Technical guideFree to read2012

NIST/SEMATECH e-Handbook of Statistical Methods: Chapter 8, Assessing Product Reliability

Original title NIST/SEMATECH e-Handbook of Statistical Methods

NIST / SEMATECH · NIST/SEMATECH

The handbook's reliability chapter explains the exponential lifetime and independent-component series, parallel and r-out-of-n models, and states the assumption behind each probability calculation.

On this page

Overview

The chapter gives four core formulas. For independent components that must all survive, system reliability is the product of the component reliabilities. For independent parallel components where one survivor suffices, system failure probability is the product of the component failure probabilities. For n identical independent components needing at least r survivors, reliability is the sum of the binomial probabilities for r through n survivors.

With a constant failure rate lambda, lifetime reliability is exp(-lambda x time) and mean time to failure (MTTF) is 1/lambda. For instance, two independent components of reliability 0.9 give 0.81 in series and 1 - 0.1 x 0.1 = 0.99 in parallel; these numbers are a simple application of the formulas, not an example from the document. Exponential life means no ageing is modelled.

The limit matters: the chapter supplies no failure data for a particular facility and does not model common-cause failures. The formulas hold only if components are independent; two 'redundant' units fed by the same generator line violate that assumption. Results are therefore an assumption-dependent calculation, not proof of achieved service availability. In short, the formulas are a calculator, not a data source; the failure rates must come from the user and their source.

Key points

  1. For independent components that must all survive, system reliability is the product of individual reliabilities.
  2. For independent parallel components where one survivor suffices, system failure probability is the product of component failure probabilities.
  3. For n identical independent components needing at least r survivors, reliability is the sum of binomial probabilities from r through n.
  4. With constant failure rate lambda, reliability is exp(-lambda x time) and MTTF is 1/lambda.
  5. The chapter gives no facility-specific failure data and does not model common-cause failures.

Using it in design

  • Make independence and capacity assumptions required inputs of every reliability calculation and keep input provenance.
  • Use series, parallel and r-out-of-n blocks as a numeric check of N, N+1 and 2N redundancy schemes.
  • Do not present the output as achieved service availability; add a separate note on common-cause failure.

Who should read it

Designers calculating the reliability of redundancy schemes and engineers auditing a calculation's assumptions.

Publication details

Authors
NIST/SEMATECH
Publisher
NIST / SEMATECH
Year
2012
Document number
Chapter 8, Assessing Product Reliability
Document language
English
Source type
Government / public
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document

Citation

NIST/SEMATECH (2012). NIST/SEMATECH e-Handbook of Statistical Methods. NIST / SEMATECH. Chapter 8, Assessing Product Reliability. https://doi.org/10.18434/M32189

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Redundancy scenarios in SoSo CAD

Compare normal operation with equipment failures and see served loads and capacity shortfalls in the same view.

Normal operation and failure scenario comparison in SoSo CAD

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.