Warranty Guidelines for Immersion Cooled Technology Components, Equipment and Systems, Revision 1.0 (26 April 2024)
Open Compute Project Foundation · Rich Lappenbusch (Super Micro Computer, editor), Michael Cordle (Seagate, editor emeritus) et al.
An OCP guideline explaining why warranties for immersion-cooled IT equipment are offered inconsistently and how buyers and sellers can manage that risk. It is relevant to procurement and owner risk when an immersion design is chosen.
CC BY-SA 4.0: share with attribution under the same licence
On this page
Overview
The guideline is the product of the OCP Immersion Warranty workstream, chartered in January 2023. Focus is only on IT equipment and components (CPU, GPU, NPU, ASIC and the like), and the coolants considered are those meeting the OCP base specification for immersion fluids. Warranty law is summarised for the EU and US: Directive (EU) 2019/771 on contracts for the sale of goods, applicable since 1 January 2022, and the Magnuson-Moss Warranty Act in the US. The document notes that accounting and legal standards vary by country and describes its content as illustrative and suggestive.
The core argument is that almost all IT warranties today treat air cooling as the accepted, often only, use case. The quick route to covering immersion is therefore to extend an existing air-cooling warranty into a list of fluids, with air one of them. Air itself assumes a level of cleanliness, humidity and pollution control; the document argues that particle filtering, moisture control and contamination monitoring are needed for every coolant.
Immersion risk factors and warranty challenges are listed with a proposed solution for each: fluid-component compatibility (elastomers and plastics first), temperature limits (in one example a board limits operation above 35 degC while immersion applications prefer 40 to 60 degC), maintenance requirements, inconsistent warranty periods (1 to 7 years for IT, a 10 to 20 year wish for the fluid), lack of data, a fear of increased claims, fluid and operational variability, and material and hardware variability. The lack of data and of MTBF figures is the main reason warranties are uncertain.
Recommendations include placing warranty statements in all sales contracts as standard machine-readable tables, aligning part numbering and serial-number nomenclature with UN and ISO conventions, and limiting the warranty clause to fluids that meet the OCP specification. The annexes contain a schedule of warranties and a template warranty statement covering scope, exclusions, claims, remedies, transferability, limitations and governing law.
Key points
- The workstream was chartered in January 2023; scope is IT components and equipment only, and fluids are limited to those meeting the OCP Immersion Fluid base specification.
- In the EU, Directive (EU) 2019/771 has applied since 1 January 2022; in the US, warranties are governed by the Magnuson-Moss Warranty Act.
- Warranty uncertainty is attributed to the lack of MTBF data and wide variation in immersion systems, fluids and deployment methods.
- IT warranty periods typically run from 1 to 7 years; the industry has voiced a wish for 10 or 20 years for the fluid.
- Temperature-limit example: one board's warrantied range limits operation above 35 degC while most immersion applications prefer 40 to 60 degC.
- Warranty statements should be in all sales contracts as standard machine-readable data tables for immersion environments.
- It recommends limiting the warranty clause to fluids meeting the OCP specification and favouring broadly compatible materials.
- The template warranty statement includes scope, exclusions, claims, remedies, transferability, limitations, governing law and contact sections.
- Experiments aimed at a 7-year IT life are said to yield information for shorter periods too.
Using it in design
- In an immersion design, add a written clause to the purchase specification stating that the hardware warranty applies to the chosen fluid and operating temperature range.
- Compare the operating-temperature target (for example 40-60 degC) with the narrowest component warranty range; build a range table for tank, fluid, board, CPU, memory, NIC and cable.
- Limit fluid selection to those meeting the OCP specification and request the hardware manufacturer's compatible-fluid list in writing.
- Assign fluid-quality monitoring and maintenance responsibility explicitly to the operator or service provider in the contract; use the exclusions and claims conditions of the template as a checklist.
- Keep part and serial-number records in machine-readable form to support traceability in warranty claims.
Who should read it
Operators buying immersion cooling, server and system manufacturers, contracts and legal teams, and risk managers.
Document contents
- Introduction (charter, scope, requirements, deliverables)
- Warranty Information (government regulations, business guidance, reliability)
- Warranties for Immersion Cooling (immersion cooling, immersion risk factors, warranty challenges)
- Glossary and references
- Schedule of Warranties
- Warranty Statement Template (coverage scope, what is covered, what is not covered, claims, remedies, transferability, limitations, governing law, contact)
Related standards
- OCP Base Specification for Immersion Fluids
- OCP Material Compatibility in Immersion Cooling
- Directive (EU) 2019/771
Read the document
ocp-immersion-warranty-guidelines-2024.pdf
CC BY-SA 4.0: share with attribution under the same licence
The document is provided unaltered because its licence permits redistribution.
Publication details
- Authors
- Rich Lappenbusch (Super Micro Computer, editor); Michael Cordle (Seagate, editor emeritus); OCP Immersion Warranty workstream members
- Publisher
- Open Compute Project Foundation
- Year
- 2024
- Document number
- Revision 1.0
- Document language
- English
- Source type
- Industry body
- Access
- Open licence (downloadable)
- Licence
- CC BY-SA 4.0: share with attribution under the same licence
- Licence evidence
- www.opencompute.org
Original licence note
Creative Commons Attribution-ShareAlike 4.0 International; licence verified from the licence statement in the document itself. Attribution to the authors and publisher is kept; adaptations must keep the same licence.
Citation
Rich Lappenbusch (Super Micro Computer, editor); Michael Cordle (Seagate, editor emeritus); OCP Immersion Warranty workstream members (2024). Warranty Guidelines for Immersion Cooled Technology Components, Equipment and Systems, Revision 1.0 (26 April 2024). Open Compute Project Foundation. Revision 1.0. https://www.opencompute.org/documents/2024-04-26-ocp-warranty-guidelines-for-immersion-cooled-technology-components-v1-00-pdf-1/
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.