and KG-LN41/51/61 with letter sizes from D to N.

There are 49 reference conditions. Wet bulb runs 50, 55, 60, 65, 70, 75, 80, 85 and 90 °F, inlet water 67-117 °F, outlet water 57-102 °F, range 9-15 °F and approach 7-12 °F. Additional conditions include near-SI points such as 89.6/80.6 °F water and 69.8-82.4 °F wet bulb. Blank cells mean the condition is outside that model's scope.

Flow values are capped at an upper limit (3 288 gpm in the table). For example the KG-LG61-N reaches the highest flows at high wet bulb and wide approach conditions. The document is a selection table with no method, energy consumption or noise information.

For a data centre designer, the table is used once design wet bulb and required approach/range are set, to check a tower model's flow adequacy. Regional summer wet bulb together with approach directly drives the selection.

Key points

  1. The table gives flow in gpm in IP units for the KG-L line (normal type) and the VR stack version of the KG series.
  2. 49 reference conditions are defined; wet bulb is swept from 50 to 90 °F in 5 °F steps.
  3. Range is 9-15 °F and approach 7-12 °F; the most common pairs are 10/7, 10/10, 10/12, 15/7 and 15/12 °F.
  4. Inlet water temperatures span 67 to 117 °F and outlet water 57 to 102 °F.
  5. Series are KG-LE31, KG-LG31/41/51/61, KG-LJ31/41/51/61 and KG-LN41/51/61, with sizes separated by letters D to N.
  6. A blank cell means the condition is outside the model's scope; the upper flow limit in the table is 3 288 gpm.
  7. For the same model, flow capacity falls as wet bulb rises or approach shrinks.

Using it in design

  • Set the site design wet bulb (for example a 0.4 percent summer value) and required tower outlet water temperature, then read model flow from the nearest condition column.
  • A lower approach (for example 7 °F) needs a larger tower; choose approach against chiller or free-cooling circuit targets.
  • When checking flow adequacy, leave separate capacity margin for twin towers or cell redundancy (N+1).
  • Document unit conversions (gpm, °F) when converting table values to project units.
  • The table excludes energy and noise; take fan power and sound level from manufacturer data separately.

Who should read it

Mechanical designers selecting cooling towers for data centre condenser water circuits.

Document contents

  1. KG series heat rejection capacity: KG-L line (normal type), standard type
  2. KG-L line with VR stack, circulating water flowrate (gpm)

Publication details

Authors
Nihon Spindle
Publisher
Nihon Spindle
Year
2022
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Nihon Spindle (2022). KG-L Heat Rejection Capacity: IP units. Nihon Spindle. https://www.spindle.co.jp/en/cooling_tower/pdf4/2022_3-1-2_R7.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Cooling capacity in SoSo CAD

Check zone heat loads, installed capacity and the capacity left with the largest unit out, as part of the design.

Zone heat loads and capacity balance in the SoSo CAD cooling workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.