Server Component Immersion Material Compatibility Testing, Version 1.5 (June 2026)
Open Compute Project Foundation · Brian Kinkade (FUCHS Lubricants), Beau Van Vaerenbergh (Oleon) et al.
An OCP guideline defining the test flow that checks whether server components such as cables, connectors, optics, plastics, elastomers and adhesives and dielectric immersion fluids degrade each other. It is used to set up a qualification step for IT hardware and fluids in an immersion design.
CC BY-SA 4.0: share with attribution under the same licence
On this page
Overview
Server OEMs integrate components from many vendors, and each component is built from different materials such as plastics, elastomers, metals and adhesives. Exposure to a dielectric fluid can degrade a component's materials; a component can also contaminate the fluid, and that contamination can harm other parts through secondary effects without changing the tested component's own performance. The guideline manages this two-way risk with one test flow.
The flow runs through component and fluid selection with a criticality assessment, baseline characterisation, heat soak, visual and physical inspection, functional testing, failure root-cause analysis and fluid analysis. A pristine component is stored as a control in every trial, and a fluid control is heated without the component. Multiple samples are recommended so that standard deviation can be reported.
For single-phase fluids the recommended heat soak is 80 +/- 2 degC for 14 days. For two-phase fluids, small components are tested by Soxhlet extraction or under boiling conditions, and larger ones in a heated two-phase tank; OCP fluid guidelines run Soxhlet continuously for 48 hours, extendable to 7 days. In a two-phase tank the sample-to-fluid mass ratio should be at most 1%. Fluid analysis measures appearance, turbidity, water, metal ions, organic acids, particles and acid number using ASTM and IEC methods.
Version 1.5 removed the mandatory must and shall wording; the document sets no acceptance thresholds, certification criteria or qualification procedure, and results should not be read as certifying compatibility or establishing service life. Material was added to the title because IT design considerations outside its scope exist. System-level thermochemical reliability belongs to a separate OCP workstream.
Key points
- Single-phase heat soak: 80 +/- 2 degC for 14 days, with a fluid-only control sample and a pristine component control in every trial.
- For two-phase fluids, Soxhlet extraction on small components runs 48 hours continuously and may extend to 7 days; sample-to-fluid mass ratio in a two-phase tank is at most 1%.
- Three fluid samples are needed: component control (not heated), fluid control (heated without component) and fluid after component soak.
- Fluid analysis covers appearance (ASTM D1524), turbidity, water (IEC 60814, ASTM D1533), particles (ISO 4406), acid number (ASTM D974), metal ions and organic acids; water can lower dielectric properties and trigger metal corrosion.
- Component criticality is classed along safety, power, signal-integrity and performance axes; the guide tracks sheath stiffening and insulation cracking in cables, EPDM seal swelling and PVC stiffening in optical assemblies.
- Visual inspection calls for before-and-after photographs with the same camera, positioning and a scale bar, looking for colour change, cable routing, label loss and corrosion signs.
- Version 1.5 removed mandatory language and turned the document into guidance without acceptance thresholds.
- Performance test examples are provided for cable and connector assemblies and for optical transceivers.
Using it in design
- In an immersion design, require evidence of fluid compatibility for each IT component in the procurement specification, and classify cables, connectors, optics and seals by criticality (safety, power, signal) first.
- Include the 80 degC, 14-day heat soak and a fluid control sample in the qualification plan, and carry the test duration and laboratory cost into the commissioning schedule.
- In fluid selection and the operating plan, address contaminants leaching from components: schedule periodic fluid analysis for water, acid number and metal ions.
- Keep in mind that the guideline sets no thresholds: define acceptance criteria for the project using the hardware manufacturer's production acceptance specification.
- Complement these component tests with a separate thermochemical reliability assessment for system-level reliability in the immersion environment.
Who should read it
Engineers designing or operating immersion cooling, server and component manufacturers, dielectric fluid suppliers and test laboratories.
Document contents
- Introduction (related documents, scope and non-requirements)
- Compliance with Open Compute Project Tenets
- Component & Fluid Selection
- Baseline Setting
- Heat Soak Protocols (single-phase and two-phase fluids)
- Component Testing (visual, physical, functional, root cause analysis)
- Fluid Analysis (fluid requirements, contamination analysis)
- Component Performance Test Examples (cable and connector assemblies, optical transceivers)
- Conclusion, glossary and references
Related standards
- OCP Base Specification for Immersion Fluids
- OCP Material Compatibility in Immersion Cooling
- IEC 60814
Read the document
ocp-immersion-component-compatibility-testing-v1-5-2026.pdf
CC BY-SA 4.0: share with attribution under the same licence
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Brian Kinkade (FUCHS Lubricants); Beau Van Vaerenbergh (Oleon); Samantha Yates (Intel)
- Publisher
- Open Compute Project Foundation
- Year
- 2026
- Document number
- Version 1.5
- Document language
- English
- Source type
- Industry body
- Access
- Open licence (downloadable)
- Licence
- CC BY-SA 4.0: share with attribution under the same licence
- Licence evidence
- www.opencompute.org
Original licence note
Creative Commons Attribution-ShareAlike 4.0 International; licence verified from the licence statement in the document itself. Attribution to the authors and publisher is kept; adaptations must keep the same licence.
Citation
Brian Kinkade (FUCHS Lubricants); Beau Van Vaerenbergh (Oleon); Samantha Yates (Intel) (2026). Server Component Immersion Material Compatibility Testing, Version 1.5 (June 2026). Open Compute Project Foundation. Version 1.5. https://www.opencompute.org/documents/ocp-component-compatibility-testing-guidelines-v1-5-final-june-5-2026-pdf/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
